Carrier MPE62L-10R, 50MP62L-10R, 48MPD specifications General, Supply FAN, Occupied Cooling

Page 39

General

NOTE: If unit is equipped with REMOTE START function, place the LOCAL/REMOTE switch in the LOCAL (Off) position.

1.Put the ON/OFF switch in the ON position. Close the con- trol circuit breaker (CCB), which will energize the con- trol circuit and the crankcase heaters.

2.Using the HSIO or Building Supervisor, verify that no alarms have been detected.

3.Ensure that quick test has been performed to make sure that the controls are operating properly. Refer to the Con- trols and Troubleshooting Guide for more information.

4.Using the HSIO, put the unit into Run mode.

a.Press .

b.Press .

c.Press CLEAR . This will put the unit in Run mode.

d.Press . The unit will change from mode 25

(standby), to mode 32 (occupied) or mode 27 (unoc- cupied) depending on the programmed time schedule.

Operating Sequences Ð Base unit operating sequences are presented below. Refer to unit Controls and Troubleshooting literature for expanded details on unit con- trols operation, additional controls functions, and logic theory.

SUPPLY FAN

VAV Units Ð During Occupied periods, the control will en- ergize the supply fan contactor. The contactor will close, energizing supply fan motor. Fan wheel will turn. Air¯ow Switch (differential pressure switch) contacts close, provid- ing discrete input (DI) to Channel 12 (Closed = Fan ON). Fan operation will continue through the Occupied period.

During Unoccupied period with demand, the control will energize fan contactor when demand is sensed. After fan sta- tus is con®rmed, operating routines will start. When demand is removed, routines will end and fan will shut off.

CV Units, Continuous Fan Ð During Occupied periods, the control will energize the supply fan contactor. The contactor will close, energizing supply fan motor. Fan wheel will turn. Air¯ow Switch (differential pressure switch) contacts close, providing discrete input (DI) to Channel 12 (Closed = Fan ON). Fan operation will continue through the Occupied period.

During Unoccupied period with demand, the control will energize fan contactor when demand is sensed. After fan sta- tus is con®rmed, operating routines will start. When demand is removed, routines will end and fan will shut off.

CV Units, Automatic Fan Ð Fan will be turned OFF during Occupied period when there is no demand for heating or cool- ing operation. When demand is sensed, control will energize fan contactor and initiate cooling cycle. Fan status will be con®rmed. When demand is removed, routines will termi- nate and fan will be shut off.

ECONOMIZER Ð The economizer control loop will be de- layed 2 minutes after the supply fan is turned ON, to allow system and temperatures to stabilize before starting control. When coming out of STANDBY or Heating mode, a 4-minute delay will occur before the economizer damper is con- trolled. During this delay, damper position is limited to CLOSED or MINIMUM position (depending on current unit occu- pancy status).

If fan status is OFF, the outside air dampers will remain closed (return air dampers will be open). If fan status is ON, the outside air dampers will normally be at minimum damper position.

Economizer operation is permitted if the system is not in Heating mode, if outdoor air enthalpy (via switch or humid- ity differential) is acceptable, and if outside air temperature is less than space temperature.

If economizer operation is permitted, the ecomizer con- trol loop checks for Cooling System operation. If ON, the outside air dampers will be driven to maximum position.

If cooling is not on , for VAV units, the economizer will modulate to satisfy the supply air set point.

If cooling is not on, for CV units, the economizer will modulate to satisfy the space temperature set point.

If Economizer operation is not permitted, the outside air dampers will be driven to minimum position (during Occu- pied period) or closed (during Unoccupied period).

For VAV units, Economizer operation is not permitted when Occupied Heating is enabled and the Return Air Tempera- ture is LESS THAN (OHSP + 1).

COOLING (All Units) Ð The controls try to control the supply- air temperature (SAT) to a system-calculated coil reference temperature value by cycling the compressors and the unloader(s). Both the supply- and return-air temperature sen- sors are used to adjust the cycling deadband to match the actual load. The control system provides cooling capacity control of up to 11 stages to maintain supply-air temperature (VAV) or space temperature (CV) to an occupied or un- occupied set point. Automatic lead-lag circuit switching occurs (if con®gured) to equalize run times per compressor for improved compressor reliability. The compressor to start ®rst is changed every time stage equals zero.

NOTE: Automatic lead/lag should be disabled if optional hot gas bypass is employed because the unit only contains hot gas bypass on one circuit.

The VAV control system sequence uses the modi®ed supply- air set point (MSAT = supply-air set point 1 reset value) as the supply-air temperature required to satisfy conditions (sub- master reference value [CSSR]) and outputs this value to the submaster loop.

The submaster loop uses the modi®ed supply-air set point compared to the actual supply-air temperature to determine the required number of capacity stages to satisfy the load. The logic for determining when to add or subtract a stage is a time-based integration of the deviation from the set point plus the rate of change of the supply-air temperature.

The CV control system sequence reads the space sensor and performs a calculation to determine the supply-air tem- perature required (a cooling coil submaster reference [CCSR] value) to satisfy conditions and outputs this value to the sub- master loop.

OCCUPIED COOLING

General Ð Economizer cycle must not be usable or damper position must be open to 90% or higher.

VAV Units Ð Supply fan must be ON for cooling control to operate. Sequence is as follows:

1.Unit must not be in Heating mode.

2.Master Loop will survey occupancy status, Supply Air Set Point (SASP) and any Supply Air Temperature Reset command, then issue Cooling Coil Submaster Reference (CCSR) to Cooling Submaster Loop (CSL).

3.The CSL surveys actual SAT, then calculates number of capacity stages required to produce the CCSR leaving the unit.

4.Stages of cooling capacity are initiated. From zero stages, there will be a 1.5 to 3 minute delay before the ®rst stage is initiated. The time delay between stages in increasing demand is 90 seconds.

39

Image 39
Contents Contents Installation, Start-Up and Service InstructionsContents Safety ConsiderationsGeneral Install Outdoor Hoods InstallationBase Unit 48/50MP Physical DataPhysical Data FAN Motor Optional Power Exhaust SpecicationsCompressor Oil Charge Variable Frequency Drive VFD Physical DataRoof Curb Dimensions, 48/50MP62L and 70M Roof Curb Dimensions, 48/50MP82N-10R Base Unit Dimensions, 48MP62L, 70M Base Unit Dimensions, 48MP82N-10R Base Unit Dimensions, 50MP62L and 70M Base Unit Dimensions, 50MP82N-10R Unit Weight SizeUnit Make Electrical Connections Field Electrical ConnectionsEquip GNDNEC MCA Electrical DataFLA LRAManufacturer Recommended Sensor Device Non-Shielded CableSpace Temperature Sensor Wiring Space Temperature Sensor Averaging Heat Interlock Relay Outdoor Air¯ow Control Transducer/Thermistor CCN Connection Approved Shielded Cables CCN COMComm Auxiliary Control Box Location 50MP70M Unit Shown Gas Piping Details Installing Flue/Inlet Hoods 48MP Units OnlyFlue De¯ector Baffle Assembled Check Compressor MountingSystem Check PRE-START-UPExample Evaporator-Fan Belts, Pulleys, and Sheaves ÐFan Performance Forward Curved Ð 48/50MP70M Fan Performance Forward Curved Ð 48/50MP62LFan Performance Forward Curved Ð 48/50MP90P Fan Performance Forward Curved Ð 48/50MP82NFan Performance Air Foil Ð 48/50MP62L Fan Performance Forward Curved Ð 48/50MP10RFan Performance Air Foil Ð 48/50MP82N Fan Performance Air Foil Ð 48/50MP70MFan Performance Air Foil Ð 48/50MP10R Fan Performance Air Foil Ð 48/50MP90PControls Conguration and Quick Test Hsio Keypad Key Usage Keypad and Display Module Hsio ConfigurationSet Point Ranges and Defaults Basic Conguration Data SET Point Subfunction Display Default RangeSTART-UP Initial CheckGeneral Supply FANOccupied Cooling Overrides IGC Control Board LED Alarms48/50MP Units SMG, SCV and MLG Recommended Starting Values Control Loop CheckoutLead Circuit Control SystemComponents Index of Lead/Lag Circuits CompressorsStby YES Keypad and Display Module HsioHsio Keypad and Display Module Functions and Subfunctions SUB FunctionsFunction Variable Frequency Drive VFD Display ServiceEVAPORATOR-FAN MOTORS, PULLEYS, and Belts Power Exhaust MOTORS, PULLEYS, and BeltsLubrication Refrigerant CircuitManufacturer Lubricant Charging Chart Ð Unit 48/50MP62L Charging Chart Unit 48/50MP90P Switch Cutout CUT-IN AdjustmentsPressure Switch Settings Psig kPag Belt Installation and Tensioning06E Compressors, Typical Compressor Protection Gas Valve AdjustmentProtective Devices Main Burner RemovalVariable Frequency Drive VFD Processor Modules Psio High-Voltage Relay Modules DSIO1 and DSIO2Stby no Compressor Replacement Ð Perform the following TroubleshootingTorque Compressors Compressor Cycles on LOW-PRESSURE Switch Troubleshooting and DiagnosticsProblem Solution Compressor does not RUN Compressor Stops on HIGH-PRESSURE SwitchTroubleshooting and Diagnostics IGC Control Heating Ð 48MP Units Only Page Call for Free Catalog Packaged Service TrainingModel no Serial no Date Technician START-UP ChecklistIV. START-UP III. Preliminary Checklist ItemsCL-3 Fact Config Fanm

MPE62L-10R, 50MP62L-10R, 48MPD specifications

The Carrier 48MPD, 50MP62L-10R, and MPE62L-10R are advanced rooftop packaged units designed for a variety of commercial HVAC applications. These systems offer a compelling blend of energy efficiency, versatility, and high performance, making them ideal choices for businesses looking to enhance their indoor climate control.

One of the standout features of the Carrier 48MPD series is its high efficiency rating, which significantly reduces operational costs while minimizing environmental impact. The unit utilizes advanced scroll compressors that provide reliable and efficient cooling capabilities, ensuring optimal temperature regulation regardless of outdoor conditions. This innovative design also contributes to quieter operation, enhancing indoor comfort without disruptive noise levels.

The Carrier 50MP62L-10R model boasts superior cooling and heating capabilities, equipped with a multi-speed fan system that allows for tailored airflow to suit specific project requirements. This model's economizer feature is pivotal for harnessing outside air to offset mechanical cooling, leading to further energy savings, particularly in moderate weather conditions. Additionally, the unit's dual-fuel capability enhances its operational flexibility, allowing it to switch between electric and gas heating sources depending on efficiency needs.

In terms of control technologies, the MPE62L-10R is equipped with Carrier's advanced Smart Evaporator Control, which ensures precise humidity management while optimizing energy consumption. This model also integrates seamlessly with building automation systems, enabling remote monitoring and adjustments for greater operational oversight and efficiency. The intuitive user interface simplifies system programming and operation, making it accessible even for those without extensive technical backgrounds.

Another important characteristic of these units is their robust construction, designed to withstand challenging weather conditions and ensure longevity. The use of high-quality materials and components means lower maintenance costs over time.

Overall, the Carrier 48MPD, 50MP62L-10R, and MPE62L-10R represent a well-engineered suite of HVAC solutions that excel in efficiency, adaptability, and user-friendliness, establishing themselves as leading choices for commercial indoor climate management. With their blend of innovative technology and solid performance, these systems are well-suited to meet the diverse needs of modern commercial spaces.