CONNECTING FIREPLACE TO GAS SUPPLY

Installation Items Needed

5/16" hex socket wrench or nut-driver

sealant (resistant to propane/LP gas, not provided)

1.Route flexible gas line (provided by in- staller) from equipment shutoff valve to fireplace. Route flexible gas supply line through one of the access holes on side of fireplace.

2.Attach flexible gas line from gas supply to control valve (see Figure 22).

3.Check all gas connections for leaks. See Checking Gas Connections.

 

 

Red Surface

Equipment

Flexible

Indicates For

Gas Line

Propane/LP Use

Shutoff

Do NOT

Only

 

Valve

Kink

 

 

 

 

 

1/2" NPT

Inlet

 

Outlet

Incoming

Pressure

Gas Line

Tap

 

Pressure

 

 

 

Tap

Note: Wire Connections Not Shown for Clarity

Figure 22 - Connecting Flexible Gas Line

to Electronic Valve

CHECKING GAS CONNECTIONS

WARNING: Test all gas piping and connections, internal and external to unit, for leaks after installing or servicing. Correct all leaks at once.

WARNING:Neveruseanopen flame to check for a leak. Apply noncorrosive leak detection fluid toalljoints.Bubblesformingshow a leak. Correct all leaks at once.

Pressure Testing Gas Supply Piping System

Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)

1.Disconnect fireplace and its individual equipment shutoff valve from gas supply piping system. Pressures in excess of

1/2 psig (3.5 kPa) will damage fireplace gas regulator.

2.Cap off open end of gas pipe where equip- ment shutoff valve was connected.

3.Pressurize supply piping system by either opening propane/LP supply tank valve for propane/LP gas fireplace or opening main gas valve located on or near gas meter for natural gas fireplace or using compressed air.

4.Check all joints of gas supply piping sys- tem. Apply noncorrosive leak detection fluid to all joints. Bubbles forming show a leak. Correct all leaks at once.

5.Reconnect fireplace and equipment shutoff valve to gas supply. Check recon- nected fittings for leaks.

Test Pressures Equal To or Less Than 1/2 PSIG (3.5 kPa)

1.Close equipment shutoff valve (see Figure 23).

2.Pressurize supply piping system by either opening propane/LP supply tank valve for propane/LP gas fireplace or opening main gas valve located on or near gas meter for natural gas fireplace or using compressed air.

3.Check all joints from propane/LP supply tank or gas meter to equipment shutoff valve (see Figure 24 or Figure 25, page

17). Apply noncorrosive leak detection fluid to all joints. Bubbles forming show a leak.

4.Correct all leaks at once.

Equipment

Open

Shutoff Valve

 

Closed

Figure 23 - Equipment Shutoff Valve

16

www.desatech.com

120441-01A

Image 16
Contents Propane/LP Gas Models Gas Models NaturalStacked Brick/Standard Glass Table of Contents Safety InformationNatural and Propane/LP Gas Natural This fireplaceProduct Identification Product FeaturesLocal Codes Preinstallation InstallationLocation and space requirements Proper clearances must be maintainedClearances Framing and finishingFor specific venting ClearancesLocation of Termination Cap Balcony with Perpendicular Side WallVenting Installation Installation PrecautionsInstallation Planning Twist-Lock Procedure The femaleSee , Apply Mastic to All Four Sides Vent Cap Wood ScrewTo All Four Sides Horizontal High Wind Square Termination Elbow Wall FirestopMax max max Vertical Termination Installation Flat Ceiling InstallationOutside Air Flex Installation High Altitude InstallationVertical Venting = 40 maxFireplace Installation Parts list for venting kits and componentsInstalling Gas Piping to Fireplace Location Check GAS TypeGas Connection Connecting Fireplace to GAS Supply Checking GAS ConnectionsPsig 3.5 kPa will damage fireplace gas regulator Test Pressures Equal To or Less Than 1/2 Psig 3.5 kPaPressure Testing Fireplace Gas Connections Installing Middle Door DVF-36SC/HC Models OnlyInstalling Outer Door DVF-36SC/HC Models Only FireplaceSee , Follow these instructions in reverse to reinstall Spring Loaded Pin Pin Located on Middle DoorHook LocatedOuter Door Hinge On Inner Door Middle Door Remove screen and rod see ,Lava Rock, Ember Flakes Scrap Log Installation Side Bricks Side Trim Screen Rod LeftBottom Brick Middle Bottom Brick Right Bottom BrickWall Switch Installation Remote control Installation Model WRCWiring Diagram For your safety Read before lightingOperation Lighting InstructionsPilot Assembly Inspecting BurnersTo Turn OFF GAS To Appliance Remote OperationCleaning Maintenance Glass DoorsTechnical Service SpecificationsReplacement Parts Service HintsTroubleshooting Observed Problem Possible Cause Remedy21 and/or check ground wire to ignition module Pilot will not stay litTo ignition module and/or Poor ground to ignitionTions, ConfigurationGlass soots Debris around burner air Illustrated Parts Breakdown Parts List Not a field replaceable partIllustrated parts breakdown Bottom Pan Weldment Illustrated parts breakdown 120168-01 Refractory Trim, RH 120168-02 Refractory Trim, LH 120441-01A 120441-01A Warranty Information Keep this WarrantyLimited Warranty Direct vent Fireplace