Carrier 50MP62L-10R, MPE62L-10R, 48MPD specifications Pre-Start-Up, System Check

Page 28

Fig. 41 Ð Compressor Mounting Ð

48/50MP62L Units

Fig. 42 Ð Front View of Compressor Mounting

Rail Assembly Ð 48/50MP70M-10R Units

COMPRESSOR MOUNTING FOOT

NUT

COMPRESSOR MOUNTING RAIL

Fig. 43 Ð Rear View of Compressor Mounting

Rail Assembly Ð 48/50MP70M-10R Units

PRE-START-UP

IMPORTANT: Before beginning Pre-Start-Up or Start- Up, review Start-Up Checklist at the center of this publication. The Checklist assures proper start-up of a unit and provides a record of unit condition, applica- tion requirements, system information, and operation at initial start-up.

Do not attempt to start the air-conditioning system until following checks have been completed.

System Check

1.Check the outside air hoods to ensure the hoods are fully opened and secure, with ®lters in place.

2.Check the supply fan and exhaust fan suspension brack- ets. Shipping spacers should be removed and sleds levelled to speci®cation.

3.Check compressor suspension. On 48/50MP62L units snubber washers can be moved with ®nger pressure. On all other units, rails allow compressors to ¯oat freely on compressor rail springs.

4.Electrical power source must agree with unit nameplate.

5.Check tightness of all electrical connections.

Failure to open discharge service valve prior to start- ing compressor can result in damage to or failure of the compressor.

6.Backseat (open) compressor suction and discharge shut- off valves. Close valves one turn to allow refrigerant pres- sure to reach the test gages.

7.Open liquid line service valves.

8.Oil should be visible in the compressor sight glasses. See Fig. 44. An acceptable oil level in the compressor is from 3¤8 to 1¤8 of sight glass (06E-299 compressors are 1¤8 of sight glass). Adjust the oil level as required. No oil should be removed unless the crankcase heater has been energized for at least 24 hours. Oil Charge section on page 49 for Carrier-approved oils.

9.Perform leak test. Be sure there are no refrigerant leaks. All units are shipped with a complete operating charge of R-22 and should be under sufficient pressure for leak testing after installation. If there is no system pressure, add refrigerant until a pressure is observed and check for leaks. After leaks are repaired, remove and recover refrigerant from system. For leak testing procedures, see GTAC 2, Module 5, Charging, Recovery, Recycling and Reclamation section. Do not use the system compres- sors to remove refrigerant from the system.

10.Crankcase heaters must be ®rmly locked into compres- sors, and must be on for 24 hours prior to start-up.

Crankcase heaters on all units are wired into the control circuit, so they are always operable as long as the main power supply disconnect is on (closed), even if any safety device is open. Compressor heat- ers must be on for 24 hours prior to the start-up of any compressor.

28

Image 28
Contents Installation, Start-Up and Service Instructions ContentsSafety Considerations ContentsGeneral Installation Install Outdoor HoodsPhysical Data Base Unit 48/50MPPhysical Data Optional Power Exhaust Specications Compressor Oil ChargeVariable Frequency Drive VFD Physical Data FAN MotorRoof Curb Dimensions, 48/50MP62L and 70M Roof Curb Dimensions, 48/50MP82N-10R Base Unit Dimensions, 48MP62L, 70M Base Unit Dimensions, 48MP82N-10R Base Unit Dimensions, 50MP62L and 70M Base Unit Dimensions, 50MP82N-10R Size Unit WeightUnit Field Electrical Connections Make Electrical ConnectionsGND EquipNEC Electrical Data FLALRA MCARecommended Sensor Device Non-Shielded Cable ManufacturerSpace Temperature Sensor Wiring Space Temperature Sensor Averaging Heat Interlock Relay Outdoor Air¯ow Control Transducer/Thermistor CCN Connection Approved Shielded Cables COM CCNComm Auxiliary Control Box Location 50MP70M Unit Shown Installing Flue/Inlet Hoods 48MP Units Only Gas Piping DetailsCheck Compressor Mounting Flue De¯ector Baffle AssembledPRE-START-UP System CheckEvaporator-Fan Belts, Pulleys, and Sheaves Ð ExampleFan Performance Forward Curved Ð 48/50MP62L Fan Performance Forward Curved Ð 48/50MP70MFan Performance Forward Curved Ð 48/50MP82N Fan Performance Forward Curved Ð 48/50MP90PFan Performance Forward Curved Ð 48/50MP10R Fan Performance Air Foil Ð 48/50MP62LFan Performance Air Foil Ð 48/50MP70M Fan Performance Air Foil Ð 48/50MP82NFan Performance Air Foil Ð 48/50MP90P Fan Performance Air Foil Ð 48/50MP10RControls Conguration and Quick Test Keypad and Display Module Hsio Configuration Hsio Keypad Key UsageSet Point Ranges and Defaults SET Point Subfunction Display Default Range START-UPInitial Check Basic Conguration DataSupply FAN GeneralOccupied Cooling IGC Control Board LED Alarms OverridesControl Loop Checkout 48/50MP Units SMG, SCV and MLG Recommended Starting ValuesControl System ComponentsIndex of Lead/Lag Circuits Compressors Lead CircuitKeypad and Display Module Hsio Stby YESSUB Functions Hsio Keypad and Display Module Functions and SubfunctionsFunction Service Variable Frequency Drive VFD DisplayPower Exhaust MOTORS, PULLEYS, and Belts EVAPORATOR-FAN MOTORS, PULLEYS, and BeltsRefrigerant Circuit LubricationManufacturer Lubricant Charging Chart Ð Unit 48/50MP62L Charging Chart Unit 48/50MP90P Adjustments Pressure Switch Settings Psig kPagBelt Installation and Tensioning Switch Cutout CUT-IN06E Compressors, Typical Gas Valve Adjustment Protective DevicesMain Burner Removal Compressor ProtectionVariable Frequency Drive VFD High-Voltage Relay Modules DSIO1 and DSIO2 Processor Modules PsioStby no Troubleshooting Compressor Replacement Ð Perform the followingTorque Compressors Troubleshooting and Diagnostics Problem Solution Compressor does not RUNCompressor Stops on HIGH-PRESSURE Switch Compressor Cycles on LOW-PRESSURE SwitchTroubleshooting and Diagnostics IGC Control Heating Ð 48MP Units Only Page Packaged Service Training Call for Free CatalogSTART-UP Checklist Model no Serial no Date TechnicianIII. Preliminary Checklist Items IV. START-UPCL-3 Fact Config Fanm

MPE62L-10R, 50MP62L-10R, 48MPD specifications

The Carrier 48MPD, 50MP62L-10R, and MPE62L-10R are advanced rooftop packaged units designed for a variety of commercial HVAC applications. These systems offer a compelling blend of energy efficiency, versatility, and high performance, making them ideal choices for businesses looking to enhance their indoor climate control.

One of the standout features of the Carrier 48MPD series is its high efficiency rating, which significantly reduces operational costs while minimizing environmental impact. The unit utilizes advanced scroll compressors that provide reliable and efficient cooling capabilities, ensuring optimal temperature regulation regardless of outdoor conditions. This innovative design also contributes to quieter operation, enhancing indoor comfort without disruptive noise levels.

The Carrier 50MP62L-10R model boasts superior cooling and heating capabilities, equipped with a multi-speed fan system that allows for tailored airflow to suit specific project requirements. This model's economizer feature is pivotal for harnessing outside air to offset mechanical cooling, leading to further energy savings, particularly in moderate weather conditions. Additionally, the unit's dual-fuel capability enhances its operational flexibility, allowing it to switch between electric and gas heating sources depending on efficiency needs.

In terms of control technologies, the MPE62L-10R is equipped with Carrier's advanced Smart Evaporator Control, which ensures precise humidity management while optimizing energy consumption. This model also integrates seamlessly with building automation systems, enabling remote monitoring and adjustments for greater operational oversight and efficiency. The intuitive user interface simplifies system programming and operation, making it accessible even for those without extensive technical backgrounds.

Another important characteristic of these units is their robust construction, designed to withstand challenging weather conditions and ensure longevity. The use of high-quality materials and components means lower maintenance costs over time.

Overall, the Carrier 48MPD, 50MP62L-10R, and MPE62L-10R represent a well-engineered suite of HVAC solutions that excel in efficiency, adaptability, and user-friendliness, establishing themselves as leading choices for commercial indoor climate management. With their blend of innovative technology and solid performance, these systems are well-suited to meet the diverse needs of modern commercial spaces.