Configuration using the PC |
programming is always available if there is no Access code in the unit.
This code can be 1 to 7 digits in length and may use any of the 16 DTMF digits including A, B, C, and D.
Default Access Code: an empty string.
Shift Change Code
The shift that is being used at any particular time is determined by the last time that a Shift Change Code message was received. The Cv2 retains the current shift when it is powered down and returns to that shift when power is restored. Each time a Shift Change Code is received, the shift advances by one. If the Cv2 is currently set to shift 4 and the change code is received, it will go to the shift 1 setting.
This code can be 1 to 7 digits in length and may use any of the 16 DTMF digits including A, B, C, and D.
Default Shift Change Code: an empty string.
Temporary Acknowledge Time
Temporary Acknowledge time is used as a safeguard with the Acknowledge Code. When the Temporary Acknowledge Time is set to Off it has no effect on Cv2 operations. Normally, receipt of the Acknowledge Code for a group will cause that group to cease alarm reporting activities until a new alarm is detected. When this control is set to any of the four available times (30, 60, 120 and 240 minutes), receipt of the Acknowledge Code, with the digit ‘#’ appended to it, will cause the alarm activities to cease only for the time period set by the Temporary Time. After this timer expires, if the alarm condition has not been removed, the Cv2 will continue alarm functions as though the Acknowledge Code had not been received.
Default Temporary Acknowledge Time: Off
Call Progress
When Call Progress is enabled, the Cv2 will wait for the called party to speak before beginning the voice announcement. When Call Progress is enabled, there should not be any Answer commands directly following a Dial command in the directories. This will cause the Cv2 to look for a voice response twice in a row and may prevent alarm announcements.
Default Call Progress: disabled
3.5.6 Configuration Programming
Three types of data can be transferred between the Cv2 and the programming PC. The programming cable must be connected between the PC and the Cv2 before any data transfer is initiated. Select the correct COM port for the attached cable in the Serial Port box.
While the serial cable is attached, the Cv2 will be in programming mode and will not be
B1272M001 | BARNETT ENGINEERING LTD. | ProTalk Cv2 |