PERFORMANCE DATA (cont)
FAN PERFORMANCE Ð 580D036-150 VERTICAL DISCHARGE UNITS
580D036 (3 TONS) Ð STANDARD MOTOR (DIRECT DRIVE)
Air¯ow |
|
| Low Speed |
|
|
|
|
| High Speed |
|
|
| ||
| 208 V |
|
| 230, 460, 575 V |
| 208 V |
|
| 230, 460, 575 V | |||||
(Cfm) |
|
|
|
|
|
| ||||||||
| Esp | Bhp | Watts | Esp |
| Bhp | Watts | Esp | Bhp | Watts | Esp |
| Bhp | Watts |
900 | 0.49 | 0.21 | 253 | 0.50 |
| 0.23 | 277 | 0.51 | 0.26 | 307 | 0.55 |
| 0.31 | 363 |
1000 | 0.42 | 0.23 | 270 | 0.43 |
| 0.25 | 292 | 0.43 | 0.27 | 321 | 0.51 |
| 0.32 | 374 |
1100 | 0.37 | 0.24 | 287 | 0.38 |
| 0.26 | 307 | 0.39 | 0.28 | 335 | 0.46 |
| 0.33 | 385 |
1200 | 0.33 | 0.26 | 304 | 0.33 |
| 0.27 | 323 | 0.34 | 0.29 | 349 | 0.40 |
| 0.34 | 397 |
1300 | 0.27 | 0.27 | 321 | 0.28 |
| 0.29 | 338 | 0.28 | 0.31 | 364 | 0.34 |
| 0.34 | 408 |
1400 | 0.20 | 0.29 | 338 | 0.23 |
| 0.30 | 354 | 0.25 | 0.32 | 378 | Ð |
| Ð | Ð |
1500 | 0.16 | 0.30 | 355 | 0.18 |
| 0.31 | 369 | 0.20 | 0.33 | 392 | Ð |
| Ð | Ð |
|
| LEGEND |
Bhp | Ð Brake Horsepower Input to Fan | |
Esp | Ð | External Static Pressure (in. wg) |
FIOP | Ð |
|
NOTES:
1.Values include losses for ®lters, unit casing, and wet coils. See page 52 for accessory/FIOP static pressure information.
2.Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with con®dence. Using your fan motors up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. See
3.Use of a
580D036 (3 TONS) Ð ALTERNATE MOTOR (BELT DRIVE)*
Air¯ow |
|
|
|
|
|
| External Static Pressure (in. wg) |
|
|
|
|
|
| ||||||
| 0.1 |
|
| 0.2 |
|
| 0.3 |
|
|
| 0.4 |
|
| 0.5 |
|
| 0.6 |
| |
Cfm |
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||
| Rpm | Bhp | Watts | Rpm | Bhp | Watts | Rpm | Bhp |
| Watts | Rpm | Bhp | Watts | Rpm | Bhp | Watts | Rpm | Bhp | Watts |
900 | 581 | 0.12 | 119 | 673 | 0.18 | 179 | 736 | 0.22 |
| 219 | 805 | 0.25 | 249 | 865 | 0.29 | 288 | 911 | 0.34 | 338 |
1000 | 644 | 0.19 | 189 | 709 | 0.22 | 219 | 782 | 0.28 |
| 279 | 835 | 0.30 | 298 | 900 | 0.35 | 348 | 937 | 0.38 | 378 |
1100 | 687 | 0.22 | 219 | 746 | 0.26 | 259 | 806 | 0.30 |
| 298 | 867 | 0.35 | 348 | 929 | 0.40 | 398 | 964 | 0.40 | 398 |
1200 | 733 | 0.26 | 259 | 785 | 0.32 | 318 | 843 | 0.35 |
| 348 | 903 | 0.41 | 408 | 960 | 0.47 | 467 | 994 | 0.50 | 497 |
1300 | 754 | 0.29 | 288 | 826 | 0.38 | 378 | 891 | 0.43 |
| 428 | 942 | 0.48 | 477 | 991 | 0.53 | 527 | 1047 | 0.60 | 597 |
1400 | 810 | 0.35 | 348 | 868 | 0.45 | 448 | 937 | 0.51 |
| 507 | 984 | 0.57 | 567 | 1032 | 0.62 | 617 | 1067 | 0.67 | 666 |
1500 | 841 | 0.42 | 418 | 911 | 0.53 | 527 | 985 | 0.61 |
| 607 | 1029 | 0.66 | 656 | 1073 | 0.72 | 716 | 1109 | 0.77 | 766 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
580D036 (3 TONS) Ð ALTERNATE MOTOR (BELT DRIVE)* (cont) |
|
|
|
|
|
|
|
|
|
| |||||||||
Air¯ow |
|
|
|
|
|
| External Static Pressure (in. wg) |
|
|
|
|
|
| ||||||
| 0.7 |
|
| 0.8 |
|
| 0.9 |
|
|
| 1.0 |
|
| 1.1 |
|
| 1.2 |
| |
Cfm |
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||
| Rpm | Bhp | Watts | Rpm | Bhp | Watts | Rpm | Bhp |
| Watts | Rpm | Bhp | Watts | Rpm | Bhp | Watts | Rpm | Bhp | Watts |
900 | 957 | 0.39 | 388 | 988 | 0.43 | 428 | 1039 | 0.47 |
| 448 | 1061 | 0.51 | 487 | 1083 | 0.54 | 527 | 1105 | 0.58 | 567 |
1000 | 992 | 0.44 | 438 | 1039 | 0.49 | 487 | 1061 | 0.55 |
| 507 | 1088 | 0.60 | 547 | 1111 | 0.66 | 587 | 1136 | 0.72 | 627 |
1100 | 1013 | 0.49 | 487 | 1068 | 0.55 | 547 | 1091 | 0.61 |
| 577 | 1109 | 0.66 | 607 | 1127 | 0.73 | 637 | 1145 | 0.80 | 666 |
1200 | 1045 | 0.56 | 557 | 1090 | 0.64 | 637 | 1109 | 0.68 |
| 647 | 1156 | 0.73 | 676 | 1203 | 0.81 | 706 | 1250 | 0.86 | 736 |
1300 | 1075 | 0.64 | 637 | 1122 | 0.70 | 696 | 1152 | 0.76 |
| 716 | 1190 | 0.82 | 756 | 1228 | 0.87 | 796 | 1266 | 0.94 | 836 |
1400 | 1110 | 0.73 | 726 | 1160 | 0.78 | 766 | 1181 | 0.83 |
| 806 | 1237 | 0.88 | 845 | 1293 | 0.94 | 885 | 1349 | 0.99 | 925 |
1500 | 1150 | 0.78 | 816 | 1190 | 0.84 | 855 | 1225 | 0.89 |
| 895 | 1271 | 0.95 | 945 | 1317 | 1.00 | 995 | 1383 | 1.05 | 1044 |
|
| LEGEND |
Bhp | Ð Brake Horsepower Input to Fan | |
FIOP | Ð | |
Watts | Ð | Input Watts to Motor |
*Motor drive range is 760 to 1000 rpm. All other rpms require a ®eld- supplied drive.
NOTES:
1.Boldface indicates
2.Values include losses for ®lters, unit casing, and wet coils. See page 52 for accessory/FIOP static pressure information.
3.Maximum continuous bhp is 1.0 and the maximum continuous watts are 1000. Extensive motor and electrical testing on these units en- sures that the full range of the motor can be utilized with con®dence. Using your fan motors up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. See
4.Use of a
5.Interpolation is permissible. Do not extrapolate.
31