GUIDE SPECIFICATIONS Ð 580D036-150 (cont)
5.The integrated gas controller (IGC) board shall include gas heat operation fault noti®cation using an LED
6.Unit shall be equipped with
7.The IGC board shall contain algorithms that modify
8.The LED shall be visible without removal of control box access panel.
G.Refrigerant Components:
Refrigerant circuit components shall include:
1.Fixed ori®ce feed system.
2.Refrigerant strainer.
3.Service gage connections on suction, discharge, and liquid lines.
H.Filter Section:
1.Standard ®lter section shall consist of factory- installed, low velocity, throwaway
2.Filter face velocity shall not exceed 320 fpm at nomi- nal air¯ows.
3.Filter section should use only one size ®lter.
4.Filters shall be accessible through an access panel with
I.Controls and Safeties:
1.Unit Controls:
Unit shall be complete with
2.Safeties:
a.Unit shall incorporate compressor overtempera- ture and overcurrent safety devices to shut off compressor.
b.Heating section shall be provided with the follow- ing minimum protections:
1)
2)
3)Flame rollout switch.
4)Flame proving controls.
J.Operating Characteristics:
1.Unit shall be capable of starting and running at 115 F ambient outdoor temperature, meeting maxi- mum load criteria of ARI Standard 210/240 or 360.
2.Compressor with standard controls shall be capable of operation down to 25 F ambient outdoor temperature.
K.Electrical Requirements:
All unit power wiring shall enter unit cabinet at a single
L.Motors:
1.Compressor motors shall be cooled by refrig- erant gas passing through motor windings and shall have line break thermal and current overload protection.
2.
3.Totally enclosed
4.
M.Special Features:
Certain features are not applicable when the features designated * are speci®ed. For assistance in amending the speci®cations, contact your local sales of®ce.
1.Roof Curbs (Horizontal and Vertical):
a.Formed galvanized steel with wood nailer strip and shall be capable of supporting entire unit weight.
b.Permits installation and securing of ductwork to curb prior to mounting unit on the curb.
*2. Integrated Economizers:
a.Integrated integral modulating type capable of simultaneous economizer and compressor operation.
b.Includes all hardware and controls to provide cooling with outdoor air.
c.Equipped with
d.Capable of introducing up to 100% outdoor air.
e.Parallel opposed blade economizer shall be equipped with a barometric relief damper with up to 30% of return air
f.Designed to close damper during
g.Dry bulb
h.Variable sliding plate economizer is a guillotine- style damper, and the parallel opposed blade economizer is a parallel blade design.
i.Parallel opposed blade economizer shall provide control of internal building pressure through its in- herent power exhaust function.
j.Parallel opposed blade economizer shall be ca- pable of exhausting up to 100% outdoor air.
NOTE: Parallel opposed blade type economizer shall also be available with power exhaust.
*3. Manual
Manual damper package shall consist of damper, birdscreen, and rainhood which can be preset to ad- mit up to 50% outdoor air for year round ventilation.
*4. 100%
a.