Step 7

Gas Pressure

Requirements

Pressure requirements for Heat & Glo gas fireplaces are shown in the table below.

 

Natural Gas

Propane

Butane

Natural Gas

 

(G20)

(G31)

(G30)

(G25)

Inlet Pressure

20 mbar

37 or 50 mbar

30 or 50 mbar

25 mbar

Manifold Pressure

4-8.7 mbar

15.7-25 mbar

15.7-25 mbar

4-8.7 mbar

Gas Rate

.54 m3/h

.24 m3/h

.16 m3/h

.54 m3/h

Max. Input(NETCV)

10.0 kW

10.0 kW

9.5 kW

8.5 kW

Burner Injector

DMS 33

1.8 mm

DMS 51

DMS 33

Pilot Injector

51

30

30

51

A tap is provided on the outlet side of the gas control for a test gauge connection to measure the manifold pressure. To measure inlet pressure, provisions must be made to attach a test gauge to the tap immediately upstream of the gas supply connection to the fireplace.

The fireplace and its individual shut-off valve must be disconnected from the gas supply piping system during any pressure testing of the system at test pressures in excess of 60 mbar.

If the fireplace must be isolated from the gas supply piping system by closing an individual shut-off valve, it must be of the handle-less type.

Step 8

Wiring the

Fireplace

Optional Accessories

Optional remote control kits require that 230 VAC be wired to the factory in- stalled junction box before the fireplace is permanently installed.

Wall Switch

NOTE: Electrical wiring must be installed by a competent electrician.

For Standing Pilot Ignition Wiring

Appliance Requirements

WARNING: DO NOT CONNECT 230 VAC

!TO THE GAS CONTROL VALVE OR THE APPLIANCE WILL MALFUNCTION AND THE VALVE WILL BE DESTROYED.

Position the wall switch in the desired position on a wall. Run a maximum of 780 cm or less length of 0.102 cm diameter minimum wire and connect it to the fireplace ON/OFF switch pigtails.

Heat & Glo • 6000TRS-CE2049-900 Rev. Q • 2/11

31

Image 31
Contents What to do if you smell gas ModelSafety and Warning Information Maintaining and Servicing Installing the FireplaceService Parts Log Set Assembly6000TRS-CE Service Parts List6000TRS-CE Valve AssemblyAppliance Certification Installation RegulationsANY Such Action MAY Possibly Cause a Fire Hazard Location Centimeters Clearance Requirements StepLocating FireplaceFraming should be constructed of 2 X 4 lumber or heavier Step Framing FireplaceFlue System Approvals Step Installing Flue SystemIdentifying Flue Components DVP4 DVP6 DVP12 Straight UP Flue with ONE 1 90o Elbow Flue with TWO 2 90 Elbows Flue with TWO 2 90 Elbows Flue with Three 3 90 Elbows + H Venting Out the Rear Flue Installing Flue ComponentsVenting Out the Top Flue On the TOP of the heater Install Support BracketsInstalling Support Brackets Install FirestopsFlue Pipe & Firestop Flue Termination For Horizontal Terminations using the DVP-TRAPBe Positioned SO That the Arrow is Pointing UP DVP Termination Cap Outside of the building Alcove Applications Standing Pilot Ignition System Step Positioning Leveling, Securing FireplaceStep Gas Supply Line Step Gas Pressure Requirements Optional AccessoriesFinishing Installing the Ceramic Re Installing the TrimFractory LOG Placement Heat & Glo 6000TRS-CE 2049-900 Rev. Q 2/11 Placing the Ember Material Glass AssemblyDouble-check for gas leaks Review safety warnings and cautionsDouble-check for faulty components Step Before Lighting FireplaceStep Lighting Fireplace After the Installation Maintaining Servicing Your Fireplace Make Sure the Flames Standing Pilot Troubleshooting With the pilot lit, and the ON/OFF switch Placed in this Opening Limited Lifetime Warranty Limited Lifetime WarrantyWarranty Conditions