Vermont Casting BHDR36 installation instructions General Venting Information

Page 8

GENERAL VENTING INFORMATION

Your fireplace is approved to be vented either through the side wall, or vertical through the roof.

-Only Majestic venting components specifically approved and labelled for this fireplace may be used.

-Minimum clearances between vent pipes and combustible materials is one (1") inch (25 mm), except where stated otherwise.

-Venting terminals shall not be recessed into a wall or siding.

-Horizontal venting must be installed on a level plane without an inclining or declining slope.

There must not be any obstruction such as bushes, garden sheds, fences, decks or utility buildings within 24" from the front of the termination hood.

Do not locate termination hood where excessive snow or ice build up may occur. Be sure to check vent termination area after snow falls, and clear to prevent accidental blockage of venting system. When using snow blowers, make sure snow is not directed towards vent termination area.

Location of Vent Termination

It is imperative that the vent termination be located observ- ing the minimum clearances as shown on this page.

*Check with local codes or in absence of local codes, with National Fuel Gas Code, ANSI Z223.1 - latest edition for USA, or CAN 1 B1-149.1 and .1 Installation Code for Canada.

D

E

 

V

 

C

L

B

 

 

 

 

 

Fixed

 

 

 

 

 

 

Closed

 

F

V

Openable

 

 

V

Openable

B V

Fixed

Closed

H

N

 

I

N

G

V

B

 

 

B

M

B

V J X

G

A

G

V KX V A

V TERMINATION CAP

X AIR SUPPLY INLET

G

GAS METER

RESTRICTED AREA

 

 

 

 

(TERMINATION PROHIBITED)

A = clearance above grade, veranda, porch, deck, or balcony [* 12 inches (305mm) minimum]

B = clearance to window or door that may be opened 12" (306mm).

C = clearance to permanently closed window [minimum 12 inches (305mm) recommended to prevent con- densation on window]

D = vertical clearance to ventilated soffit located above the termina/ within a horizontal distance of 24 inches (610mm) from the centre-line of the terminal [18 inches (458mm) minimum]

E = clearance to unventilated soffit [12 inches (305mm) minimum

F = clearance to outside comer see next page G = clearance to inside comer see next page

H = * not to be installed above a meter/regulator assem- bly within 36 inches (914mm) horizontally from the centre-line of the regulator

I = clearance to service regulator vent outlet [*72 inches (1828mm) minimum]

J = clearance to non-mechanical air supply inlet to building or the combustion air inlet to any other fireplace [ *12 inches (305mm) minimum]

K = clearance to a mechanical air supply inlet [* 72 inches (1828mm) minimum]

L = † clearance above paved side-walk or a paved driveway located on public property [*84 inches (2133mm) minimum]

M = clearance under veranda, porch, deck [*12 inches (305mm) minimum ‡]

N = Clearance above a roof shall extend a minimum of 24" (610mm) above the highest point when it passes through the roof surface, and any other obstruciton within a horizontal distance of 18" (450mm).

a vent shall not terminate directly above a side-walk or paved driveway which is located between two single family dwellings and serves both dwellings *

only permitted if veranda, porch, deck, is fully open on a minimum 2 sides beneath the floor *

*check with local codes, or in the absence of local codes, with National Fuel Gas Code, ANSI Z223.1 - latest edition

for USA, or CAN 1B1-149.1 and .2 Installation Code for Canada. Note: Local codes or regulations may require different clearances.

- 8 -

Image 8 Contents
BHDR36 Table of Contents Installation Instructions Locating Your GAS FireplaceFireplace Dimensions Mantel Chart MantelsClearance to Combustibles Framing and FinishingHearth GAS SpecificationsFinal Finishing GAS Line Installation Remote Switch Installation For RN/RPGeneral Venting Information Termination Clearances Rear Wall Installations Rear Venting ApplicationsVertical Sidewall Installations Vertical Sidewall Applications Sidewall Venting Graph HOW to USE the Vent GraphVent Sidewall Installation Ensure Pipes Are Below Grade Installations Vertical Through Roof ApplicationsVertical Thru Roof Installation Proceed to plumb for additional openings throughCrimped END Venting Components General Information on Assembling Twist Lock Vent Pipes Rear Venting Applications190mm Vertical Sidewall Installations Vertical Sidewall ApplicationsSee page 23 for Venting Requirements for Snorkels NON-COMBUSTIBLE Walls Hole opening must be Below Grade Installations InstallationVertical Through Roof Applications RiseVertical Through the Roof Installation Twist Lock Venting Components Glass Cleaning General Glass InformationLouvre Removal Glass Frame RemovalLava Rock Installation of LogsFlame Adjustment Flame Characteristics MaintenanceCleaning the Standing Pilot Control System Inspecting the Venting SystemLighting and Operating Instructions Trouble Shooting the GAS Control System SIT 820 Nova Millivolt Valve Replacement Parts List Replacement Parts Optional FAN KIT FK24 Wiring InstructionsOptional BAY Window Installation Optional Remote Control Optional Screen KIT InstallationOptional Ceramic Refractory Installation