Step 7
Gas Pressure
Requirements
Pressure requirements for Heat & Glo gas fireplaces are shown in the table below.
| Natural Gas | Propane | Butane | Natural Gas |
| (G20) | (G31) | (G30) | (G25) |
Inlet Pressure | 20 mbar | 37 or 50 mbar | 30 or 50 mbar | 25 mbar |
Manifold Pressure | ||||
Gas Rate | .54 m3/h | .24 m3/h | .16 m3/h | .54 m3/h |
Max. Input(NETCV) | 10.0 kW | 10.0 kW | 9.5 kW | 8.5 kW |
Burner Injector | DMS 33 | 1.8 mm | DMS 51 | DMS 33 |
Pilot Injector | 51 | 30 | 30 | 51 |
A tap is provided on the outlet side of the gas control for a test gauge connection to measure the manifold pressure. To measure inlet pressure, provisions must be made to attach a test gauge to the tap immediately upstream of the gas supply connection to the fireplace.
The fireplace and its individual
If the fireplace must be isolated from the gas supply piping system by closing an individual
Step 8
Wiring the
Fireplace
Optional Accessories
Optional remote control kits require that 230 VAC be wired to the factory in- stalled junction box before the fireplace is permanently installed.
Wall Switch
NOTE: Electrical wiring must be installed by a competent electrician.
For Standing Pilot Ignition Wiring
Appliance Requirements
WARNING: DO NOT CONNECT 230 VAC
!TO THE GAS CONTROL VALVE OR THE APPLIANCE WILL MALFUNCTION AND THE VALVE WILL BE DESTROYED.
Position the wall switch in the desired position on a wall. Run a maximum of 780 cm or less length of 0.102 cm diameter minimum wire and connect it to the fireplace ON/OFF switch pigtails.
Heat & Glo • | 31 |