GUIDE SPECIFICATIONS Ð 580D036-150 (cont)

b. Damper shall close upon indoor (evaporator) fan shutoff.

c. Designed to close damper during loss of power situations.

d. Equipped with 15% barometric relief damper.

*5. 25% Two-Position Damper:

a.Two-position damper package shall include single blade damper and motor. Admits up to 25% out- door air.

b.Damper shall close upon indoor (evaporator) fan shutoff.

c.Designed to close damper during loss of power situations.

d.Equipped with barometric relief damper.

*6. Solid-State Enthalpy Control:

a.For use with variable sliding plate economizer package only.

b.Capable of sensing outdoor-air heat content (tem- perature and humidity) and control economizer cut-in point to have minimum heat content air passing over the evaporator coil for most ef®cient system operation.

*7. Differential Enthalpy Sensor:

a.For use with economizer only.

b.Capable of comparing heat content (temperature and humidity) of outdoor air and return air and controlling economizer cut-in point at the most economical level.

*8. Head Pressure Control Package:

Consists of solid-state control and condenser-coil temperature sensor to maintain condensing tem- perature between 90 F and 110 F at outdoor ambient temperatures down to −20 F by condenser-fan speed modulation or condenser-fan cycling.

9. LP (Liquid Propane) Gas Conversion Kit:

*11. Flue Shield:

Provides protection from the hot sides of the gas ¯ue hood.

*12. Thermostat and Subbase:

Provides staged cooling and heating automatic (or manual) changeover, fan control, and indicator light.

*13. Condenser Coil Hail Guard Assembly:

Hail guard shall protect against damage from hail and ¯ying debris.

14.NOx Reduction Kit:

Package shall contain all necessary hardware and instructions to convert a standard natural gas unit to

reduce the nitrous oxide (NOx) emissions to a level of 40 nanograms/joule or less for unit sizes 036-060 being installed in California Air Quality Management Districts.

15.Controls Upgrade Kit:

Kit shall contain high-pressure, loss-of-charge/low- pressure, and freeze protection switches. It shall mount on factory-installed Schrader ®ttings.

16.Alternate Motor(s) and/or Drive(s) (036-060, 090, 120, 150):

Alternate motor(s) and drive(s) shall be factory- installed to provide additional performance range.

17.Flue Discharge De¯ector:

Flue discharge de¯ector directs unit exhaust verti- cally instead of horizontally.

*18. Condenser Coil Grille:

The grille protects the condenser coil from damage by large objects without increasing unit clearances.

19.Compressor Cycle Delay:

Unit shall be prevented from restarting for minimum of 5 min. after shutdown.

20.Thru-the-Bottom Service Connectors:

Package shall contain all the necessary hardware and instructions to convert a standard natural gas unit for use with lique®ed propane gas.

Kit shall provide connectors to permit gas and elec- trical connections to be brought to the unit through the basepan.

* 10. Commercial Programmable Thermostat:

21. Fan/Filter Status Switch:

 

Seven-day commercial progammable thermostat shall be capable of auto-changeover, F/C, 3-stage heating and 2-stage cabling. Thermostat shall also be equipped with complete system status display.

Provides status of indoor (evaporator) fan (ON/OFF) or ®lter (CLEAN/DIRTY). Status shall be displayed over communication bus when used with direct digital controls or with an indicator light at the thermostat.

69

Image 69
Contents 580D036-072 579F180,216 580D090-150 579F240,300 FEATURES/BENEFITSPage Table of Contents 580D036-150 Models only Model Number NomenclatureModel Number Nomenclature 579F180-300 Models only ARI* Capacity Ratings Heating Capacities and Efficiencies Ð 580D036-150 ARI* Capacity RatingsHeating Capacities and Efficiencies Ð 579F180-300 Rise EfficiencyUnit Size 580D Physical Data Ð 580D036-072Unit Size 580D Medium LOW/MEDIUM High Heat Physical Data Ð 580D036-072090 102 120 150 Nominal Capacity tons Physical Data Ð 580D090-150Quantity...Diameter Motor Hp...Rpm Pulley Center Line Distance StdUnit Size 580D LOW/MEDIUM High Heat Hihg Heat Medium Heat Physical Data Ð 580D090-150Unit Size 579F Physical Data Ð 579F180-300Physical Data Ð 579F180-300 Unit Size 579FLOW/HIGH Heat Option ACCESSORY² Options and AccessoriesHead Pressure Control Head Pressure Control Speed Control 180,216Time Guard II Control Options and AccessoriesDurablade Economizer SizesAccusensor Control Power Exhaust 180-300 Shown Accusensor SensorOnly ThermostatUnit Base Unit Dimensions Ð 580D036-072Unit Corner Weight Dimensions Base Unit Dimensions Ð 580D090-150486 220 636 288 Base Unit Dimensions Ð 579F180,216Dimension Base Unit Dimensions Ð 579F240,300Roof Curb Ð 580D036-072 Accessory DimensionsRoof Curb Ð 580D090-150 Accessory DimensionsPKG. NO. REF Curb Description Height Dimensions degrees and inchesUnit DEG 579FPower Exhaust 579F180-300 Horizontal Supply/Return Adapter Installation 579F180-300Accessory Curb Description Package no Height Pre-Assembled, High StaticII Select Unit Based on Required Cooling Capacity Selection Procedure with 579F180 exampleSHC Performance Data Cooling CapacitiesCooling Capacities Performance DataPerformance Data Cooling Capacities 580D120 10 Tons580D150 121¤2 Tons 4500/0.08 5250/0.10 6000/0.11 6750/0.12 7500/0.14 Condenser 579F180 15 Tons Temp F Air Entering Evaporator Ð Cfm/BF579F216 18 Tons 5400/0.06 6000/0.07 7200/0.08 9000/0.09579F240 20 Tons Temp F Air Entering Evaporator Ð Cfm/BF 579F300 25 Tons7000/0.03 8750/0.05 10,000/0.07 11,250/0.09 580D036 3 Tons Ð Standard Motor Direct Drive FAN Performance Ð 580D036-150 Vertical Discharge UnitsFiop 580D036 3 Tons Ð Alternate Motor Belt Drive580D048 4 Tons Ð Alternate Motor Belt Drive 580D048 4 Tons Ð Standard Motor Direct Drive580D060 5 Tons Ð Alternate Motor Belt Drive 580D060 5 Tons Ð Standard Motor Direct DriveRpm Bhp Watts 1800 580D072 6 Tons Air¯ow External Static Pressure in. wg2600 1562Rpm Bhp Watts 2250 580D090 71¤2 Tons Air¯ow External Static Pressure in. wg2550 3100Rpm Bhp Watts 2550 580D102 81¤2 Tons Air¯ow External Static Pressure in. wg891 2188 3300 904 2300 3400Rpm Bhp Watts 3000 580D120 10 Tons Air¯ow External Static Pressure in. wg4300 985Rpm Bhp Watts 3750 580D150 121¤2 Tons Air¯ow External Static Pressure in. wg5100 5200FAN Performance Ð 580D036-150 Horizontal Discharge Units Rpm Bhp Watts 1200 569 189 641 1989 1466 2171 Bhp Brake Horsepower Input to Fan299 761 357 859 483 901 546 943 609 1300 604 231 673 352 788 410 887 546 928 615 968 683 1400 640 284 7051392 Medium Speed High Speed 208 230, 460, 575 230,460, 5751365 2038 1426 1331 1986 1400 2227 14611514 15361496 2240 1529 1603894 997 3055 1040 3333 Bhp Brake Horsepower Input to Fan882 895Rpm Bhp Watts 2550 669 627 867 692 1056 754 1062 3676 1102 3860 Bhp Brake Horsepower Input to Fan783 8121008 962973 10191166 Bhp Watts 37501178 1131FAN Performance Ð 579F180-300 Units Performance Data FAN Performance Ð 579F180-300 Units 579F240 20 Tons Air¯ow External Static Pressure in. wg 10,000 Bhp Brake Horsepower Input to FanRpm Bhp Watts 6000 9500579F300 25 Tons Air¯ow 10,500 11,000 11,250 Bhp Brake Horsepower Input to FanRpm Bhp Watts 500 3507Sound Weighted Octave Bands Unit Rating Sound Power Total UnitAIR Quantity Limits Unit Minimum CFM Maximum CFMACCESSORY/FIOP Static PRESSURE* in. wg − 579F180-300 ACCESSORY/FIOP Static PRESSURE* in. wg − 580D090-150Component CFM Unit Motor Pulley Turns OpenBtuh Nominal Altitude COMPENSATION* ÐNominal Input InputAltitude COMPENSATION* Ð 580D090-150 Fan Performance Using Accessory Power Exhaust 579F180-300EVAPORATOR-FAN Motor Efficiency Altitude Derating FACTOR* Ð ALL UnitsMaximum Unit EVAPORATOR-FAN Acceptable EVAPORATOR-FAN Motor PerformanceContinuous Operating AMP Draw BHP 580D036RLA LRA FLA MCA MOCP² Electrical Data Ð 580D036-150Electrical Data Ð 579F180-300 Vertical Discharge Ducting Typical Piping and Wiring Ð 580D036-150Horizontal Discharge Ducting NEC Ð National Electrical Code579F180 shown Typical Piping and Wiring Ð 579F180-300Typical Wiring Schematic Ð 580D036-150 Typical Wiring Schematic 579F240-300, 460-v shown PRI AHAIDM IFCOperating Sequence ControlsCooling, Units With Parablade Economizer 580D036-072 Controls580D036-150 Application DataApplication Data Part 1 Ð General Guide Specifications Ð 580D036-150Guide Specifications Ð 580D036-150 Guide Specifications Ð 580D036-150 Guide Specifications Ð 579F180-300 Guide Specifications Ð 579F180-300 Copyright 1998 Bryant Heating & Cooling Systems