APPLICATION DATA

1.DUCTWORK (580D036-150) Ð Secure vertical discharge ductwork to roof curb. For horizontal discharge applica- tions, attach ductwork to unit, or ®eld-supplied ¯anges can be attached to horizontal discharge openings and all duct- work attached to ¯anges.

2.DUCTWORK (579F180-300) Ð Ductwork should be at- tached to the curb on all units. Interior installation may pro- ceed before unit is set in place on roof. If ductwork will be attached to the unit, do not drill in condensate drain pan area Ð leaks may result. See ®gures on page 66 for in- formation on ®eld-installed concentric ductwork when applicable.

3.TO CONVERT DURABLADE ECONOMIZER FROM VER- TICAL DISCHARGE TO HORIZONTAL DISCHARGE

(580D036-150):

1.Remove economizer to gain access to return duct opening.

2.Move the horizontal discharge duct opening covers to the vertical discharge openings.

3.Rotate economizer 90 degrees (until the economizer motor faces the condenser section).

4.Rotate the barometric relief damper 90 degrees (econo- mizer only).

5.Install block-off plate over the opening on the access panel.

NOTE: Parablade economizer is for vertical discharge units only.

4.THRU-THE-CURB SERVICE CONNECTIONS (579F180- 300) Ð Roof curb connections allow ®eld power wires, con- trol wires, and gas supply to enter through the roof curb opening.

5.THRU-THE-BOTTOM SERVICE CONNECTIONS (580D036-150) Ð An accessory kit is required for proper installation of thru-the-bottom connections.

6.THERMOSTAT Ð Use of 2-stage cooling thermostat is rec- ommended for all units. A 2-stage cooling thermostat is required on units with accessory economizer to provide integrated cooling.

7.HEATING-TO-COOLING CHANGEOVER Ð All units are automatic changeover from heating to cooling when auto- matic changeover thermostat and subbase are used.

8.AIRFLOW Ð Units are draw-thru on cooling and blow-thru on heating.

9.MAXIMUM AIRFLOW Ð To minimize the possibility of con- densate blow-off from evaporator, air¯ow through units should not exceed 500 cfm/ton on size 036-240 units, and 11,250 cfm on size 028 units.

10.MINIMUM AIRFLOW Ð The minimum air¯ow for cooling is 300 cfm/ton on size 036-240 units and 280 cfm/ton on size 300 units. Refer to Heating Capacities and Ef®ciencies table on page 7 for minimum air¯ow cfm for heating on size 180-300 units.

11.MINIMUM AMBIENT COOLING OPERATION TEMPERA- TURE (580D036-150) Ð The cooling temperature for size 036-150 standard units is 25 F. With accessory Motor- master control units can operate at outdoor temperatures down to −20 F.

12.MINIMUM AMBIENT COOLING OPERATION TEMPERA- TURE (579F180-300) Ð Units are designed to operate at outdoor temperatures down to 40 F for 579F180, 35 F for 579F216 25 F for 579F240, and 48 F for 579F300. To op- erate at lower outdoor-air temperatures, see Price Pages or contact your local representative for appropriate accessory combinations for speci®c applications.

13.MAXIMUM OPERATING OUTDOOR-AIR TEMPERA- TURE Ð For cooling, this temperature is 115 F on size 036- 180 units, 125 F on size 216-300 units.

14.HIGH ALTITUDE Ð A change to the gas ori®ce may be re- quired at high altitudes. Refer to Altitude Compensation charts on pages 53 and 54.

15.MINIMUM TEMPERATURE Ð Air entering the heat ex- changer in heating must be a minimum of 50 F continuous and 45 F intermittent.

16.INTERNAL UNIT DESIGN Ð Due to the internal unit de- sign (draw-thru over the motor), air path, and specially de- signed motors, the full horsepower (maximum continuous bhp) listed in the Physical Data table and the notes follow- ing each Fan Performance table can be utilized with ex- treme con®dence.

Using motors with the values listed in the Physical and Fan Performance Data tables will not result in nuisance tripping or premature motor failure. The unit warranty will not be affected.

65

Image 65
Contents 580D036-072 579F180,216 580D090-150 579F240,300 FEATURES/BENEFITSPage Table of Contents 580D036-150 Models only Model Number NomenclatureModel Number Nomenclature 579F180-300 Models only ARI* Capacity Ratings Heating Capacities and Efficiencies Ð 580D036-150 ARI* Capacity RatingsHeating Capacities and Efficiencies Ð 579F180-300 Rise EfficiencyUnit Size 580D Physical Data Ð 580D036-072Unit Size 580D Medium LOW/MEDIUM High Heat Physical Data Ð 580D036-072090 102 120 150 Nominal Capacity tons Physical Data Ð 580D090-150Quantity...Diameter Motor Hp...Rpm Pulley Center Line Distance StdUnit Size 580D LOW/MEDIUM High Heat Hihg Heat Medium Heat Physical Data Ð 580D090-150Unit Size 579F Physical Data Ð 579F180-300LOW/HIGH Heat Physical Data Ð 579F180-300Unit Size 579F Option ACCESSORY² Options and AccessoriesHead Pressure Control Head Pressure Control Speed Control 180,216Time Guard II Control Options and AccessoriesDurablade Economizer SizesAccusensor Control Power Exhaust 180-300 Shown Accusensor SensorOnly ThermostatUnit Base Unit Dimensions Ð 580D036-072Unit Corner Weight Dimensions Base Unit Dimensions Ð 580D090-150486 220 636 288 Base Unit Dimensions Ð 579F180,216Dimension Base Unit Dimensions Ð 579F240,300Roof Curb Ð 580D036-072 Accessory DimensionsRoof Curb Ð 580D090-150 Accessory DimensionsPKG. NO. REF Curb Description Height Dimensions degrees and inchesUnit DEG 579FPower Exhaust 579F180-300 Horizontal Supply/Return Adapter Installation 579F180-300Accessory Curb Description Package no Height Pre-Assembled, High StaticII Select Unit Based on Required Cooling Capacity Selection Procedure with 579F180 exampleSHC Performance Data Cooling CapacitiesCooling Capacities Performance Data580D150 121¤2 Tons Performance Data Cooling Capacities580D120 10 Tons 4500/0.08 5250/0.10 6000/0.11 6750/0.12 7500/0.14 Condenser 579F180 15 Tons Temp F Air Entering Evaporator Ð Cfm/BF579F216 18 Tons 5400/0.06 6000/0.07 7200/0.08 9000/0.097000/0.03 8750/0.05 10,000/0.07 11,250/0.09 579F240 20 Tons Temp F Air Entering Evaporator Ð Cfm/BF579F300 25 Tons 580D036 3 Tons Ð Standard Motor Direct Drive FAN Performance Ð 580D036-150 Vertical Discharge UnitsFiop 580D036 3 Tons Ð Alternate Motor Belt Drive580D048 4 Tons Ð Alternate Motor Belt Drive 580D048 4 Tons Ð Standard Motor Direct Drive580D060 5 Tons Ð Alternate Motor Belt Drive 580D060 5 Tons Ð Standard Motor Direct DriveRpm Bhp Watts 1800 580D072 6 Tons Air¯ow External Static Pressure in. wg2600 1562Rpm Bhp Watts 2250 580D090 71¤2 Tons Air¯ow External Static Pressure in. wg2550 3100Rpm Bhp Watts 2550 580D102 81¤2 Tons Air¯ow External Static Pressure in. wg891 2188 3300 904 2300 3400Rpm Bhp Watts 3000 580D120 10 Tons Air¯ow External Static Pressure in. wg4300 985Rpm Bhp Watts 3750 580D150 121¤2 Tons Air¯ow External Static Pressure in. wg5100 5200FAN Performance Ð 580D036-150 Horizontal Discharge Units Rpm Bhp Watts 1200 569 189 641 1989 1466 2171 Bhp Brake Horsepower Input to Fan299 761 357 859 483 901 546 943 609 1300 604 231 673 352 788 410 887 546 928 615 968 683 1400 640 284 7051392 Medium Speed High Speed 208 230, 460, 575 230,460, 5751365 2038 1426 1331 1986 1400 2227 14611514 15361496 2240 1529 1603894 997 3055 1040 3333 Bhp Brake Horsepower Input to Fan882 895Rpm Bhp Watts 2550 669 627 867 692 1056 754 1062 3676 1102 3860 Bhp Brake Horsepower Input to Fan783 8121008 962973 10191166 Bhp Watts 37501178 1131FAN Performance Ð 579F180-300 Units Performance Data FAN Performance Ð 579F180-300 Units 579F240 20 Tons Air¯ow External Static Pressure in. wg 10,000 Bhp Brake Horsepower Input to FanRpm Bhp Watts 6000 9500579F300 25 Tons Air¯ow 10,500 11,000 11,250 Bhp Brake Horsepower Input to FanRpm Bhp Watts 500 3507Sound Weighted Octave Bands Unit Rating Sound Power Total UnitAIR Quantity Limits Unit Minimum CFM Maximum CFMACCESSORY/FIOP Static PRESSURE* in. wg − 579F180-300 ACCESSORY/FIOP Static PRESSURE* in. wg − 580D090-150Component CFM Unit Motor Pulley Turns OpenBtuh Nominal Altitude COMPENSATION* ÐNominal Input InputAltitude COMPENSATION* Ð 580D090-150 Fan Performance Using Accessory Power Exhaust 579F180-300EVAPORATOR-FAN Motor Efficiency Altitude Derating FACTOR* Ð ALL UnitsMaximum Unit EVAPORATOR-FAN Acceptable EVAPORATOR-FAN Motor PerformanceContinuous Operating AMP Draw BHP 580D036RLA LRA FLA MCA MOCP² Electrical Data Ð 580D036-150Electrical Data Ð 579F180-300 Vertical Discharge Ducting Typical Piping and Wiring Ð 580D036-150Horizontal Discharge Ducting NEC Ð National Electrical Code579F180 shown Typical Piping and Wiring Ð 579F180-300Typical Wiring Schematic Ð 580D036-150 Typical Wiring Schematic 579F240-300, 460-v shown PRI AHAIDM IFCOperating Sequence ControlsCooling, Units With Parablade Economizer 580D036-072 Controls580D036-150 Application DataApplication Data Part 1 Ð General Guide Specifications Ð 580D036-150Guide Specifications Ð 580D036-150 Guide Specifications Ð 580D036-150 Guide Specifications Ð 579F180-300 Guide Specifications Ð 579F180-300 Copyright 1998 Bryant Heating & Cooling Systems