Carrier MPE62L-10R, 50MP62L-10R, 48MPD specifications Installation, Install Outdoor Hoods

Page 3

INSTALLATION

Jobsite Survey Ð Complete the following checks be- fore installation.

1.Consult local building codes and the NEC (National Electrical Code) (ANSI/NFPA [National Fire Protection Association] 70) for special installation requirements.

2.Determine unit location (from project plans) or select unit location.

3.Check for possible overhead obstructions which may in- terfere with unit lifting or rigging.

Do not lift unit with forklift truck. Move unit with overhead rigging only.

Unit Placement Ð Inspect unit for transportation dam- age. File claim with transportation agency.

Provide clearance around and above unit for air¯ow, safety, and service access. Do not restrict top (area above con- denser fans) in any way. Allow at least 6 ft on all sides for rated performance, code compliance, and service.

Check unit dimensional drawings for unit arrangement and minimum performance and service clearances.

Do not install unit in an indoor location. Do not locate air inlets near exhaust vents or other sources of contaminated air.

On units equipped with power exhaust option, high velocity air is exhausted out the hood. Unit should be positioned with at least 10 ft clearance between the exhaust hood and any obstruction. Although unit is weatherproof, guard against water from higher level runoff and overhangs.

Level by using unit frame as a reference. Physical data is shown in Tables 1-4.

Roof Mount Ð Check building codes for weight distri- bution requirements. Unit weight is shown in Table 1. Unit may be mounted on class A, B, or C roo®ng material.

ROOF CURB Ð Assemble and install as described in in- structions shipped with the accessory. Accessory roof curb and information required to ®eld fabricate a roof curb is shown in Fig. 1 and 2. Install insulation, cant strips, roo®ng, and counter ¯ashing as required. For unit condensate drain to func- tion properly, curb must be level or within tolerances shown in Fig. 1 and 2.

STEEL BEAMS Ð If roof curb is not used, support unit with steel beams along its entire length and then support steel as required. As a minimum, unit must be supported across its width at each lifting lug location.

Slab Mount Ð Provide a level concrete slab that ex- tends beyond unit cabinet at least 6 inches. Make a slab 8 in. thick with 4 in. above grade. Use gravel apron in front of condenser coil air inlet to prevent grass and foliage from ob- structing air¯ow. Ensure that slab is of sufficient height to allow for 7-in. condensate trap.

Field-Fabricated Ductwork Ð Units are designed for vertical supply/return only. Field-fabricated ductwork should be attached to the roof curb. Supply and return duct dimen- sions are shown in Fig. 1-6.

To attach ductwork to roof curb, insert duct approxi- mately 10 to 11 in. up into roof curb. Connect ductwork to 14-gage roof curb material with sheet metal screws driven from inside of the duct.

Secure all ducts to the building structure, using ¯exible duct connectors between roof curb and ducts as required. Ducts passing through an unconditioned space must be insulated and covered with a vapor barrier. Outlet grilles must not lie directly below unit discharge. The return duct must have a 90-degree elbow before opening into the building space if unit is equipped with power exhaust.

Design supply duct strong enough to handle expected static pressures.

For vertical supply and return units, tools or parts could drop into ductwork and cause an injury. Install 90 de- gree turns in the supply and return ductwork between the unit and the conditioned space. If a 90 degree elbow cannot be installed, then grilles of sufficient strength and density should be installed to prevent objects from fall- ing into the conditioned space.

Rigging Ð Do not drop unit; keep upright. Use spreader bars over unit to prevent sling or cable damage. Leave con- denser coil shipping protection in place while rigging to prevent coil damage. All lifting lugs MUST be used when lifting unit.

Level by using unit frame as a reference. See Fig. 7 for information. Unit and accessory weights are shown in Tables 1-4. Weight distribution and center of gravity can be found in Fig. 8.

Condensate Drains Ð The condensate drain connec- tion is a 1 1¤2-in. NPT pipe connection located on the right hand side of the unit. See Fig. 9.

NOTE: Use a trap of at least 7-in. deep.

Condenser Coil Shipping Covers Ð Remove and discard.

Install Outdoor Hoods

1.Outdoor-air hoods are shipped bolted to the unit in a ship- ping position. To open hoods, remove the 3 holddown bars holding the air hood in shipping position. See Fig. 10.

2.Lift up the highest hood top and swing out hood sides to form the outside frame of the air hood. Fasten hood top to hood sides at middle and top holes only, using two screws on each side. See Fig. 11.

3.Remove the bottom hood block-off plate and set aside.

4.Swing up second hood (from the top of unit) into place and fasten to hood sides with screws provided using up- per hole only.

5.Swing up third hood (from the top of unit) into place and fasten to hood sides with screws provided using upper hole only.

6.Swing up fourth hood (bottom hood) into place. Before fastening hood to hood sides, swing down bottom ®lter rack. Fasten hood to hood sides with screws provided us- ing upper hole only.

7.Attach block off plate removed from Step 3.

8.Clip wire tie holding ®lter track. Swing ®lter track into position and fasten to hood sides using screws provided. Repeat until all 4 ®lter racks have been installed.

9.Apply a bead of RTV or similar sealant to corner of each hood at pivot point to prevent water leaks.

Copy continues on page 14.

3

Image 3
Contents Contents Installation, Start-Up and Service InstructionsContents Safety ConsiderationsGeneral Install Outdoor Hoods InstallationBase Unit 48/50MP Physical DataPhysical Data FAN Motor Optional Power Exhaust SpecicationsCompressor Oil Charge Variable Frequency Drive VFD Physical DataRoof Curb Dimensions, 48/50MP62L and 70M Roof Curb Dimensions, 48/50MP82N-10R Base Unit Dimensions, 48MP62L, 70M Base Unit Dimensions, 48MP82N-10R Base Unit Dimensions, 50MP62L and 70M Base Unit Dimensions, 50MP82N-10R Unit Weight SizeUnit Make Electrical Connections Field Electrical ConnectionsEquip GNDNEC MCA Electrical DataFLA LRAManufacturer Recommended Sensor Device Non-Shielded CableSpace Temperature Sensor Wiring Space Temperature Sensor Averaging Heat Interlock Relay Outdoor Air¯ow Control Transducer/Thermistor CCN Connection Approved Shielded Cables CCN COMComm Auxiliary Control Box Location 50MP70M Unit Shown Gas Piping Details Installing Flue/Inlet Hoods 48MP Units OnlyFlue De¯ector Baffle Assembled Check Compressor MountingSystem Check PRE-START-UPExample Evaporator-Fan Belts, Pulleys, and Sheaves ÐFan Performance Forward Curved Ð 48/50MP70M Fan Performance Forward Curved Ð 48/50MP62LFan Performance Forward Curved Ð 48/50MP90P Fan Performance Forward Curved Ð 48/50MP82NFan Performance Air Foil Ð 48/50MP62L Fan Performance Forward Curved Ð 48/50MP10RFan Performance Air Foil Ð 48/50MP82N Fan Performance Air Foil Ð 48/50MP70MFan Performance Air Foil Ð 48/50MP10R Fan Performance Air Foil Ð 48/50MP90PControls Conguration and Quick Test Hsio Keypad Key Usage Keypad and Display Module Hsio ConfigurationSet Point Ranges and Defaults Basic Conguration Data SET Point Subfunction Display Default RangeSTART-UP Initial CheckGeneral Supply FANOccupied Cooling Overrides IGC Control Board LED Alarms48/50MP Units SMG, SCV and MLG Recommended Starting Values Control Loop CheckoutLead Circuit Control SystemComponents Index of Lead/Lag Circuits CompressorsStby YES Keypad and Display Module HsioHsio Keypad and Display Module Functions and Subfunctions SUB FunctionsFunction Variable Frequency Drive VFD Display ServiceEVAPORATOR-FAN MOTORS, PULLEYS, and Belts Power Exhaust MOTORS, PULLEYS, and BeltsLubrication Refrigerant CircuitManufacturer Lubricant Charging Chart Ð Unit 48/50MP62L Charging Chart Unit 48/50MP90P Switch Cutout CUT-IN AdjustmentsPressure Switch Settings Psig kPag Belt Installation and Tensioning06E Compressors, Typical Compressor Protection Gas Valve AdjustmentProtective Devices Main Burner RemovalVariable Frequency Drive VFD Processor Modules Psio High-Voltage Relay Modules DSIO1 and DSIO2Stby no Compressor Replacement Ð Perform the following TroubleshootingTorque Compressors Compressor Cycles on LOW-PRESSURE Switch Troubleshooting and DiagnosticsProblem Solution Compressor does not RUN Compressor Stops on HIGH-PRESSURE SwitchTroubleshooting and Diagnostics IGC Control Heating Ð 48MP Units Only Page Call for Free Catalog Packaged Service TrainingModel no Serial no Date Technician START-UP ChecklistIV. START-UP III. Preliminary Checklist ItemsCL-3 Fact Config Fanm

MPE62L-10R, 50MP62L-10R, 48MPD specifications

The Carrier 48MPD, 50MP62L-10R, and MPE62L-10R are advanced rooftop packaged units designed for a variety of commercial HVAC applications. These systems offer a compelling blend of energy efficiency, versatility, and high performance, making them ideal choices for businesses looking to enhance their indoor climate control.

One of the standout features of the Carrier 48MPD series is its high efficiency rating, which significantly reduces operational costs while minimizing environmental impact. The unit utilizes advanced scroll compressors that provide reliable and efficient cooling capabilities, ensuring optimal temperature regulation regardless of outdoor conditions. This innovative design also contributes to quieter operation, enhancing indoor comfort without disruptive noise levels.

The Carrier 50MP62L-10R model boasts superior cooling and heating capabilities, equipped with a multi-speed fan system that allows for tailored airflow to suit specific project requirements. This model's economizer feature is pivotal for harnessing outside air to offset mechanical cooling, leading to further energy savings, particularly in moderate weather conditions. Additionally, the unit's dual-fuel capability enhances its operational flexibility, allowing it to switch between electric and gas heating sources depending on efficiency needs.

In terms of control technologies, the MPE62L-10R is equipped with Carrier's advanced Smart Evaporator Control, which ensures precise humidity management while optimizing energy consumption. This model also integrates seamlessly with building automation systems, enabling remote monitoring and adjustments for greater operational oversight and efficiency. The intuitive user interface simplifies system programming and operation, making it accessible even for those without extensive technical backgrounds.

Another important characteristic of these units is their robust construction, designed to withstand challenging weather conditions and ensure longevity. The use of high-quality materials and components means lower maintenance costs over time.

Overall, the Carrier 48MPD, 50MP62L-10R, and MPE62L-10R represent a well-engineered suite of HVAC solutions that excel in efficiency, adaptability, and user-friendliness, establishing themselves as leading choices for commercial indoor climate management. With their blend of innovative technology and solid performance, these systems are well-suited to meet the diverse needs of modern commercial spaces.