Carrier 48MPD Adjustments, Pressure Switch Settings Psig kPag, Belt Installation and Tensioning

Page 50

Replace the ®lter cores whenever the moisture/liquid in- dicator shows moisture in the system.

Follow instructions on the packaging for the replacement cores for disassembling and reassembling the ®lter assem- blies and housings.

Liquid Line Service Valve Ð Located immediately ahead of the ®lter drier, this valve has a 1¤4-in. ¯are connec- tion for ®eld charging. With the liquid circuit shut, the com- pressor can be used to pump the refrigerant down into the high side. The refrigerant can then be stored there by closing the compressor discharge valve.

Compressor Suction and Discharge Service Valves Ð Each compressor is provided with suction and discharge service valves. With these valves, the compressor can be isolated from the refrigerant system for servicing or replacing.

High-Pressure Switch Ð This switch has nonadjust- able settings. Figure 60 shows connection on a cylinder head. See Table 31 for pressure switch settings.

Table 31 Ð Pressure Switch Settings,

Psig (kPag)

SWITCH

CUTOUT

CUT-IN

High

426

± 7

320

± 20

(2935

± 48)

(2205

± 138)

 

Low

27

± 4

67 ± 7

(186 ± 28)

(462

± 48)

 

NOTE: High-pressure switch must be removed from cylin- der head before removing compressor from the unit.

TO CHECK Ð Slowly close the discharge shutoff valve until the compressor shuts down. This should be at approx- imately 426 psig (2935 kPag). Slowly open the valve. When the pressure drops to approximately 320 psig (2205 kPag), the pressure switch resets. To reenergize the control circuit, manually switch the fan circuit breaker off and then on. The compressor starts again under Time Guard controls.

Low-Pressure Switch Ð The low-pressure switch (LPS) has ®xed nonadjustable settings. It is located at the pump end of the compressor above the bearing head. See Table 31 for pressure switch settings.

TO CHECK Ð Slowly close the suction cut-off valve and allow the compressor to shut down. This should occur at approximately 27 psig (186 kPag). Slowly open the valve. The compressor restarts under Time Guard control when the pressure builds to approximately 67 psig (462 kPag).

Pressure Relief Ð High-side pressure relief is provided by a fusible plug in the liquid line at the serv- ice valve. For low-side pressure relief, a fusible plug is inserted in the side of the accumulator. See Fig. 60. A pres- sure relief valve installed on the compressor relieves at 450 psig (3102 kPag).

Adjustments

EVAPORATOR FAN AND POWER EXHAUST MOTOR PLATE Ð Adjust using a 15¤16-in. wrench on the adjusting bolts:

1.Loosen holddown bolts. (See Fig. 61.)

2.Turn the adjusting bolts to move the motor mounting plate toward or away from the fan to loosen or tighten the belts. Make the same number of turns to each bolt.

3.Retighten holddown bolts.

BELT INSTALLATION AND TENSIONING

IMPORTANT: When installing or replacing belts, al- ways use a complete set of new, matched belts to pre- vent potential vibration problems. Mixing belts often results in premature breakage of the new belts.

1.Turn off unit power.

2.Adjust motor plate so belts can be installed without stretch- ing over the grooves of the pulley. (Forcing the belts can result in uneven belt stretching and a mismatched set of belts.)

3.Before tensioning the belts, equalize belt slack so that it is on the same side of the belt for all belts. Failure to do so may result in uneven belt stretching.

4.Tighten belts using the motor plate adjusting bolts.

5.Adjust until proper belt tension (1/2-in. de¯ection with one ®nger) is obtained. Be sure to adjust both adjusting bolts the same number of turns.

NOTE: Check the tension at least twice during the ®rst day of operation, as there is normally a rapid decrease in tension until the belts have run in. Check tension periodically thereafter and keep it at the recommended tension.

With the correct belt tension, belts may slip and squeal momentarily on start-up. This slippage is normal and dis- appears after wheel reaches operating speed. Excessive belt tension shortens belt life and may cause bearing and shaft damage.

50

Image 50
Contents Installation, Start-Up and Service Instructions ContentsGeneral ContentsSafety Considerations Installation Install Outdoor HoodsPhysical Data Base Unit 48/50MPPhysical Data Variable Frequency Drive VFD Physical Data Optional Power Exhaust SpecicationsCompressor Oil Charge FAN MotorRoof Curb Dimensions, 48/50MP62L and 70M Roof Curb Dimensions, 48/50MP82N-10R Base Unit Dimensions, 48MP62L, 70M Base Unit Dimensions, 48MP82N-10R Base Unit Dimensions, 50MP62L and 70M Base Unit Dimensions, 50MP82N-10R Unit Unit WeightSize Field Electrical Connections Make Electrical ConnectionsNEC EquipGND LRA Electrical DataFLA MCARecommended Sensor Device Non-Shielded Cable ManufacturerSpace Temperature Sensor Wiring Space Temperature Sensor Averaging Heat Interlock Relay Outdoor Air¯ow Control Transducer/Thermistor CCN Connection Approved Shielded Cables Comm CCNCOM Auxiliary Control Box Location 50MP70M Unit Shown Installing Flue/Inlet Hoods 48MP Units Only Gas Piping DetailsCheck Compressor Mounting Flue De¯ector Baffle AssembledPRE-START-UP System CheckEvaporator-Fan Belts, Pulleys, and Sheaves Ð ExampleFan Performance Forward Curved Ð 48/50MP62L Fan Performance Forward Curved Ð 48/50MP70MFan Performance Forward Curved Ð 48/50MP82N Fan Performance Forward Curved Ð 48/50MP90PFan Performance Forward Curved Ð 48/50MP10R Fan Performance Air Foil Ð 48/50MP62LFan Performance Air Foil Ð 48/50MP70M Fan Performance Air Foil Ð 48/50MP82NFan Performance Air Foil Ð 48/50MP90P Fan Performance Air Foil Ð 48/50MP10RControls Conguration and Quick Test Keypad and Display Module Hsio Configuration Hsio Keypad Key UsageSet Point Ranges and Defaults Initial Check SET Point Subfunction Display Default RangeSTART-UP Basic Conguration DataOccupied Cooling GeneralSupply FAN IGC Control Board LED Alarms OverridesControl Loop Checkout 48/50MP Units SMG, SCV and MLG Recommended Starting ValuesIndex of Lead/Lag Circuits Compressors Control SystemComponents Lead CircuitKeypad and Display Module Hsio Stby YESFunction Hsio Keypad and Display Module Functions and SubfunctionsSUB Functions Service Variable Frequency Drive VFD DisplayPower Exhaust MOTORS, PULLEYS, and Belts EVAPORATOR-FAN MOTORS, PULLEYS, and BeltsManufacturer Lubricant LubricationRefrigerant Circuit Charging Chart Ð Unit 48/50MP62L Charging Chart Unit 48/50MP90P Belt Installation and Tensioning AdjustmentsPressure Switch Settings Psig kPag Switch Cutout CUT-IN06E Compressors, Typical Main Burner Removal Gas Valve AdjustmentProtective Devices Compressor ProtectionVariable Frequency Drive VFD Stby no Processor Modules PsioHigh-Voltage Relay Modules DSIO1 and DSIO2 Torque Compressors Compressor Replacement Ð Perform the followingTroubleshooting Compressor Stops on HIGH-PRESSURE Switch Troubleshooting and DiagnosticsProblem Solution Compressor does not RUN Compressor Cycles on LOW-PRESSURE SwitchTroubleshooting and Diagnostics IGC Control Heating Ð 48MP Units Only Page Packaged Service Training Call for Free CatalogSTART-UP Checklist Model no Serial no Date TechnicianIII. Preliminary Checklist Items IV. START-UPCL-3 Fact Config Fanm

MPE62L-10R, 50MP62L-10R, 48MPD specifications

The Carrier 48MPD, 50MP62L-10R, and MPE62L-10R are advanced rooftop packaged units designed for a variety of commercial HVAC applications. These systems offer a compelling blend of energy efficiency, versatility, and high performance, making them ideal choices for businesses looking to enhance their indoor climate control.

One of the standout features of the Carrier 48MPD series is its high efficiency rating, which significantly reduces operational costs while minimizing environmental impact. The unit utilizes advanced scroll compressors that provide reliable and efficient cooling capabilities, ensuring optimal temperature regulation regardless of outdoor conditions. This innovative design also contributes to quieter operation, enhancing indoor comfort without disruptive noise levels.

The Carrier 50MP62L-10R model boasts superior cooling and heating capabilities, equipped with a multi-speed fan system that allows for tailored airflow to suit specific project requirements. This model's economizer feature is pivotal for harnessing outside air to offset mechanical cooling, leading to further energy savings, particularly in moderate weather conditions. Additionally, the unit's dual-fuel capability enhances its operational flexibility, allowing it to switch between electric and gas heating sources depending on efficiency needs.

In terms of control technologies, the MPE62L-10R is equipped with Carrier's advanced Smart Evaporator Control, which ensures precise humidity management while optimizing energy consumption. This model also integrates seamlessly with building automation systems, enabling remote monitoring and adjustments for greater operational oversight and efficiency. The intuitive user interface simplifies system programming and operation, making it accessible even for those without extensive technical backgrounds.

Another important characteristic of these units is their robust construction, designed to withstand challenging weather conditions and ensure longevity. The use of high-quality materials and components means lower maintenance costs over time.

Overall, the Carrier 48MPD, 50MP62L-10R, and MPE62L-10R represent a well-engineered suite of HVAC solutions that excel in efficiency, adaptability, and user-friendliness, establishing themselves as leading choices for commercial indoor climate management. With their blend of innovative technology and solid performance, these systems are well-suited to meet the diverse needs of modern commercial spaces.