DVS 30-2 installation instructions Venting Fireplace, Installation, Example a, Example B

Page 10

VENTING FIREPLACE

To Use the Vent Graph (Figure 10)

1.Determine the height of the center of the horizontal vent pipe. Using this dimension on the Sidewall Vent Graph, locate the point it intersects with the slanted graph line.

2.From the point of this intersection, draw a vertical line to the bottom of the graph.

3.Select the indicated dimension, and position the unit in accordance with same.

EXAMPLE A:

If the vertical dimension from the floor of the unit is 22.5 feet, the horizontal run to the outer wall flange must not exceed 6.5 feet.

EXAMPLE B:

If the vertical dimension from the floor of the unit is 6.5 feet, the horizontal run to the outer wall flange must not exceed 14.5 feet.

SPECIAL NOTE: For each 45 degree elbow installed in the horizontal run, the length of the horizontal run MUST be reduced by 18" (45cm). This does not apply if the 45 degree elbows are installed on the vertical part of the vent system.

Example: According to the chart the maximum horizontal vent length is 20' and if two 45 degree elbows are required in the horizontal vent it must be reduced to 17'.

The maximum number of 45 degree elbows permitted per side wall installation is two (2). These elbows can be installed in either the vertical or horizontal run.

Venting Graph (Dimensions in Feet)

 

 

 

 

 

 

SIDEWALL VENTING GRAPH

 

 

 

 

 

 

 

 

 

 

 

 

(DIMENSIONS IN FEET)

 

 

 

 

 

 

 

 

25

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UNIT

 

24

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

23

 

 

 

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

THE

 

22

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

21

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VERTICALDIMENSIONFROMTHEBOTTOMOF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TOTHECENTEROFTHEHORIZONTALPIPE

20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

19

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

18

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

17

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

14

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

11

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

 

 

 

 

 

 

 

 

 

 

 

B

 

 

 

 

 

 

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

HORIZONTAL RUN

Figure 10

Acceptable vertical and horizontal vent run.

Unacceptable vertical and horizontal vent run.

INSTALLATION

Framing and Finishing

1. Choose unit location.

2. Frame in fireplace with a header across the top. It is important to allow for finished face when setting the depth of the frame.

3. Attach fireplace to frame using adjustable frame. Preset depth to suit facing material (adjustable to 1/2", 5/8" or 3/4" depths).

4. Use (8) 1/2" hex-head screws supplied in hardware package, to screw through slotted holes in drywall strip and then screw into pre-drilled holes on fireplace side. Measure from face of fireplace to face of drywall strip to determine final depth.

DVS-36/42 Shown

Figure 11

Page 10

13369-1-0203

Image 10
Contents Installation Instructions Table of Contents Important Safety Information Safety Information for Users of LP-GAS LP-GAS Warning OdorIntroduction Specifications Fireplace Dimensions Model DVS-30/DVS-36/DVS-42Fireplace Component Installation Heater Baffle is Used on DVS-36 & DVS-42 onlyLocating Fireplace Mantel Chart FigureClearances Clearances FigureGAS Supply Installing a New Main Gas CockChecking Manifold Pressures Example a InstallationVenting Fireplace Example BFinishing Figure Three 3 basic types of installationsFraming Figure Vent Runs Figures 14, 15, 16, 17Installation Vertical Sidewall Application Positioning the Fireplace MAX Cutting the Hole Figures 22Termination Clearances Vertical Sidewall InstallationsInformation on Various Venting Routes and Components Vent Clearances Vent System Identification Installing Vent Components FigureInner flue joints do not require any sealant Installing Firestops Figures 30, 31, 32 Installing Support Brackets FigureDVS-30 Framing and Finishing DVS-30 Framing and Finishing Installing Firestops Figures 35, 36, 37 DVS-36 & DVS-42 Framing and FinishingDVS-36 & DVS-42 Framing and Finishing Installing the Vent System in a Chase Vertical Termination For All ModelsVertical Through the Roof Applications Figure LOG PlacementReassembly and Resealing Vent Pipe System Glass RemovalDVS-36 and DVS-42 Placement of glowing embers Glass ReplacementDVS-30 Placement of glowing embers TOP View of LOG SETFlame Appearance Standing Pilot Operating InstructionsMillivolt System Figures 48 Recommended Wire Gauges Standing Pilot Wiring Diagram Standing Pilot Lighting Instructions What to do if YOU Smell GASPilot and main burner extinguish while in operation Standing Pilot TroubleshootingFrequent pilot outage problem Glass sootsDVS-36 & DVS-42 Intermittent Pilot Wiring Diagram Electrical Connection FigureTo Turn OFF GAS to Appliance Trial for Ignition SpecificationsOperation CheckoutSafety Lockout Main Burner OperationIgnition System Checks ARC Length ActionDVS-36 & DVS-42 Intermittent Pilot Troubleshooting RF Standing Pilot Operating Instructions RF Wiring Diagram RF Standing Pilot Lighting Instructions Maintenance and Service Please NoteHOW to Order Repair Parts DVS-30 Parts ListDVS-36 Parts List #41 Orifice NATDVS-42 Parts List Parts View Accessory Parts LouversVariable Speed Blower Installation Instructions Blower Motor Optional Single Speed Blower Installation Instructions FBB1A Blower InstallationParts List Optional Fresh AIR Intake KIT DVFB-AK-30, FB-AK-2 Optional Fresh Air Intake Kit FigureExample of Installation Brick Liner KIT Installing Optional Brick LinerParts List DVS-BL-30-2, DVS- BL-36-2, DVS-BL-42-2