PERFORMANCE DATA (cont)
FAN PERFORMANCE Ð
580D048 (4 TONS) Ð STANDARD MOTOR (DIRECT DRIVE)
Air¯ow |
|
| Low Speed |
|
|
|
|
| High Speed |
|
|
| ||
| 208 v |
|
| 230, 460, 575 v |
| 208 v |
|
| 230, 460, 575 v | |||||
(Cfm) |
|
|
|
|
|
| ||||||||
| Esp | Bhp | Watts | Esp |
| Bhp | Watts | Esp | Bhp | Watts | Esp |
| Bhp | Watts |
1200 | 0.75 | 0.41 | 458 | 0.81 |
| 0.45 | 506 | 0.87 | 0.51 | 572 | 0.92 |
| 0.56 | 632 |
1300 | 0.68 | 0.42 | 471 | 0.74 |
| 0.46 | 521 | 0.79 | 0.52 | 589 | 0.85 |
| 0.58 | 651 |
1400 | 0.60 | 0.45 | 503 | 0.66 |
| 0.49 | 556 | 0.71 | 0.54 | 616 | 0.77 |
| 0.60 | 681 |
1500 | 0.51 | 0.47 | 536 | 0.58 |
| 0.52 | 593 | 0.64 | 0.56 | 631 | 0.70 |
| 0.62 | 698 |
1600 | 0.42 | 0.49 | 557 | 0.49 |
| 0.54 | 616 | 0.56 | 0.58 | 654 | 0.63 |
| 0.64 | 723 |
1700 | 0.32 | 0.52 | 584 | 0.39 |
| 0.57 | 646 | 0.48 | 0.60 | 678 | 0.55 |
| 0.66 | 750 |
1800 | 0.21 | 0.54 | 610 | 0.29 |
| 0.60 | 674 | 0.41 | 0.62 | 698 | 0.48 |
| 0.68 | 772 |
1900 | 0.09 | 0.56 | 629 | 0.18 |
| 0.62 | 696 | 0.33 | 0.64 | 720 | 0.41 |
| 0.70 | 796 |
2000 | Ð | Ð | Ð | 0.06 |
| 0.65 | 731 | 0.26 | 0.66 | 744 | 0.33 |
| 0.73 | 823 |
|
| LEGEND |
Bhp | Ð Brake Horsepower Input to Fan | |
Esp | Ð | External Static Pressure (in. wg) |
FIOP | Ð |
|
NOTES:
1.Values include losses for ®lters, unit casing, and wet coils. See page 52 for accessory/FIOP static pressure information.
2.Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with con®dence. Using your fan motors up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. See
3.Use of a
580D048 (4 TONS) Ð ALTERNATE MOTOR (BELT DRIVE)*
Air¯ow |
|
|
|
|
|
|
|
|
|
|
| External Static Pressure (in. wg) |
|
|
|
|
|
|
|
|
| |||||||||||
| 0.1 |
|
| 0.2 |
|
|
|
| 0.3 |
|
|
|
|
| 0.4 |
|
|
|
|
| 0.6 |
|
|
|
|
| 0.7 |
|
| 0.8 |
| |
(Cfm) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||
| Rpm | Bhp | Watts | Rpm | Bhp | Watts | Rpm | Bhp | Watts | Rpm | Bhp | Watts | Rpm | Bhp | Watts | Rpm | Bhp | Watts | Rpm | Bhp | Watts | |||||||||||
1200 | 569 | 0.18 | 189 | 641 | 0.23 | 242 |
| 701 |
| 0.29 |
| 299 |
| 761 |
| 0.34 |
| 357 |
| 859 |
| 0.46 |
| 483 |
| 901 |
| 0.52 | 546 | 943 | 0.58 | 609 |
1300 | 604 | 0.22 | 231 | 673 | 0.28 | 294 |
| 731 |
| 0.34 |
| 352 |
| 788 |
| 0.39 |
| 410 |
| 887 |
| 0.52 |
| 546 |
| 928 |
| 0.59 | 615 | 968 | 0.65 | 683 |
1400 | 640 | 0.27 | 284 | 705 | 0.33 | 347 |
| 761 |
| 0.39 |
| 410 |
| 817 |
| 0.45 |
| 473 |
| 914 |
| 0.59 |
| 620 |
| 955 |
| 0.66 | 688 | 996 | 0.72 | 757 |
1500 | 676 | 0.32 | 336 | 738 | 0.38 | 399 |
| 793 |
| 0.45 |
| 468 |
| 847 |
| 0.51 |
| 536 |
| 940 |
| 0.65 |
| 683 |
| 982 |
| 0.73 | 767 | 1024 | 0.81 | 851 |
1600 | 713 | 0.38 | 399 | 772 | 0.44 | 462 |
| 825 |
| 0.51 |
| 536 |
| 877 |
| 0.58 |
| 609 |
| 967 |
| 0.73 |
| 767 |
| 1009 |
| 0.81 | 851 | 1051 | 0.89 | 935 |
1700 | 750 | 0.45 | 473 | 806 | 0.51 | 536 |
| 857 |
| 0.59 |
| 615 |
| 908 |
| 0.66 |
| 693 |
| 997 |
| 0.81 |
| 851 |
| 1037 |
| 0.90 | 940 | 1077 | 1.01 | 1030 |
1800 | 788 | 0.52 | 546 | 841 | 0.59 | 620 |
| 890 |
| 0.67 |
| 704 |
| 939 |
| 0.75 |
| 788 |
| 1026 |
| 0.91 |
| 956 |
| 1065 |
| 1.01 | 1040 | 1104 | 1.07 | 1124 |
1900 | 826 | 0.60 | 630 | 876 | 0.68 | 714 |
| 924 |
| 0.76 |
| 799 |
| 971 |
| 0.84 |
| 883 |
| 1056 |
| 1.01 |
| 1061 |
| 1094 |
| 1.10 | 1151 | 1132 | 1.18 | 1240 |
2000 | 864 | 0.70 | 735 | 912 | 0.77 | 809 |
| 958 |
| 0.86 |
| 898 |
| 1004 |
| 0.94 |
| 988 |
| 1087 |
| 1.12 |
| 1177 |
| 1125 |
| 1.21 | 1271 | 1162 | 1.30 | 1366 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
580D048 (4 TONS) Ð ALTERNATE MOTOR (BELT DRIVE)* (cont) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||||||||
Air¯ow |
|
|
|
|
|
|
|
|
|
| External Static Pressure (in. wg) |
|
|
|
|
|
|
|
|
| ||||||||||||
| 0.9 |
|
| 1.0 |
|
|
|
| 1.1 |
|
|
|
|
| 1.2 |
|
|
|
|
| 1.4 |
|
|
|
|
| 1.6 |
|
| 1.8 |
| |
(Cfm) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||
| Rpm | Bhp | Watts | Rpm | Bhp | Watts | Rpm | Bhp | Watts | Rpm | Bhp | Watts | Rpm | Bhp | Watts | Rpm | Bhp | Watts | Rpm | Bhp | Watts | |||||||||||
1200 | 987 | 0.64 | 652 | 1030 | 0.70 | 695 |
| 1068 |
| 0.79 | 792 |
| 1106 |
| 0.87 |
| 889 |
| 1134 |
| 0.98 |
| 998 |
| 1189 |
| 1.12 | 1138 | 1245 | 1.21 | 1358 | |
1300 | 1006 | 0.71 | 709 | 1044 | 0.77 | 736 |
| 1086 |
| 0.84 | 833 |
| 1128 |
| 0.91 |
| 930 |
| 1183 |
| 1.10 |
| 1052 |
| 1226 |
| 1.23 | 1215 | 1297 | 1.35 | 1406 | |
1400 | 1033 | 0.79 | 797 | 1069 | 0.86 | 838 |
| 1104 |
| 0.93 | 925 |
| 1139 |
| 1.01 |
| 1012 |
| 1218 |
| 1.14 |
| 1090 |
| 1286 |
| 1.34 | 1282 | 1320 | 1.48 | 1463 | |
1500 | 1060 | 0.88 | 891 | 1095 | 0.95 | 930 |
| 1129 |
| 1.02 | 1022 |
| 1162 |
| 1.09 |
| 1114 |
| 1228 |
| 1.24 |
| 1186 |
| 1303 |
| 1.40 | 1339 | 1343 | 1.60 | 1530 | |
1600 | 1087 | 1.01 | 1001 | 1123 | 1.05 | 1073 |
| 1156 |
| 1.13 | 1150 |
| 1185 |
| 1.20 |
| 1226 |
| 1250 |
| 1.35 |
| 1291 |
| 1319 |
| 1.51 | 1444 | 1382 | 1.68 | 1607 | |
1700 | 1114 | 1.07 | 1108 | 1151 | 1.15 | 1185 |
| 1183 |
| 1.23 | 1262 |
| 1215 |
| 1.31 |
| 1339 |
| 1276 |
| 1.48 |
| 1415 |
| 1334 |
| 1.64 | 1569 | 1398 | 1.80 | 1722 | |
1800 | 1141 | 1.17 | 1221 | 1178 | 1.26 | 1318 |
| 1211 |
| 1.35 | 1390 |
| 1243 |
| 1.43 |
| 1461 |
| 1303 |
| 1.61 |
| 1540 |
| 1359 |
| 1.78 | 1702 | 1418 | 1.95 | 1865 | |
1900 | 1168 | 1.28 | 1371 | 1204 | 1.37 | 1502 |
| 1238 |
| 1.47 | 1548 |
| 1271 |
| 1.56 |
| 1594 |
| 1330 |
| 1.74 |
| 1664 |
| 1386 |
| 1.93 | 1846 | 1439 | 2.11 | 2018 | |
2000 | 1197 | 1.39 | 1485 | 1231 | 1.48 | 1604 |
| 1265 |
| 1.59 | 1666 |
| 1298 |
| 1.69 |
| 1727 |
| 1358 |
| 1.89 |
| 1808 |
| 1413 |
| 2.08 | 1989 | 1466 | 2.27 | 2171 |
|
| LEGEND |
Bhp | Ð Brake Horsepower Input to Fan | |
FIOP | Ð |
|
Watts | Ð | Input Watts to Motor |
*Motor drive range is 835 to 1185 rpm. All other rpms require a ®eld- supplied drive.
NOTES:
1.Boldface indicates
2.Values include losses for ®lters, unit casing, and wet coils. See page 52 for accessory/FIOP static pressure information.
3.Maximum continuous bhp is 1.00 and the maximum continuous watts are 1000. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with con®- dence. Using your fan motors up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit war- ranty will not be affected. See
4.Use of a
5.Interpolation is permissible. Do not extrapolate.