Carrier 48MPD Control Loop Checkout, 48/50MP Units SMG, SCV and MLG Recommended Starting Values

Page 41

Control Loop Checkout

The checkout and adjustment of control loops should only be done by certi®ed Carrier Comfort Network (CCN) technicians. The following checkout procedure is offered as a guide and presumes the user has obtained basic knowledge of controls through CCN training.

TO CHECK OPERATION OF ANALOG OUTPUTS Ð The control algorithms of the unit controls utilize the master/ submaster loop concept. The master loop monitors the master sensor (the sensor which tries to maintain the desired set point), and calculates the submaster reference required to do so. The submaster loop monitors the submaster sensor and controls the actual output to the controlled device.

These algorithms require the adjustment of a number of gain values to function properly. The 48/50MP units come with preset default values. However, it may be necessary to adjust several of these values to achieve stable control. These values are submaster loop gain (SMG), submaster loop cen- ter value (SCV), and master loop gain (MLG). In addition, proportional, integral, and derivative multiplier values can be accessed through the Building Supervisor, Service Tool, or ComfortWorks™ software.

To verify or adjust submaster default values, perform the following for each controlled device (control loop):

1.Verify that the system is in the Occupied mode and the supply-air fan is running.

2.Verify that the supply-air fan status indicates ON. If the fan status is OFF, the unit control algorithms will dis- able all routines.

3.Verify that all forced values have been removed.

4.Table 27 indicates recommended starting values for MLG and SMG for 48/50MP units. Verify that these values have been entered by checking the service function.

5.Verify/adjust the SMG. If the SMG is too large, the loop will tend to oscillate (hunt). If it is too small, the loop will react too slowly.

Verify or adjust the SMG as follows:

Using the HSIO keypad, force the submaster reference of the control loop to a value above or below the actual sensor reading. Verify that the actuator responds cor- rectly. If the actuator drives in the wrong direction, go to the submaster gain (SMG) for the control loop and reverse the sign of the gain.

For example: If the submaster loop gain is 5.0, change it to -5.0.

6.Observe the operation of the controlled device for a few minutes. If the device oscillates every few seconds around the forced value, then lower the SMG by small amounts until the output steadies. If the output to the device re- sponds to a change in the temperature in small incre- ments, then increase the SMG in small amounts until the output steadies.

NOTE: Do not be alarmed if the submaster sensor sta- bilizes at a value greater or less than the forced value. This is called the submaster droop offset and is normal.

7.It is not necessary to adjust the submaster loop center value, as the master loop will adjust the submaster ref- erence as required to satisfy its set point. However, it may be desirable to keep the submaster droop to a mini- mum. This is most often required for economizer loops.

If the submaster droop is too large, adjust the SCV as follows:

If the submaster droop is positive (actual value greater than reference value), the SCV should be decreased for HCV (heating coil) and IGV (supply fan VFD) loops and increased for CC (cooling control) and ECON (econo- mizer) loops.

If the submaster droop is negative (actual value less than reference value), the SCV should be increased for HCV and IGV loops and decreased for CC and ECON loops.

Table 27 Ð 48/50MP Units SMG, SCV and MLG Recommended Starting Values

 

 

 

 

SERVICE

 

GAIN VALUE

 

 

FUNCTION/GAIN OR SCV

 

SUBFUNCTION

 

 

 

 

 

 

 

(HSIO)

CV Application

 

VAV Application

 

 

Cooling Control

 

 

 

 

 

 

 

MLG

 

8

1.0

 

1.0

 

 

Economizer

 

 

 

 

 

 

 

MLG

 

10

1.0

 

1.0

 

 

SMG

 

10

−7.5

 

−7.5

 

 

SCV

 

10

50

 

50

 

 

Duct Pressure (VFD)

 

 

 

 

 

 

 

MLG

 

9

N/A

 

1.0

 

 

SMG

 

9

N/A

 

2.0*

 

 

SCV

 

9

N/A

 

35*

 

 

Building Pressure

 

 

 

 

 

 

 

MLG

 

18

1.0

 

1.0

 

 

SMG

 

18

−5.0

 

−5.0

 

 

SCV

 

18

50

 

50

 

 

Staged Heat

 

 

 

 

 

 

 

MLG ²

 

11

1.0

 

1.0

 

 

SMG ²

 

11

5.0

 

5.0

 

 

Heating Coil

 

 

 

 

 

 

 

MLG

 

7

1.0

 

1.0

 

 

SMG

 

7

7.5

 

7.5

 

 

SCV

 

7

50

 

50

 

 

Humidi®er

 

 

 

 

 

 

 

MLG

 

17

1.0

 

1.0

 

 

SMG

 

17

7.5

 

7.5

 

 

SCV

 

17

50

 

50

*Factory setting; differs from new control setting.

 

 

 

 

²48MP only.

 

 

 

 

 

 

LEGEND

 

 

 

 

CV

Ð Constant Volume

 

 

 

 

MLG

Ð Master Loop Gain

 

 

 

 

SCV

Ð Submaster Center Value

 

 

 

 

SMG Ð Submaster Loop Gain

 

 

 

 

VAV

Ð Variable Air Volume

 

 

 

 

41

Image 41
Contents Contents Installation, Start-Up and Service InstructionsGeneral ContentsSafety Considerations Install Outdoor Hoods InstallationBase Unit 48/50MP Physical DataPhysical Data Compressor Oil Charge Optional Power Exhaust SpecicationsVariable Frequency Drive VFD Physical Data FAN MotorRoof Curb Dimensions, 48/50MP62L and 70M Roof Curb Dimensions, 48/50MP82N-10R Base Unit Dimensions, 48MP62L, 70M Base Unit Dimensions, 48MP82N-10R Base Unit Dimensions, 50MP62L and 70M Base Unit Dimensions, 50MP82N-10R Unit Unit WeightSize Make Electrical Connections Field Electrical ConnectionsNEC EquipGND FLA Electrical DataLRA MCAManufacturer Recommended Sensor Device Non-Shielded CableSpace Temperature Sensor Wiring Space Temperature Sensor Averaging Heat Interlock Relay Outdoor Air¯ow Control Transducer/Thermistor CCN Connection Approved Shielded Cables Comm CCNCOM Auxiliary Control Box Location 50MP70M Unit Shown Gas Piping Details Installing Flue/Inlet Hoods 48MP Units OnlyFlue De¯ector Baffle Assembled Check Compressor MountingSystem Check PRE-START-UPExample Evaporator-Fan Belts, Pulleys, and Sheaves ÐFan Performance Forward Curved Ð 48/50MP70M Fan Performance Forward Curved Ð 48/50MP62LFan Performance Forward Curved Ð 48/50MP90P Fan Performance Forward Curved Ð 48/50MP82NFan Performance Air Foil Ð 48/50MP62L Fan Performance Forward Curved Ð 48/50MP10RFan Performance Air Foil Ð 48/50MP82N Fan Performance Air Foil Ð 48/50MP70MFan Performance Air Foil Ð 48/50MP10R Fan Performance Air Foil Ð 48/50MP90PControls Conguration and Quick Test Hsio Keypad Key Usage Keypad and Display Module Hsio ConfigurationSet Point Ranges and Defaults START-UP SET Point Subfunction Display Default RangeInitial Check Basic Conguration DataOccupied Cooling GeneralSupply FAN Overrides IGC Control Board LED Alarms48/50MP Units SMG, SCV and MLG Recommended Starting Values Control Loop CheckoutComponents Control SystemIndex of Lead/Lag Circuits Compressors Lead CircuitStby YES Keypad and Display Module HsioFunction Hsio Keypad and Display Module Functions and SubfunctionsSUB Functions Variable Frequency Drive VFD Display ServiceEVAPORATOR-FAN MOTORS, PULLEYS, and Belts Power Exhaust MOTORS, PULLEYS, and BeltsManufacturer Lubricant LubricationRefrigerant Circuit Charging Chart Ð Unit 48/50MP62L Charging Chart Unit 48/50MP90P Pressure Switch Settings Psig kPag AdjustmentsBelt Installation and Tensioning Switch Cutout CUT-IN06E Compressors, Typical Protective Devices Gas Valve AdjustmentMain Burner Removal Compressor ProtectionVariable Frequency Drive VFD Stby no Processor Modules PsioHigh-Voltage Relay Modules DSIO1 and DSIO2 Torque Compressors Compressor Replacement Ð Perform the followingTroubleshooting Problem Solution Compressor does not RUN Troubleshooting and DiagnosticsCompressor Stops on HIGH-PRESSURE Switch Compressor Cycles on LOW-PRESSURE SwitchTroubleshooting and Diagnostics IGC Control Heating Ð 48MP Units Only Page Call for Free Catalog Packaged Service TrainingModel no Serial no Date Technician START-UP ChecklistIV. START-UP III. Preliminary Checklist ItemsCL-3 Fact Config Fanm

MPE62L-10R, 50MP62L-10R, 48MPD specifications

The Carrier 48MPD, 50MP62L-10R, and MPE62L-10R are advanced rooftop packaged units designed for a variety of commercial HVAC applications. These systems offer a compelling blend of energy efficiency, versatility, and high performance, making them ideal choices for businesses looking to enhance their indoor climate control.

One of the standout features of the Carrier 48MPD series is its high efficiency rating, which significantly reduces operational costs while minimizing environmental impact. The unit utilizes advanced scroll compressors that provide reliable and efficient cooling capabilities, ensuring optimal temperature regulation regardless of outdoor conditions. This innovative design also contributes to quieter operation, enhancing indoor comfort without disruptive noise levels.

The Carrier 50MP62L-10R model boasts superior cooling and heating capabilities, equipped with a multi-speed fan system that allows for tailored airflow to suit specific project requirements. This model's economizer feature is pivotal for harnessing outside air to offset mechanical cooling, leading to further energy savings, particularly in moderate weather conditions. Additionally, the unit's dual-fuel capability enhances its operational flexibility, allowing it to switch between electric and gas heating sources depending on efficiency needs.

In terms of control technologies, the MPE62L-10R is equipped with Carrier's advanced Smart Evaporator Control, which ensures precise humidity management while optimizing energy consumption. This model also integrates seamlessly with building automation systems, enabling remote monitoring and adjustments for greater operational oversight and efficiency. The intuitive user interface simplifies system programming and operation, making it accessible even for those without extensive technical backgrounds.

Another important characteristic of these units is their robust construction, designed to withstand challenging weather conditions and ensure longevity. The use of high-quality materials and components means lower maintenance costs over time.

Overall, the Carrier 48MPD, 50MP62L-10R, and MPE62L-10R represent a well-engineered suite of HVAC solutions that excel in efficiency, adaptability, and user-friendliness, establishing themselves as leading choices for commercial indoor climate management. With their blend of innovative technology and solid performance, these systems are well-suited to meet the diverse needs of modern commercial spaces.