Carrier 50MP62L-10R, MPE62L-10R, 48MPD specifications Charging Chart Unit 48/50MP90P

Page 49

LIQUID TEMPERATURE AT LIQUID VALVE (DEG F)

150

 

125

ADD CHARGE IF ABOVE CURVE

 

100

 

75

REMOVE CHARGE IF BELOW CURVE

 

50

 

100

150

200

250

300

350

400

 

LIQUID PRESSURE AT LIQUID VALVE (PSIG)

 

 

ALL OUTDOOR FANS MUST BE OPERATING

Fig. 58 Ð Charging Chart Unit 48/50MP90P

LIQIUD TEMPERATURE AT LIQUID VALVE (DEG F)

150

130

110

90

70

50

100

TEMPERATURELIQUID

(DEGVALVELIQUIDAT F)

150

 

125

 

ADD CHARGE IF ABOVE CURVE

 

ADD CHARGE IF ABOVE CURVE

 

 

 

REMOVE CHARGE IF BELOW CURVE

 

100

 

 

 

 

 

 

75

REMOVE CHARGE IF BELOW CURVE

 

 

 

 

 

50

 

150

200

250

300

350

400

450

 

 

 

 

 

 

 

LIQUID PRESSURE AT LIQUID VALVE (PSIG)

 

100

150

200

250

300

350

400

 

 

 

 

 

 

 

 

 

LIQUID PRESSURE AT LIQUID VALVE (PSIG)

ALL OUTDOOR FANS MUST BE RUNNING

Fig. 59 Ð Charging Chart Ð Unit 48/50MP10R

Charging with Unit Off and Evacuated Ð Close liquid line service valve before charging. Weigh in charge shown in Table 1. Open liquid line service valve; start unit and allow it to run several minutes fully loaded. Check for a clear sight glass. Be sure clear condition is liquid and not vapor. Complete charging the unit.

Charging with Unit Running Ð If charge is to be added while unit is operating, it is necessary to have all condenser fans and compressors operating. It may be necessary to block con- denser coils at low-ambient temperatures to raise condens- ing pressure to approximately 280 psig (1931 kPag) to turn all condenser fans on. Do not totally block a coil to do this. Partially block all coils in uniform pattern. Charge vapor into compressor low-side service port located above oil pump crank- shaft housing. Charge each circuit until sight glass shows clear liquid.

Oil Charge (Refer to Table 3) Ð All units are fac- tory charged with oil. Acceptable oil level for each compres- sor is from 3¤8 to 1¤8 (on 06E299, 1¤8 max) of sight glass (see Fig. 44, page 29).

When additional oil or a complete charge is required, use only Carrier-approved compressor oil.

Approved oils are:

Petroleum Specialties, Inc. Ð Cryol 150A (factory oil charge)

Texaco, Inc.

Ð Capella WF-32-150

Witco Chemical Co.

Ð Suniso 3GS

Do not reuse drained oil, and do not use any oil that has been exposed to atmosphere.

ADD OIL Ð Close suction shutoff valve and pump down crankcase to 2 psig (14 kPa). (Low-pressure cutout must be jumped.) Wait a few minutes and repeat until pressure re- mains steady at 2 psig (14 kPa). Remove oil ®ll plug above the oil level sight glass, add oil through plug hole, and re- place plug. Run compressor for 20 minutes and check oil level.

IMPORTANT: For units with 2 compressors per re- frigeration circuit, both compressors must be running to adjust the oil level. Two oil level equalizer lines be- tween compressors distribute the oil to each compressor.

REMOVE OIL Ð Pump down compressor to 2 psig (14 kPag). Loosen the 1¤4-in. (6.4-mm) pipe plug at the com- pressor base and allow the oil to seep out past the threads of the plug.

NOTE: The crankcase will be slightly pressurized. Do not remove the plug, or the entire oil charge will be lost.

Small amounts of oil can be removed through the oil pump discharge connection while the compressor is running.

Moisture/Liquid Indicator Ð A clear ¯ow of liquid refrigerant indicates sufficient charge in the system. Bubbles indicate undercharged system or the presence of non- condensables. Moisture in the system measured in parts per million (ppm) changes the color of the indicator:

Green

Ð moisture below 45 ppm (dry)

Chartreuse Ð 45 to 130 ppm (caution!)

Yellow

Ð moisture above 130 ppm (wet)

Change ®lter driers at the ®rst sign of moisture in the sys- tem. See Carrier Charging Handbook for more information.

IMPORTANT: Unit must be in operation at least 12 hours before moisture indicator can give an accu- rate reading. With unit running, indicating element must be in contact with liquid refrigerant to give a true reading.

Filter Driers Ð The 48/50MP units use replaceable core type ®lter driers, one in each refrigeration circuit. The ®lter driers are located in the condenser sections, accessible from the right side of the unit.

49

Image 49
Contents Contents Installation, Start-Up and Service InstructionsSafety Considerations ContentsGeneral Install Outdoor Hoods InstallationBase Unit 48/50MP Physical DataPhysical Data Compressor Oil Charge Optional Power Exhaust SpecicationsVariable Frequency Drive VFD Physical Data FAN MotorRoof Curb Dimensions, 48/50MP62L and 70M Roof Curb Dimensions, 48/50MP82N-10R Base Unit Dimensions, 48MP62L, 70M Base Unit Dimensions, 48MP82N-10R Base Unit Dimensions, 50MP62L and 70M Base Unit Dimensions, 50MP82N-10R Size Unit WeightUnit Make Electrical Connections Field Electrical ConnectionsGND EquipNEC FLA Electrical DataLRA MCAManufacturer Recommended Sensor Device Non-Shielded CableSpace Temperature Sensor Wiring Space Temperature Sensor Averaging Heat Interlock Relay Outdoor Air¯ow Control Transducer/Thermistor CCN Connection Approved Shielded Cables COM CCNComm Auxiliary Control Box Location 50MP70M Unit Shown Gas Piping Details Installing Flue/Inlet Hoods 48MP Units OnlyFlue De¯ector Baffle Assembled Check Compressor MountingSystem Check PRE-START-UPExample Evaporator-Fan Belts, Pulleys, and Sheaves ÐFan Performance Forward Curved Ð 48/50MP70M Fan Performance Forward Curved Ð 48/50MP62LFan Performance Forward Curved Ð 48/50MP90P Fan Performance Forward Curved Ð 48/50MP82NFan Performance Air Foil Ð 48/50MP62L Fan Performance Forward Curved Ð 48/50MP10RFan Performance Air Foil Ð 48/50MP82N Fan Performance Air Foil Ð 48/50MP70MFan Performance Air Foil Ð 48/50MP10R Fan Performance Air Foil Ð 48/50MP90PControls Conguration and Quick Test Hsio Keypad Key Usage Keypad and Display Module Hsio ConfigurationSet Point Ranges and Defaults START-UP SET Point Subfunction Display Default RangeInitial Check Basic Conguration DataSupply FAN GeneralOccupied Cooling Overrides IGC Control Board LED Alarms48/50MP Units SMG, SCV and MLG Recommended Starting Values Control Loop CheckoutComponents Control SystemIndex of Lead/Lag Circuits Compressors Lead CircuitStby YES Keypad and Display Module HsioSUB Functions Hsio Keypad and Display Module Functions and SubfunctionsFunction Variable Frequency Drive VFD Display ServiceEVAPORATOR-FAN MOTORS, PULLEYS, and Belts Power Exhaust MOTORS, PULLEYS, and BeltsRefrigerant Circuit LubricationManufacturer Lubricant Charging Chart Ð Unit 48/50MP62L Charging Chart Unit 48/50MP90P Pressure Switch Settings Psig kPag AdjustmentsBelt Installation and Tensioning Switch Cutout CUT-IN06E Compressors, Typical Protective Devices Gas Valve AdjustmentMain Burner Removal Compressor ProtectionVariable Frequency Drive VFD High-Voltage Relay Modules DSIO1 and DSIO2 Processor Modules PsioStby no Troubleshooting Compressor Replacement Ð Perform the followingTorque Compressors Problem Solution Compressor does not RUN Troubleshooting and DiagnosticsCompressor Stops on HIGH-PRESSURE Switch Compressor Cycles on LOW-PRESSURE SwitchTroubleshooting and Diagnostics IGC Control Heating Ð 48MP Units Only Page Call for Free Catalog Packaged Service TrainingModel no Serial no Date Technician START-UP ChecklistIV. START-UP III. Preliminary Checklist ItemsCL-3 Fact Config Fanm

MPE62L-10R, 50MP62L-10R, 48MPD specifications

The Carrier 48MPD, 50MP62L-10R, and MPE62L-10R are advanced rooftop packaged units designed for a variety of commercial HVAC applications. These systems offer a compelling blend of energy efficiency, versatility, and high performance, making them ideal choices for businesses looking to enhance their indoor climate control.

One of the standout features of the Carrier 48MPD series is its high efficiency rating, which significantly reduces operational costs while minimizing environmental impact. The unit utilizes advanced scroll compressors that provide reliable and efficient cooling capabilities, ensuring optimal temperature regulation regardless of outdoor conditions. This innovative design also contributes to quieter operation, enhancing indoor comfort without disruptive noise levels.

The Carrier 50MP62L-10R model boasts superior cooling and heating capabilities, equipped with a multi-speed fan system that allows for tailored airflow to suit specific project requirements. This model's economizer feature is pivotal for harnessing outside air to offset mechanical cooling, leading to further energy savings, particularly in moderate weather conditions. Additionally, the unit's dual-fuel capability enhances its operational flexibility, allowing it to switch between electric and gas heating sources depending on efficiency needs.

In terms of control technologies, the MPE62L-10R is equipped with Carrier's advanced Smart Evaporator Control, which ensures precise humidity management while optimizing energy consumption. This model also integrates seamlessly with building automation systems, enabling remote monitoring and adjustments for greater operational oversight and efficiency. The intuitive user interface simplifies system programming and operation, making it accessible even for those without extensive technical backgrounds.

Another important characteristic of these units is their robust construction, designed to withstand challenging weather conditions and ensure longevity. The use of high-quality materials and components means lower maintenance costs over time.

Overall, the Carrier 48MPD, 50MP62L-10R, and MPE62L-10R represent a well-engineered suite of HVAC solutions that excel in efficiency, adaptability, and user-friendliness, establishing themselves as leading choices for commercial indoor climate management. With their blend of innovative technology and solid performance, these systems are well-suited to meet the diverse needs of modern commercial spaces.