Carrier 48MPD, MPE62L-10R, 50MP62L-10R Recommended Sensor Device Non-Shielded Cable, Manufacturer

Page 17

Control Wiring Ð See Fig. 13 for sensor wiring con- nections to main and auxiliary control boxes. The recom- mended types of control wiring for 48/50MP unit devices are shown in Table 6.

Table 6 Ð Recommended Sensor and

Device Non-Shielded Cable

MANUFACTURER

PART NO.

Regular Wiring

Plenum Wiring

 

Alpha

1895

Ð

American

A21451

A48301

Belden

8205

884421

Columbia

D6451

Ð

Manhattan

M13402

M64430

Quabik

6130

Ð

 

 

 

SENSORS Ð Sensors should be wired using single twisted pairs of 20 AWG (American Wire Gage) conductor cable rated for the application, except for the T56 accessory sensor which requires 3-conductor cable.

NOTE: Humidity and CO2 sensors must be powered from isolated 24-v power supplies.

HUMIDITY CONTROL AND HOT WATER AND STEAM VALVES Ð These devices require 20 AWG twisted pair con- ductor cables rated for the application for the 4 to 20 mA signal.

SPACE TEMPERATURE SENSOR (T55) Ð The space tem- perature sensor (P/N CEC0121448-01) is shipped standard with every unit, and is located in the main control box. Space temperature sensor wires are to be connected to terminals in the unit main control box. The space temperature sensor includes a terminal block (TB1), a jumper between pins E2 and E3, and an RJ11 female connector. The RJ11 connector is used to tap into the Carrier Comfort Network (CCN) at the sensor. See RJ11 Plug Wiring section on page 24 to con- nect the RJ11 connector to the CCN. A 3-lead cable must run from the RJ11 connector to the unit for communication through the sensor.

Jumper MUST be in place between pins E2 and E3 or inaccurate readings could result.

To connect the space temperature sensor (Fig. 13):

1.Connect 1 wire of the twisted pair to terminal T1 (T55) and connect the other wire to terminal T2 on terminal block 1 (TB1) located on the cover of the space tempera- ture sensor using a 20 AWG twisted pair conductor cable rated for the application.

2.Connect the other ends of the wires to terminals 1 and 2 on TB3 located in the unit main control box.

NOTE: This sensor should be installed for all applica- tions. For VAV (variable air volume) applications, it is used to control heating and cooling during unoccupied periods. For DAV (digital air volume) applications, it is used to maintain control of the space during linkage fail- ures with the TSM (terminal system manager).

NOTE: Either the T55 or T56 sensor must be connect- ed for CV (constant volume) applications to function properly.

SPACE TEMPERATURE SENSOR (T56) (CV Applica- tions Only) Ð The space temperature sensor (P/N CEC0121503-01) wires are to be connected to termi- nals in the unit main control box. The space temperature sensor includes a terminal block (TB1), a jumper between

pins E2 and E3, and an RJ11 female connector. The RJ11 connector is used to tap into the CCN at the sensor. See RJ11 Plug Wiring section on page 24 to connect the RJ11 con- nector to the CCN.

Jumper MUST be in place between pins E2 and E3 or inaccurate readings could result.

To connect the space temperature sensor (Fig. 13):

1.Connect one wire of the 3-conductor cable to terminal TH, one wire to terminal COM, and the other wire to ter- minal SW on terminal block 1 (TB1) located on the cover of the space temperature sensor using a 20 AWG twisted 3-conductor cable rated for the application.

2.Connect the other ends of the wires to terminals 1, 2, and 3 on TB3 located in the unit main control box. The wire from terminal SW MUST be connected to terminal 3.

NOTE: Either the T55 or the T56 sensor must be con- nected for CV applications to function properly.

SPACE TEMPERATURE AVERAGING Ð Applications that require averaging using multiple space temperature sensors can be satis®ed using either 4 or 9 sensors as shown in Fig. 14.

NOTE: Only Carrier sensors may be used for standard T55 space averaging. Sensors must be used in multiples of 1, 4, and 9 only, with total sensors wiring not to exceed 1000 ft. However, space temperature reset can be accomplished with only one sensor.

NOTE: Do not use T56 sensors for space temperature averaging because the 5 degree offset function will not work in a multiple sensor application.

HEAT INTERLOCK RELAY (VAV Units Only Ð Not Nec- essary For Digital Air Volume Applications) Ð Variable air volume (VAV) units using optimal start (morning warm-up) and/or occupied heating require that room terminals be con- trolled to the fully open position when the unit goes into heating mode. The HIR (Heat Interlock Relay) function is provided for this control on DSIO no. 2, channel 60. When the unit goes into heating mode, the HIR is energized to pro- vide switch closure or opening (depending on how the ®eld- supplied power source is set up) to open the room terminals. The ®eld connections for the HIR are: Normally Closed, ter- minals 8 and 10 on TB3; and Normally Open, terminals 8 and 9 on TB3. See Fig. 15.

OPTION AND ACCESSORY CONTROL WIRING Ð The 48/50MP units may be used in applications with additional control features, options, or accessories. Refer to the Con- trols and Troubleshooting manual for more information con- cerning installation and con®guration of options and acces- sories. Figures 15 to 29 contain wiring information on the following features:

·heat interlock relay (Fig. 15)

·differential enthalpy sensor (Fig. 16)

·remote start (Fig. 17)

·accessory humidity control (Fig. 18)

·®re/smoke control (Fig. 19)

·indoor air quality (Fig. 20)

·outdoor air¯ow control (Fig. 21)

·timed discrete output (Fig. 22)

·humidi®er (Fig. 23)

·hydronic heating (Fig. 24)

·freezestat (Fig. 25)

·remote supply air temperature/space temperature offset (Fig. 26)

·transducer/thermistor (Fig. 27)

·CCN Building Supervisor (Fig. 28)

·variable frequency drive (VFD) (Fig. 29)

17

Image 17
Contents Contents Installation, Start-Up and Service InstructionsGeneral ContentsSafety Considerations Install Outdoor Hoods InstallationBase Unit 48/50MP Physical DataPhysical Data Compressor Oil Charge Optional Power Exhaust SpecicationsVariable Frequency Drive VFD Physical Data FAN MotorRoof Curb Dimensions, 48/50MP62L and 70M Roof Curb Dimensions, 48/50MP82N-10R Base Unit Dimensions, 48MP62L, 70M Base Unit Dimensions, 48MP82N-10R Base Unit Dimensions, 50MP62L and 70M Base Unit Dimensions, 50MP82N-10R Unit Unit WeightSize Make Electrical Connections Field Electrical ConnectionsNEC EquipGND FLA Electrical DataLRA MCAManufacturer Recommended Sensor Device Non-Shielded CableSpace Temperature Sensor Wiring Space Temperature Sensor Averaging Heat Interlock Relay Outdoor Air¯ow Control Transducer/Thermistor CCN Connection Approved Shielded Cables Comm CCNCOM Auxiliary Control Box Location 50MP70M Unit Shown Gas Piping Details Installing Flue/Inlet Hoods 48MP Units OnlyFlue De¯ector Baffle Assembled Check Compressor MountingSystem Check PRE-START-UPExample Evaporator-Fan Belts, Pulleys, and Sheaves ÐFan Performance Forward Curved Ð 48/50MP70M Fan Performance Forward Curved Ð 48/50MP62LFan Performance Forward Curved Ð 48/50MP90P Fan Performance Forward Curved Ð 48/50MP82NFan Performance Air Foil Ð 48/50MP62L Fan Performance Forward Curved Ð 48/50MP10RFan Performance Air Foil Ð 48/50MP82N Fan Performance Air Foil Ð 48/50MP70MFan Performance Air Foil Ð 48/50MP10R Fan Performance Air Foil Ð 48/50MP90PControls Conguration and Quick Test Hsio Keypad Key Usage Keypad and Display Module Hsio ConfigurationSet Point Ranges and Defaults START-UP SET Point Subfunction Display Default RangeInitial Check Basic Conguration DataOccupied Cooling GeneralSupply FAN Overrides IGC Control Board LED Alarms48/50MP Units SMG, SCV and MLG Recommended Starting Values Control Loop CheckoutComponents Control SystemIndex of Lead/Lag Circuits Compressors Lead CircuitStby YES Keypad and Display Module HsioFunction Hsio Keypad and Display Module Functions and SubfunctionsSUB Functions Variable Frequency Drive VFD Display ServiceEVAPORATOR-FAN MOTORS, PULLEYS, and Belts Power Exhaust MOTORS, PULLEYS, and BeltsManufacturer Lubricant LubricationRefrigerant Circuit Charging Chart Ð Unit 48/50MP62L Charging Chart Unit 48/50MP90P Pressure Switch Settings Psig kPag AdjustmentsBelt Installation and Tensioning Switch Cutout CUT-IN06E Compressors, Typical Protective Devices Gas Valve AdjustmentMain Burner Removal Compressor ProtectionVariable Frequency Drive VFD Stby no Processor Modules PsioHigh-Voltage Relay Modules DSIO1 and DSIO2 Torque Compressors Compressor Replacement Ð Perform the followingTroubleshooting Problem Solution Compressor does not RUN Troubleshooting and DiagnosticsCompressor Stops on HIGH-PRESSURE Switch Compressor Cycles on LOW-PRESSURE SwitchTroubleshooting and Diagnostics IGC Control Heating Ð 48MP Units Only Page Call for Free Catalog Packaged Service TrainingModel no Serial no Date Technician START-UP ChecklistIV. START-UP III. Preliminary Checklist ItemsCL-3 Fact Config Fanm

MPE62L-10R, 50MP62L-10R, 48MPD specifications

The Carrier 48MPD, 50MP62L-10R, and MPE62L-10R are advanced rooftop packaged units designed for a variety of commercial HVAC applications. These systems offer a compelling blend of energy efficiency, versatility, and high performance, making them ideal choices for businesses looking to enhance their indoor climate control.

One of the standout features of the Carrier 48MPD series is its high efficiency rating, which significantly reduces operational costs while minimizing environmental impact. The unit utilizes advanced scroll compressors that provide reliable and efficient cooling capabilities, ensuring optimal temperature regulation regardless of outdoor conditions. This innovative design also contributes to quieter operation, enhancing indoor comfort without disruptive noise levels.

The Carrier 50MP62L-10R model boasts superior cooling and heating capabilities, equipped with a multi-speed fan system that allows for tailored airflow to suit specific project requirements. This model's economizer feature is pivotal for harnessing outside air to offset mechanical cooling, leading to further energy savings, particularly in moderate weather conditions. Additionally, the unit's dual-fuel capability enhances its operational flexibility, allowing it to switch between electric and gas heating sources depending on efficiency needs.

In terms of control technologies, the MPE62L-10R is equipped with Carrier's advanced Smart Evaporator Control, which ensures precise humidity management while optimizing energy consumption. This model also integrates seamlessly with building automation systems, enabling remote monitoring and adjustments for greater operational oversight and efficiency. The intuitive user interface simplifies system programming and operation, making it accessible even for those without extensive technical backgrounds.

Another important characteristic of these units is their robust construction, designed to withstand challenging weather conditions and ensure longevity. The use of high-quality materials and components means lower maintenance costs over time.

Overall, the Carrier 48MPD, 50MP62L-10R, and MPE62L-10R represent a well-engineered suite of HVAC solutions that excel in efficiency, adaptability, and user-friendliness, establishing themselves as leading choices for commercial indoor climate management. With their blend of innovative technology and solid performance, these systems are well-suited to meet the diverse needs of modern commercial spaces.