GUIDE SPECIFICATIONS Ð 579F180-300
H.Filter Section:
Standard ®lter section shall consist of 2 sizes of factory- installed
I.Controls and Safeties:
1.Unit Controls:
a.Economizer control (optional)
b.Capacity control
c.Unit shall be complete with
2.Safeties:
a.Unit shall incorporate a
1)Compressor overtemperature, overcurrent.
2)
3)Freezestats (evaporator coil).
4)
b.
c.Heating section shall be provided with the follow- ing minimum protections:
1)
2)
3)Flame rollout switch.
4)Flame proving controls.
5)Redundant gas valve.
J.Operating Characteristics:
1.Unit shall be capable of starting and running at 115 F ambient outdoor temperature per maximum load crite- ria of ARI Standard 360.
2.Unit with standard controls will operate in cooling down to an outdoor ambient temperature of 40 F on 579F180 units, to 35 F on 216 units, to 25 F ambient on 240 units, and to 48 F ambient on 300 units.
3.Unit shall be provided with fan time delay to prevent cold air delivery.
K.Electrical Requirements:
All unit power wiring shall enter unit cabinet at a single location.
L.Motors:
1.All compressor motors shall be of the refrigerant cooled type with thermal and calibrated circuit breaker overload protection.
2.All fan motors shall have permanently lubricated, sealed bearings and inherent
3.All
1.Roof Curbs (Horizontal and Vertical):
a.Formed of
b.Permits installing and securing ductwork to curb prior to mounting unit on the curb.
2.Horizontal Adapter Roof Curb:
Includes
*3. Integrated Economizer:
a.Integrated type capable of simultaneous econo- mizer and compressor operation to provide cool- ing with outdoor air.
b.Equipped with
c.Capable of introducing up to 100% outdoor air.
d.Equipped with
e.Equipped with a
4.
5.Accessory Compressor Cycle Delay:
Compressor shall be prevented from restarting for a minimum of 5 minutes after shutdown.
*6. Thermostats and Subbases:
To provide staged heating and cooling in addition to automatic (or manual) changeover and fan control.
*7. Barometric Relief Damper Package:
a.Package shall include damper, seals, hardware, and hoods to relieve excess internal pressure.
b.Damper shall close due to gravity upon unit shut- down.
*8. Power Exhaust:
Package shall include an exhaust (propeller style) fan, 1¤2 Hp
*9. Head Pressure Control Package:
Consists of an accessory
10.
When used, allows units to operate at lower outdoor ambient temperatures. See trade prices for more information.
M.Special Features:
Certain features are not applicable when the features designated * are speci®ed. For assistance in amending the speci®cations, contact your local sales of®ce.