The following color code is recommended:

SIGNAL

CCN BUS CONDUCTOR

COMM1 PLUG

TYPE

INSULATION COLOR

PIN NO.

1

RED

1

GROUND

WHITE

2

2

BLACK

3

NOTE: If a cable with a different color scheme is selec- ted, a similar color code should be adopted for the entire network.

At each system element, the shields of its communication bus cables must be tied together. If the communication bus is entirely within one building, the resulting continuous shield must be connected to a ground at one point only. If the communication bus cable exits from one building and enters another, the shields must be connected to grounds at the lightning suppressor in each building where the cable enters or exits the building (one point per building only).

To connect the unit to the network:

1.Turn off power to the control box.

2.Cut the CCN wire and strip the ends of the red (1), white (ground) and black (2) conductors. (If a different net- work color scheme is used, substitute appropriate colors.)

3.Remove the 4-pin female plug from the fuse and control circuit breaker bracket in the main control box, and con- nect the wires as follows:

a.Insert and secure the red (1) wire to terminal 1 of the 4-pin plug.

b.Insert and secure the white (ground) wire to terminal 2 of the 4-pin plug.

c.Insert and secure the black (2) wire to terminal 3 of the 4-pin plug.

4.Insert the plug into the existing 4-pin mating connector on the fuse or control circuit breaker bracket in the main control box.

IMPORTANT: A shorted CCN bus cable will pre- vent some routines from running and may prevent unit from starting. If abnormal conditions occur, un- plug the connector. If conditions return to normal, check CCN connector, and run new cable if nec- essary. A short in one section of the bus can cause problems with all system elements on the bus.

 

LEGEND

CCN

Ð Carrier Comfort Network

COM

Ð Common

COMM

Ð Communications

GND

Ð Ground

RJ11 PLUG WIRING Ð Units on the CCN can be moni- tored from the space at the sensor through the RJ11 con- nector, if desired. To wire the RJ11 connector into the CCN (Fig. 30):

IMPORTANT: The cable selected for the RJ11 con- nector wiring MUST be identical to the CCN com- munication bus wire used for the entire network. Re- fer to Table 7 for acceptable wiring.

1.Cut the CCN wire and strip ends of the red (1), white (ground), and black (2) conductors. (If another wire color scheme is used, strip ends of appropriate wires.)

2.Insert and secure the red (1) wire to pin J2 (T-55) or CCN + (T-56) of the space temperature sensor terminal block (TB1).

3.Insert and secure the white (ground) wire to pin J3 (T-55) or CCN GND (T-56) of the space temperature sensor TB1.

4.Insert and secure the black (2) wire to pin J5 (T-55) or CCN − (T-56) of the space temperature sensor TB1.

5.Connect the other end of the communication bus cable to the remainder of the CCN communication bus at the COMM1 plug located on the fuse and control circuit breaker bracket in the unit main control box.

Air Pressure Tubing Ð Before options such as supply fan VFD and modulating power exhaust can operate prop- erly, the pneumatic tubes for pressure sensing must be in- stalled. The recommended ®eld-supplied tubing for this use is a nominal 1¤4-in., ®re-retardant tubing.

The tubing must be run from the appropriate location in the building to the auxiliary control box in the unit. Figures 31 and 32 show the location and layout of the auxiliary control box in the 48/50MP unit. Figure 33 shows the connection locations for the tubing on the duct pressure (DP) controller for the VFD on the supply fan and on the building pressure (BP) controller for the VFD on the modu- lating power exhaust fan.

The tubing for the duct pressure control (DP) should sample supply duct pressure about 2¤3 of the way out from the unit in the main trunk duct. The tubing for the building pressure control (BP) should sample building pressure in the area near the entrance lobby so that location is controlled as closely to design pressures as possible.

*Constant volume applications only.

Fig. 30 Ð Space Sensor to Communication Bus Wiring

24

Image 24
Contents Installation, Start-Up and Service Instructions ContentsContents Safety ConsiderationsGeneral Installation Install Outdoor HoodsPhysical Data Base Unit 48/50MPPhysical Data Optional Power Exhaust Specications Compressor Oil ChargeVariable Frequency Drive VFD Physical Data FAN MotorRoof Curb Dimensions, 48/50MP62L and 70M Roof Curb Dimensions, 48/50MP82N-10R Base Unit Dimensions, 48MP62L, 70M Base Unit Dimensions, 48MP82N-10R Base Unit Dimensions, 50MP62L and 70M Base Unit Dimensions, 50MP82N-10R Unit Weight SizeUnit Field Electrical Connections Make Electrical ConnectionsEquip GNDNEC Electrical Data FLALRA MCARecommended Sensor Device Non-Shielded Cable ManufacturerSpace Temperature Sensor Wiring Space Temperature Sensor Averaging Heat Interlock Relay Outdoor Air¯ow Control Transducer/Thermistor CCN Connection Approved Shielded Cables CCN COMComm Auxiliary Control Box Location 50MP70M Unit Shown Installing Flue/Inlet Hoods 48MP Units Only Gas Piping DetailsCheck Compressor Mounting Flue De¯ector Baffle AssembledPRE-START-UP System CheckEvaporator-Fan Belts, Pulleys, and Sheaves Ð ExampleFan Performance Forward Curved Ð 48/50MP62L Fan Performance Forward Curved Ð 48/50MP70MFan Performance Forward Curved Ð 48/50MP82N Fan Performance Forward Curved Ð 48/50MP90PFan Performance Forward Curved Ð 48/50MP10R Fan Performance Air Foil Ð 48/50MP62LFan Performance Air Foil Ð 48/50MP70M Fan Performance Air Foil Ð 48/50MP82NFan Performance Air Foil Ð 48/50MP90P Fan Performance Air Foil Ð 48/50MP10RControls Conguration and Quick Test Keypad and Display Module Hsio Configuration Hsio Keypad Key UsageSet Point Ranges and Defaults SET Point Subfunction Display Default Range START-UPInitial Check Basic Conguration DataGeneral Supply FANOccupied Cooling IGC Control Board LED Alarms OverridesControl Loop Checkout 48/50MP Units SMG, SCV and MLG Recommended Starting ValuesControl System ComponentsIndex of Lead/Lag Circuits Compressors Lead CircuitKeypad and Display Module Hsio Stby YESHsio Keypad and Display Module Functions and Subfunctions SUB FunctionsFunction Service Variable Frequency Drive VFD DisplayPower Exhaust MOTORS, PULLEYS, and Belts EVAPORATOR-FAN MOTORS, PULLEYS, and BeltsLubrication Refrigerant CircuitManufacturer Lubricant Charging Chart Ð Unit 48/50MP62L Charging Chart Unit 48/50MP90P Adjustments Pressure Switch Settings Psig kPagBelt Installation and Tensioning Switch Cutout CUT-IN06E Compressors, Typical Gas Valve Adjustment Protective DevicesMain Burner Removal Compressor ProtectionVariable Frequency Drive VFD Processor Modules Psio High-Voltage Relay Modules DSIO1 and DSIO2Stby no Compressor Replacement Ð Perform the following TroubleshootingTorque Compressors Troubleshooting and Diagnostics Problem Solution Compressor does not RUNCompressor Stops on HIGH-PRESSURE Switch Compressor Cycles on LOW-PRESSURE SwitchTroubleshooting and Diagnostics IGC Control Heating Ð 48MP Units Only Page Packaged Service Training Call for Free CatalogSTART-UP Checklist Model no Serial no Date TechnicianIII. Preliminary Checklist Items IV. START-UPCL-3 Fact Config Fanm

MPE62L-10R, 50MP62L-10R, 48MPD specifications

The Carrier 48MPD, 50MP62L-10R, and MPE62L-10R are advanced rooftop packaged units designed for a variety of commercial HVAC applications. These systems offer a compelling blend of energy efficiency, versatility, and high performance, making them ideal choices for businesses looking to enhance their indoor climate control.

One of the standout features of the Carrier 48MPD series is its high efficiency rating, which significantly reduces operational costs while minimizing environmental impact. The unit utilizes advanced scroll compressors that provide reliable and efficient cooling capabilities, ensuring optimal temperature regulation regardless of outdoor conditions. This innovative design also contributes to quieter operation, enhancing indoor comfort without disruptive noise levels.

The Carrier 50MP62L-10R model boasts superior cooling and heating capabilities, equipped with a multi-speed fan system that allows for tailored airflow to suit specific project requirements. This model's economizer feature is pivotal for harnessing outside air to offset mechanical cooling, leading to further energy savings, particularly in moderate weather conditions. Additionally, the unit's dual-fuel capability enhances its operational flexibility, allowing it to switch between electric and gas heating sources depending on efficiency needs.

In terms of control technologies, the MPE62L-10R is equipped with Carrier's advanced Smart Evaporator Control, which ensures precise humidity management while optimizing energy consumption. This model also integrates seamlessly with building automation systems, enabling remote monitoring and adjustments for greater operational oversight and efficiency. The intuitive user interface simplifies system programming and operation, making it accessible even for those without extensive technical backgrounds.

Another important characteristic of these units is their robust construction, designed to withstand challenging weather conditions and ensure longevity. The use of high-quality materials and components means lower maintenance costs over time.

Overall, the Carrier 48MPD, 50MP62L-10R, and MPE62L-10R represent a well-engineered suite of HVAC solutions that excel in efficiency, adaptability, and user-friendliness, establishing themselves as leading choices for commercial indoor climate management. With their blend of innovative technology and solid performance, these systems are well-suited to meet the diverse needs of modern commercial spaces.