PHYSICAL DATA Ð 580D036-072
UNIT SIZE 580D |
| 036 |
| 048 |
| 060 | 072 |
NOMINAL CAPACITY (tons) |
| 3 |
| 4 |
| 5 | 6 |
OPERATING WEIGHT (lb) |
|
|
|
|
|
|
|
Unit |
|
|
|
|
|
|
|
Al/Al* |
| 460 |
| 470 |
| 490 | 565 |
Al/Cu* |
| 465 |
| 476 |
| 497 | 576 |
Cu/Cu* |
| 468 |
| 482 |
| 505 | 587 |
Economizer |
|
|
|
|
|
|
|
Durablade |
| 34 |
| 34 |
| 34 | 34 |
Parablade |
| 42 |
| 42 |
| 42 | 42 |
Roof Curb² |
| 115 |
| 115 |
| 115 | 115 |
COMPRESSOR |
|
|
|
| Hermetic |
| |
Quantity |
| 1 |
| 1 | 1 | 1 | |
No. Cylinders (per Circuit) |
| 2 |
| 2 | 2 | 2 | |
Oil (oz) |
| 50 |
| 50 | 50 | 54 | |
REFRIGERANT TYPE |
|
|
|
|
| ||
Expansion Device |
|
|
| Acutrol™ Feed Device |
| ||
Operating Charge |
|
|
|
|
|
|
|
Circuit 1 |
|
|
| ||||
Circuit 2 |
| Ð |
| Ð |
| Ð | Ð |
CONDENSER COIL |
|
| Enhanced Copper Tubes, | Aluminum Lanced | Fins | ||
Rows...Fins/in. |
| 1...17 | 1...17 |
| 1...17 | 2...17 | |
Total Face Area (sq ft) |
| 7.36 | 11.39 |
| 13.19 | 10.42 | |
CONDENSER FAN |
|
|
| Propeller | Type |
| |
Nominal Cfm |
| 3500 | 4000 |
| 4000 | 4000 | |
Quantity...Diameter (in.) |
| 1...22.0 | 1...22.0 |
| 1...22.0 | 1...22.0 | |
Motor Hp...Rpm |
| 1¤4...1100 | 1¤4...1100 |
| 1¤4...1100 | 1¤4...1100 | |
Watts Input (Total) |
| 325 | 325 |
| 325 | 325 | |
EVAPORATOR COIL |
| Enhanced Copper Tubes, | Aluminum | ||||
Rows...Fins/in. |
| 2...15 | 2...15 |
| 3...15 | 4...15 | |
Total Face Area (sq ft) |
| 4.17 | 5.5 |
| 5.5 | 5.5 | |
EVAPORATOR FAN |
|
|
| Centrifugal | Type |
| |
Quantity...Size (in.) | Std | 1...10 x 10 |
| 1...10 x 10 |
| 1...11 x 10 | 1...10 x 10 |
| Alt | 1...10 x 10 |
| 1...10 x 10 |
| 1...10 x 10 | Ð |
Type Drive | Std | Direct |
| Direct |
| Direct | Belt |
Nominal Cfm | Alt | Belt |
| Belt |
| Belt | Ð |
| 1200 | 1600 |
| 2000 | 2400 | ||
Motor Hp | Std | Ð | Ð |
| Ð | Ð | |
| Alt | Ð | Ð |
| Ð | Ð | |
Maximum Continuous Bhp | Std | .34 | .75 |
| 1.20 | 2.40 | |
| Alt | 1.00 | 1.00 |
| 1.80 | Ð | |
Motor Frame Size | Std | 48 | 48 |
| 48 | 56 | |
| Alt | 48 | 48 |
| 48 | Ð | |
Nominal Rpm High/Low | Std | 860/800 | 1075/970 |
| 1075/970 | Ð | |
| Alt | Ð | Ð |
| Ð | Ð | |
Fan Rpm Range | Std | Ð | Ð |
| Ð | ||
Motor Bearing Type | Alt |
| Ð | ||||
| Ball |
| Ball |
| Ball | Ball | |
Maximum Allowable Rpm |
| 2100 | 2100 |
| 2100 | 2100 | |
Motor Pulley Pitch Diameter Min/Max (in.) | Std | Ð | Ð |
| Ð | 2.8/3.8 | |
| Alt | 1.9/2.9 | 1.9/2.9 |
| 2.4/3.4 | Ð | |
Nominal Motor Shaft Diameter (in.) | Std | 1¤2 | 1¤2 |
| 1¤2 | 5¤8 | |
| Alt | 1¤2 | 1¤2 |
| 1¤2 | Ð | |
Fan Pulley Pitch Diameter (in.) | Std | Ð | Ð |
| Ð | 4.5 | |
Nominal Fan Shaft Diameter (in.) | Alt | 4.5 | 4.0 |
| 4.5 | Ð | |
| Ð | Ð |
| Ð | Ð | ||
Belt, Quantity...Type...Length (in.) | Std | Ð | Ð |
| Ð | 1...A...40 | |
| Alt | 1...A...34 |
| 1...A...34 |
| 1...A...39 | Ð |
Pulley Center Line Distance (in.) | Std | Ð | Ð |
| Ð | ||
| Alt |
| Ð | ||||
Speed Change per Full Turn of | Std | Ð | Ð |
| Ð | 80 | |
Movable Pulley Flange (rpm) | Alt | 48 | 70 |
| 80 | Ð | |
Movable Pulley Maximum Full Turns | Std | Ð | Ð |
| Ð | 5 | |
From Closed Position | Alt | 5 | 5 |
| 5 | Ð | |
Factory Setting | Std | Ð | Ð |
| Ð | 3 | |
| Alt | 3 | 3 |
| 3 | Ð | |
Factory Speed Setting (rpm) | Std | Ð | Ð |
| Ð | 1225 | |
Fan Shaft Diameter at Pulley (in.) | Alt | 856 | 975 |
| 1060 | Ð | |
| 1¤2 | 1¤2 |
| 1¤2 | 1¤2 |
| LEGEND |
Al | Ð Aluminum |
Bhp | Ð Brake Horsepower |
Cu | Ð Copper |
*Evaporator coil ®n material/condenser coil ®n material. Contact your local representative for details about coated ®ns.
²Weight of
**Rollout switch lockout is manually reset by interrupting power to unit or resetting thermostat.
²²Requires an optional or accessory Controls Upgrade Kit.
NOTE: The
8