SECTION 11: VENTING AND FRESH AIR SUPPLY

SECTION 11: VENTING AND FRESH AIR SUPPLY

WARNING

Carbon Monoxide Hazard

Multiburner systems are not approved for unvented use and must be vented outdoors.

Unitary heaters installed unvented must be interlocked with sufficient building exhaust.

Heaters must be installed according to the installation manual.

Failure to follow these instructions can result in death or injury.

WARNING

Cut/Pinch Hazard

Wear protective gear during installation, operation and service.

Edges are sharp.

Failure to follow these instructions can result in injury.

flue must be self supporting. Suitable terminals must be fitted for horizontal and vertical flue.

In order to locate fans that are not IP54 protected away from the wet environment, a 100 mm diameter extension tube between the heat exchanger end and fan must be installed. This length must be subtracted from the maximum flue length.

Fans

Horizontal

Vertical

83 BWLG

190 mm x 75 mm (hole)

150 mm dia.

90 BWLG

190 mm x 75 mm (hole)

150 mm dia.

11.4 Ventilation Requirements

Detailed recommendations for air supply are given in the relevant National Standards. There must be an adequate supply of air for both combustion and general ventilation. Air vents should have negligible resistance. Do not locate air vents where they can be easily blocked or flooded, or adjacent to any flues or extraction systems carrying flammable vapour.

11.5 Fresh Air Supply

The burner is equipped with a fresh air adapter which has a silicone gasket incorporated. This adapter accepts tubes with 100 mm outside diameter.

100 mm OD

 

Fresh Air

Fresh Air Adapter

Supply Duct

 

11.1 Type C12 , C32 & C62 Appliance

Room Sealed

The heaters are designed to be installed as room sealed appliances. The flue and air intake are run as separate pipes to the special concentric wall or roof terminal. The wire mesh inside the fresh air adapter on the heater must be removed prior to installation. See Page 51, Figure 31.

11.2 Type B22 Appliance

The flue must be fitted with a low resistance terminal. See Page 51, Figure 31.

11.3 Flue Installation

The fan outlet may discharge vertically or horizontally. Connection should be made using 100 mm minimum diameter Aluminium or Stainless Steel flue material to National Standard and must be adapted to insert into the 100 mm flue adapter. Both fresh air supply and flue duct shall not exceed 10,000 mm. HE15 and HE20 flue must be insulated if longer than 5,000 mm. HE25 flue must be insulated if longer than 8,000 mm. For each 90° bend, subtract 1,000 mm from the maximum flue length. The

49 of 73

Image 55
Contents Owner If you smell gasPage Roberts-Gordon Europe Limited Table of ContentsPage Table of Figures Bottom and Back Panel Label PlacementPage Product Approval Heater Safety Control Side Label Placement Low Level User Instructions Installer ResponsibilityNational Standards and Applicable Codes Clearances to Combustibles Model Clearances Data Linear and Double LinearHE40ST HE45ST HE50ST HE45ST HE50ST HE15ST HE30DLHE30UT HE15UTHE20UT HE25UTTUBE, Protective Grille TUBE, Opposite 45 TiltMajor Component Descriptions General Suspension Details Typical Suspension Details Linear Standard Parts List Linear & Double Linear Heater InstallationDescription Linear General Assembly Overview HE35ST HE40ST f HE15ST f HE20ST HE25ST fHE45ST HE50ST f Double Linear Standard Parts List Double Linear General Assembly Overview HE60DL HE70DL f HE30DL fClosed Burner Tube InstallationCoupling and Tube Assembly Open2 Coupling and Tube Assembly 1 Coupling and Tube AssemblyTighten slide bar as shown below Tube Clamp Package Installation Hanger Option a Option BFan Tube Weld Spot Coupling Tee Tube Standard Parts List Tube Heater InstallationLockwasher 6mm Blackheat HE Tube Assembly OverviewHE30UT HE35UT g HE15UT g HE20UT gHE45UT g Burner Tube and Fan Tube Installation U-tube Hanger PlacementU-tube Support Bracket Assembly Installation 1 Tube Clamp Package InstallationTube, Standard Tube, Opposite Orient coupling so that Impact block is U-tube Installation Tube InstallationReflector 02750303 Reflector Support Strap 03050000 Screw #8 x 3/4 Multiburner Configuration & Installation Typical Manifold Layout Linear and U-Tube Configuration Burner Installation Burner & FAN InstallationStandard Fan Assembly Linear & U-tube Fan Installation IP55 Fan Assembly1 Double Linear Fan Installation Double Linear Fan InstallationNon-Return Valve Condensate Drain AssemblyOptional Heater Accessories 2 Side Reflector Installation Reflector Side Extension Installation 1 Bracket InstallationStep Tube Cover InstallationDistance a Extension 2 Frame Shield Installation3 Grille Installation 2 Grille End Cap Installation3 Mesh Guard Connection Sports Hall Guard Installation2 Fastener Installation 1 Grille InstallationUndershield Installation Undershield Installation 10.6.1 Hanger InstallationAdjust Undershield Height Wall Mounting Hardware InstallationVenting and Fresh AIR Supply Air Supply Requirements Outside Combustion Air SupplyCommon Duct Air Supply with Flue ConfigurationsGAS Piping Correct Positions Incorrect Positions Wrong InstallationTypical External Wiring Diagram Linear or U-Tube WiringTypical External Wiring Diagram Multiburner Typical External Wiring Diagram Double Linear OptionInternal Wiring Diagram Tubing may still be hot Heater Lockout Indicator by ConnectorOperation and service OperationSystem Checks Heater Lockout Indicator by Volt Free ConnectorTesting Commissioning MultiburnerServicing Instructions Automatic Flame Control Unit Pressure SwitchMaintenance Checklist ElectrodeGas Line Vent PipeOutside Air Inlet TubesTroubleshooting U-Tube Troubleshooting Flow Chart Linear, Double LinearTroubleshooting Flow Chart Linear, Double Linear and U-Tube Troubleshooting Flow Chart MultiburnerTroubleshooting Flow Chart Multiburner Manometer 4 3 2 1 0 1 2 3 4 5 Manifold Gas Pressure SettingReplacement Parts V2 W3 Description Quantity Viewer Window Replacement Package P/NDoor Gasket Replacement Package P/N Gas Valve Replacement Package P/NSpecifications Double Linear Heater Linear HeaterTube Heater Standard Burner Specifications Burner SpecificationsModels HE15 HE20 HE25 HE30 HE35 HE40 HE45 HE50 Page Page Maintain Clearance Side Clearance below