GUIDE SPECIFICATIONS Ð 579F180-300

H.Filter Section:

Standard ®lter section shall consist of 2 sizes of factory- installed 2-in. thick throwaway ®berglass ®lters of commercially available sizes.

I.Controls and Safeties:

1.Unit Controls:

a.Economizer control (optional)

b.Capacity control (2-step)

c.Unit shall be complete with self-contained low- voltage control circuit.

2.Safeties:

a.Unit shall incorporate a solid-state compressor lockout which provides reset capability at the space thermostat, should any of the following safety devices trip and shut off compressor:

1)Compressor overtemperature, overcurrent.

2)Low-pressure switch.

3)Freezestats (evaporator coil).

4)High-pressure switch.

b.Supply-air thermostat shall be located in the unit.

c.Heating section shall be provided with the follow- ing minimum protections:

1)High-temperature limit switch.

2)Induced-draft motor speed sensor.

3)Flame rollout switch.

4)Flame proving controls.

5)Redundant gas valve.

J.Operating Characteristics:

1.Unit shall be capable of starting and running at 115 F ambient outdoor temperature per maximum load crite- ria of ARI Standard 360.

2.Unit with standard controls will operate in cooling down to an outdoor ambient temperature of 40 F on 579F180 units, to 35 F on 216 units, to 25 F ambient on 240 units, and to 48 F ambient on 300 units.

3.Unit shall be provided with fan time delay to prevent cold air delivery.

K.Electrical Requirements:

All unit power wiring shall enter unit cabinet at a single location.

L.Motors:

1.All compressor motors shall be of the refrigerant cooled type with thermal and calibrated circuit breaker overload protection.

2.All fan motors shall have permanently lubricated, sealed bearings and inherent automatic-reset thermal overload protection or manual reset calibrated circuit breakers.

3.All indoor-fan motors 5 hp and larger shall meet the minimum ef®ciency requirements as established by the Energy Policy Act of 1992 (EPACT) effective Oc- tober 24, 1997.

1.Roof Curbs (Horizontal and Vertical):

a.Formed of 18-gage galvanized steel with wood nailer strip and shall be capable of supporting en- tire unit weight.

b.Permits installing and securing ductwork to curb prior to mounting unit on the curb.

2.Horizontal Adapter Roof Curb:

Includes factory-assembled adapter and duct and substantially improves evaporator fan static performance.

*3. Integrated Economizer:

a.Integrated type capable of simultaneous econo- mizer and compressor operation to provide cool- ing with outdoor air.

b.Equipped with low-leakage dampers not to exceed 3% leakage, at 1.0 in. wg pressure differential.

c.Capable of introducing up to 100% outdoor air.

d.Equipped with dry-bulb temperature control to govern economizer changeover.

e.Equipped with a mixed-air sensor that controls the economizer to a 55 F control point.

4.Two-Position Damper:

Two-position damper package shall include single blade damper and motor. Admits up to 25% outdoor air, and shall close upon unit shutoff.

5.Accessory Compressor Cycle Delay:

Compressor shall be prevented from restarting for a minimum of 5 minutes after shutdown.

*6. Thermostats and Subbases:

To provide staged heating and cooling in addition to automatic (or manual) changeover and fan control.

*7. Barometric Relief Damper Package:

a.Package shall include damper, seals, hardware, and hoods to relieve excess internal pressure.

b.Damper shall close due to gravity upon unit shut- down.

*8. Power Exhaust:

Package shall include an exhaust (propeller style) fan, 1¤2 Hp 208-230, 460 v (factory-wired for 460 v) motor, and damper for vertical ¯ow units with econo- mizer to control overpressurization of building.

*9. Head Pressure Control Package:

Consists of an accessory outdoor-air package and a solid-state control with condenser coil temperature sensor for controlling condenser-fan motor speed to maintain condensing temperature between 90 F and 100 F at outdoor ambient temperature down to ±20 F.

10.Low-Ambient Kits:

When used, allows units to operate at lower outdoor ambient temperatures. See trade prices for more information.

M.Special Features:

Certain features are not applicable when the features designated * are speci®ed. For assistance in amending the speci®cations, contact your local sales of®ce.

71

Image 71
Contents 580D036-072 579F180,216 580D090-150 579F240,300 FEATURES/BENEFITSPage Table of Contents 580D036-150 Models only Model Number NomenclatureModel Number Nomenclature 579F180-300 Models only ARI* Capacity Ratings Rise Efficiency ARI* Capacity RatingsHeating Capacities and Efficiencies Ð 580D036-150 Heating Capacities and Efficiencies Ð 579F180-300Unit Size 580D Physical Data Ð 580D036-072Unit Size 580D Medium LOW/MEDIUM High Heat Physical Data Ð 580D036-072Pulley Center Line Distance Std Physical Data Ð 580D090-150090 102 120 150 Nominal Capacity tons Quantity...Diameter Motor Hp...RpmUnit Size 580D LOW/MEDIUM High Heat Hihg Heat Medium Heat Physical Data Ð 580D090-150Unit Size 579F Physical Data Ð 579F180-300LOW/HIGH Heat Physical Data Ð 579F180-300Unit Size 579F Head Pressure Control Speed Control 180,216 Options and AccessoriesOption ACCESSORY² Head Pressure ControlSizes Options and AccessoriesTime Guard II Control Durablade EconomizerThermostat Power Exhaust 180-300 Shown Accusensor SensorAccusensor Control OnlyUnit Base Unit Dimensions Ð 580D036-072Unit Corner Weight Dimensions Base Unit Dimensions Ð 580D090-150486 220 636 288 Base Unit Dimensions Ð 579F180,216Dimension Base Unit Dimensions Ð 579F240,300Roof Curb Ð 580D036-072 Accessory DimensionsRoof Curb Ð 580D090-150 Accessory Dimensions579F Dimensions degrees and inchesPKG. NO. REF Curb Description Height Unit DEGPre-Assembled, High Static Horizontal Supply/Return Adapter Installation 579F180-300Power Exhaust 579F180-300 Accessory Curb Description Package no HeightII Select Unit Based on Required Cooling Capacity Selection Procedure with 579F180 exampleSHC Performance Data Cooling CapacitiesCooling Capacities Performance Data580D150 121¤2 Tons Performance Data Cooling Capacities580D120 10 Tons 5400/0.06 6000/0.07 7200/0.08 9000/0.09 579F180 15 Tons Temp F Air Entering Evaporator Ð Cfm/BF4500/0.08 5250/0.10 6000/0.11 6750/0.12 7500/0.14 Condenser 579F216 18 Tons7000/0.03 8750/0.05 10,000/0.07 11,250/0.09 579F240 20 Tons Temp F Air Entering Evaporator Ð Cfm/BF579F300 25 Tons 580D036 3 Tons Ð Alternate Motor Belt Drive FAN Performance Ð 580D036-150 Vertical Discharge Units580D036 3 Tons Ð Standard Motor Direct Drive Fiop580D048 4 Tons Ð Alternate Motor Belt Drive 580D048 4 Tons Ð Standard Motor Direct Drive580D060 5 Tons Ð Alternate Motor Belt Drive 580D060 5 Tons Ð Standard Motor Direct Drive1562 580D072 6 Tons Air¯ow External Static Pressure in. wgRpm Bhp Watts 1800 26003100 580D090 71¤2 Tons Air¯ow External Static Pressure in. wgRpm Bhp Watts 2250 2550904 2300 3400 580D102 81¤2 Tons Air¯ow External Static Pressure in. wgRpm Bhp Watts 2550 891 2188 3300985 580D120 10 Tons Air¯ow External Static Pressure in. wgRpm Bhp Watts 3000 43005200 580D150 121¤2 Tons Air¯ow External Static Pressure in. wgRpm Bhp Watts 3750 5100FAN Performance Ð 580D036-150 Horizontal Discharge Units 352 788 410 887 546 928 615 968 683 1400 640 284 705 1989 1466 2171 Bhp Brake Horsepower Input to FanRpm Bhp Watts 1200 569 189 641 299 761 357 859 483 901 546 943 609 1300 604 231 6731331 1986 1400 2227 1461 Medium Speed High Speed 208 230, 460, 575 230,460, 5751392 1365 2038 14261603 15361514 1496 2240 1529895 997 3055 1040 3333 Bhp Brake Horsepower Input to Fan894 882812 1062 3676 1102 3860 Bhp Brake Horsepower Input to FanRpm Bhp Watts 2550 669 627 867 692 1056 754 7831019 9621008 9731131 Bhp Watts 37501166 1178FAN Performance Ð 579F180-300 Units Performance Data FAN Performance Ð 579F180-300 Units 9500 10,000 Bhp Brake Horsepower Input to Fan579F240 20 Tons Air¯ow External Static Pressure in. wg Rpm Bhp Watts 60003507 10,500 11,000 11,250 Bhp Brake Horsepower Input to Fan579F300 25 Tons Air¯ow Rpm Bhp Watts 500Unit Minimum CFM Maximum CFM Sound Power Total UnitSound Weighted Octave Bands Unit Rating AIR Quantity LimitsUnit Motor Pulley Turns Open ACCESSORY/FIOP Static PRESSURE* in. wg − 580D090-150ACCESSORY/FIOP Static PRESSURE* in. wg − 579F180-300 Component CFMInput Altitude COMPENSATION* ÐBtuh Nominal Nominal InputAltitude Derating FACTOR* Ð ALL Units Fan Performance Using Accessory Power Exhaust 579F180-300Altitude COMPENSATION* Ð 580D090-150 EVAPORATOR-FAN Motor Efficiency580D036 EVAPORATOR-FAN Motor PerformanceMaximum Unit EVAPORATOR-FAN Acceptable Continuous Operating AMP Draw BHPRLA LRA FLA MCA MOCP² Electrical Data Ð 580D036-150Electrical Data Ð 579F180-300 NEC Ð National Electrical Code Typical Piping and Wiring Ð 580D036-150Vertical Discharge Ducting Horizontal Discharge Ducting579F180 shown Typical Piping and Wiring Ð 579F180-300Typical Wiring Schematic Ð 580D036-150 Typical Wiring Schematic 579F240-300, 460-v shown IFC AHAPRI IDMOperating Sequence ControlsCooling, Units With Parablade Economizer 580D036-072 Controls580D036-150 Application DataApplication Data Part 1 Ð General Guide Specifications Ð 580D036-150Guide Specifications Ð 580D036-150 Guide Specifications Ð 580D036-150 Guide Specifications Ð 579F180-300 Guide Specifications Ð 579F180-300 Copyright 1998 Bryant Heating & Cooling Systems