Carrier 50MP62L-10R, MPE62L-10R, 48MPD specifications Overrides, IGC Control Board LED Alarms

Page 40

5.As actual SAT approaches CCSR value, stages are re- leased. The minimum time delay between stages on de- creasing demand is 90 seconds.

NOTE: Demand for heating has priority and Master Loop will either terminate existing or prevent initiation of Cooling Cycle by issuing a CCSR at the maximum limit. This will cause the CSL to select zero stages of cooling capacity, initiating a stoppage of an existing cooling cycle.

CV Units Ð Supply fan must be ON for cooling control to operate. Sequence is as follows:

1.Master Loop will survey space temperature and space tem- perature offset inputs, then calculate CCSR value.

2.The CSL surveys actual SAT, then calculates number of capacity stages required to satisfy space load.

3.Stages of cooling capacity are initiated. (From zero stages, there will be a 1.5 to 3 minute delay before ®rst stage is initiated.)

UNOCCUPIED COOLING Ð The unoccupied cooling sequence of operation is similar to Occupied Cooling (see above) except for the following:

1.Supply Fan will be OFF as demand is initiated.

2.The Master Loop will start Supply Fan and cooling cycle. Fan status must be proved as ON within 2 minutes to con- tinue with cooling operation.

3.Control set point will be Unoccupied Cooling Set Point (UCSP).

4.At end of cooling cycle, Supply Fan will be turned OFF.

OVERRIDES

First Stage and Slow Change Override Ð The ®rst stage over- ride reduces cycling on the ®rst stage of capacity, and the slow change override prevents the addition or subtraction of another stage of capacity if the SAT is close to the set point and gradually moving towards the set point.

Low Temperature Override ÐThis override function pro- tects against rapid load decreases by removing a stage every 30 seconds when required based on temperature and the tem- perature rate of change.

High Temperature Override Ð This override function pro- tects against rapid load increases by adding a stage once every 60 seconds as required, based on temperature and tem- perature rate of change.

ADAPTIVE OPTIMAL START Ð Optimal start is used to heat up or cool down the space prior to occupancy. The purpose is to have the space temperature approach and then achieve the occupied set point by the time of occupancy. The control utilizes outdoor-air temperature, space temperature, occupied set point, and a ``K'' factor. The ``K'' factor is ex- pressed in minutes per degree, and calculates a start time offset, which is the time in minutes that the system shall be started in advance of the occupied time. The control moni- tors its results and adjusts the ``K'' factor to ensure that the occupied set point is achieved at time of occupancy rather than too early or too late.

ADAPTIVE OPTIMAL STOP (CV Applications Only) Ð Optimal stop is used to allow space temperature to drift to an expanded occupied set point during the last portion of an occupied period. The control calculates a stop time offset, (the time in minutes prior to the scheduled unoccupied time) during which expanded heating and cooling set points can be used. Adaptive optimal stop utilizes space temperature, an expanded occupied set point, and a ``K'' factor to calcu- late stop time offset. The amount (F) to expand the occupied

set point is user con®gurable. Like adaptive optimal start, the control corrects itself for optimal operation by adjusting the ``K'' factor as required.

GAS HEATING, OPERATION (48MP Units Only) Ð Re- fer to the Controls, Operation and Troubleshooting instruc- tions for information on the control logic used by the unit controls for gas heat operation.

The 48MPD units have 2 gas heat sections. The 48MPE units have 3 gas heat sections. Each individual section op- erates in the same manner.

NOTE: The 48MP units have 2 stages of heat.

When the PIC control calls for heating, power is sent to W on each IGC (integrated gas controller) board. An LED (light-emitting diode) on the IGC board will be on during normal operation. A check is made to ensure that the rollout switch and the limit switch are closed and the induced-draft motor is not running. The induced-draft motor is then en- ergized, and when speed is proven with the hall effect sensor on the motor, the ignition activation period begins. The burn- ers will ignite within 5 seconds.

If the burners do not light, there is a 22-second delay be- fore another 5-second attempt. If the burners still do not light, this sequence is repeated for 15 minutes. After the 15 min- utes have elapsed, if the burners have not been lit, heating is locked out. To reset the control, use the manual reset method found in the Controls Operation and Troubleshooting book.

When ignition occurs the IGC board will continue to moni- tor the condition of the rollout and limit switches, the hall effect sensor, and the ¯ame sensor.

When additional heat is required, W2 closes and initiates power to the second stage of the main gas valve. When the thermostat is satis®ed, W1 and W2 open and the gas valve closes, interrupitng the ¯ow of gas to the main burners. If the call for W1 lasted less than 1 minute, the heating cycle will not terminate until 1 minute after W1 became active.

An LED indicator is provided on the IGC to monitor op- eration. The IGC is located by removing the side panel and viewing the IGC through the view port located in the control box access panel. During normal operation, the LED is con- tinuously on. See Table 26 for error codes.

Table 26 Ð IGC Control Board LED Alarms

INDICATION

ERROR MODE

ON

Normal Operation

OFF

Hardware Failure

1 FLASH

Fan ON/OFF Delay Modi®ed

2 FLASHES

Limit Switch Fault

3 FLASHES

Flame Sense Fault

4 FLASHES

4 Consecutive Limit Switch Faults

5 FLASHES

Ignition Lockout Fault

6 FLASHES

Induced Draft Motor Fault

7 FLASHES

Rollout Switch Fault

8 FLASHES

Internal Control Fault

 

 

LEGEND

IGC Ð Integrated Gas Unit Controller

LED Ð Light-Emitting diode

NOTES:

1.There is a 3-second pause between error code displays.

2.If more than one error code exists, all applicable error codes will be displayed in numerical sequence.

3.Error codes on the IGC will be lost if power to the unit is interrupted.

40

Image 40
Contents Installation, Start-Up and Service Instructions ContentsSafety Considerations ContentsGeneral Installation Install Outdoor HoodsPhysical Data Base Unit 48/50MPPhysical Data Optional Power Exhaust Specications Compressor Oil ChargeVariable Frequency Drive VFD Physical Data FAN MotorRoof Curb Dimensions, 48/50MP62L and 70M Roof Curb Dimensions, 48/50MP82N-10R Base Unit Dimensions, 48MP62L, 70M Base Unit Dimensions, 48MP82N-10R Base Unit Dimensions, 50MP62L and 70M Base Unit Dimensions, 50MP82N-10R Size Unit WeightUnit Field Electrical Connections Make Electrical ConnectionsGND EquipNEC Electrical Data FLALRA MCARecommended Sensor Device Non-Shielded Cable ManufacturerSpace Temperature Sensor Wiring Space Temperature Sensor Averaging Heat Interlock Relay Outdoor Air¯ow Control Transducer/Thermistor CCN Connection Approved Shielded Cables COM CCNComm Auxiliary Control Box Location 50MP70M Unit Shown Installing Flue/Inlet Hoods 48MP Units Only Gas Piping DetailsCheck Compressor Mounting Flue De¯ector Baffle AssembledPRE-START-UP System CheckEvaporator-Fan Belts, Pulleys, and Sheaves Ð ExampleFan Performance Forward Curved Ð 48/50MP62L Fan Performance Forward Curved Ð 48/50MP70MFan Performance Forward Curved Ð 48/50MP82N Fan Performance Forward Curved Ð 48/50MP90PFan Performance Forward Curved Ð 48/50MP10R Fan Performance Air Foil Ð 48/50MP62LFan Performance Air Foil Ð 48/50MP70M Fan Performance Air Foil Ð 48/50MP82NFan Performance Air Foil Ð 48/50MP90P Fan Performance Air Foil Ð 48/50MP10RControls Conguration and Quick Test Keypad and Display Module Hsio Configuration Hsio Keypad Key UsageSet Point Ranges and Defaults SET Point Subfunction Display Default Range START-UPInitial Check Basic Conguration DataSupply FAN GeneralOccupied Cooling IGC Control Board LED Alarms OverridesControl Loop Checkout 48/50MP Units SMG, SCV and MLG Recommended Starting ValuesControl System ComponentsIndex of Lead/Lag Circuits Compressors Lead CircuitKeypad and Display Module Hsio Stby YESSUB Functions Hsio Keypad and Display Module Functions and SubfunctionsFunction Service Variable Frequency Drive VFD DisplayPower Exhaust MOTORS, PULLEYS, and Belts EVAPORATOR-FAN MOTORS, PULLEYS, and BeltsRefrigerant Circuit LubricationManufacturer Lubricant Charging Chart Ð Unit 48/50MP62L Charging Chart Unit 48/50MP90P Adjustments Pressure Switch Settings Psig kPagBelt Installation and Tensioning Switch Cutout CUT-IN06E Compressors, Typical Gas Valve Adjustment Protective DevicesMain Burner Removal Compressor ProtectionVariable Frequency Drive VFD High-Voltage Relay Modules DSIO1 and DSIO2 Processor Modules PsioStby no Troubleshooting Compressor Replacement Ð Perform the followingTorque Compressors Troubleshooting and Diagnostics Problem Solution Compressor does not RUNCompressor Stops on HIGH-PRESSURE Switch Compressor Cycles on LOW-PRESSURE SwitchTroubleshooting and Diagnostics IGC Control Heating Ð 48MP Units Only Page Packaged Service Training Call for Free CatalogSTART-UP Checklist Model no Serial no Date TechnicianIII. Preliminary Checklist Items IV. START-UPCL-3 Fact Config Fanm

MPE62L-10R, 50MP62L-10R, 48MPD specifications

The Carrier 48MPD, 50MP62L-10R, and MPE62L-10R are advanced rooftop packaged units designed for a variety of commercial HVAC applications. These systems offer a compelling blend of energy efficiency, versatility, and high performance, making them ideal choices for businesses looking to enhance their indoor climate control.

One of the standout features of the Carrier 48MPD series is its high efficiency rating, which significantly reduces operational costs while minimizing environmental impact. The unit utilizes advanced scroll compressors that provide reliable and efficient cooling capabilities, ensuring optimal temperature regulation regardless of outdoor conditions. This innovative design also contributes to quieter operation, enhancing indoor comfort without disruptive noise levels.

The Carrier 50MP62L-10R model boasts superior cooling and heating capabilities, equipped with a multi-speed fan system that allows for tailored airflow to suit specific project requirements. This model's economizer feature is pivotal for harnessing outside air to offset mechanical cooling, leading to further energy savings, particularly in moderate weather conditions. Additionally, the unit's dual-fuel capability enhances its operational flexibility, allowing it to switch between electric and gas heating sources depending on efficiency needs.

In terms of control technologies, the MPE62L-10R is equipped with Carrier's advanced Smart Evaporator Control, which ensures precise humidity management while optimizing energy consumption. This model also integrates seamlessly with building automation systems, enabling remote monitoring and adjustments for greater operational oversight and efficiency. The intuitive user interface simplifies system programming and operation, making it accessible even for those without extensive technical backgrounds.

Another important characteristic of these units is their robust construction, designed to withstand challenging weather conditions and ensure longevity. The use of high-quality materials and components means lower maintenance costs over time.

Overall, the Carrier 48MPD, 50MP62L-10R, and MPE62L-10R represent a well-engineered suite of HVAC solutions that excel in efficiency, adaptability, and user-friendliness, establishing themselves as leading choices for commercial indoor climate management. With their blend of innovative technology and solid performance, these systems are well-suited to meet the diverse needs of modern commercial spaces.