DVS 30-2 DVS-36 & DVS-42 Intermittent Pilot Wiring Diagram, Electrical Connection Figure

Page 31

DVS-36 & DVS-42 INTERMITTENT PILOT OPERATING INSTRUCTIONS

The intermittent pilot (120/24 volt system) is ON when the main burner is ON. When the main burner is OFF the intermittent pilot is OFF.

The pilot flame should envelop 3/8 to 1/2 inch (10 to 13mm) of the tip of the flame rod.

To adjust:

1.Remove the pilot adjustment cover screw.

2.Turn the inner adjustment screw clockwise to

decrease or counterclockwise to increase pilot flame. Pilot adjustment is shipped at full flow rate. Turn the

inner adjustment screw clockwise if the inlet pres- sure is too high.

3.Replace the cover screw after the adjustment to prevent gas leakage.

Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.

Provided on the intermittent pilot wiring harness are two (2) stripped and bare wires that are labeled THERMOSTAT. The wires will be used for attachment of 24 volt thermostat, optional FWS-1 wall switch or will attach into the receiver on an optional FRBC-1, FRBTC-1 or FREC-1 remote control.

Installation of Remote Receiver

Place remote receiver on the floor of fireplace behind the louver as far forward as possible.

Attention: The velcro loop and hook are not necessary in this installation but can be used to secure remote receiver.

DVS-36 & DVS-42 INTERMITTENT PILOT WIRING DIAGRAM

Figure 52

ELECTRICAL CONNECTION (Figure 53)

The DVS36/42IP with optional fan requires 120 VAC electrical hookup to the electrical box (installed).

The appliance, when installed, must be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code, ANSI/NFPA 70, if an external electrical source is utilized.

CAUTION: ALL WIRING SHOULD BE DONE BY A QUALI- FIED ELECTRICIAN AND SHALL BE IN COMPLIANCE WITH ALL LOCAL, CITY AND STATE BUILDING CODES. BEFORE MAKING THE ELECTRICAL CONNECTION, MAKE SURE THAT MAIN POWER SUPPLY IS DISCON- NECTED. THE APPLIANCE, WHEN INSTALLED, MUST BE ELECTRICALLY GROUNDED IN ACCORDANCE WITH LOCAL CODES OR, IN THE ABSENCE OF LOCAL CODES, WITH THE NATIONAL ELECTRICAL CODE ANSI/NFPA 70 (LATEST EDITION).

A factory installed electrical box is located on the lower right hand side of the fireplace. Wiring must be fed to the electrical box and attached to the receptacle that is provided. Remove the knockout in the installed junction box to accept wiring into the junction box. Install a UL listed cable clamp (not supplied) in the knockout hole. Leave approximately 6" of wire in the junction box for connection.

Attach black wire to one side of the receptacle and white wire to opposite side of receptacle.The ground wire should be attached to the green (neutral) screw.

Install the receptacle into the metal box with. Attach cover plate.

Plug cord set from transformer into receptacle.

JUNCTION BOX

 

 

 

NEUTRAL

 

 

 

 

 

 

 

BLACK

WHITE

GROUND

 

 

 

 

 

Figure 53

13369-1-0203

Page 31

Image 31
Contents Installation Instructions Table of Contents Important Safety Information LP-GAS Warning Odor Safety Information for Users of LP-GASIntroduction Fireplace Dimensions Model DVS-30/DVS-36/DVS-42 SpecificationsHeater Baffle is Used on DVS-36 & DVS-42 only Fireplace Component InstallationClearances Figure Mantel Chart FigureClearances Locating FireplaceGAS Supply Installing a New Main Gas CockChecking Manifold Pressures Example B InstallationVenting Fireplace Example aVent Runs Figures 14, 15, 16, 17 Three 3 basic types of installationsFraming Figure Finishing FigureInstallation Vertical Sidewall Application Positioning the Fireplace Cutting the Hole Figures 22 MAXTermination Clearances Vertical Sidewall InstallationsInformation on Various Venting Routes and Components Vent Clearances Vent System Identification Installing Vent Components FigureInner flue joints do not require any sealant Installing Firestops Figures 30, 31, 32 Installing Support Brackets FigureDVS-30 Framing and Finishing DVS-30 Framing and Finishing DVS-36 & DVS-42 Framing and Finishing Installing Firestops Figures 35, 36, 37DVS-36 & DVS-42 Framing and Finishing Vertical Termination For All Models Installing the Vent System in a ChaseGlass Removal LOG PlacementReassembly and Resealing Vent Pipe System Vertical Through the Roof Applications FigureTOP View of LOG SET Glass ReplacementDVS-30 Placement of glowing embers DVS-36 and DVS-42 Placement of glowing embersFlame Appearance Standing Pilot Operating InstructionsMillivolt System Figures 48 Recommended Wire Gauges Standing Pilot Wiring Diagram What to do if YOU Smell GAS Standing Pilot Lighting InstructionsGlass soots Standing Pilot TroubleshootingFrequent pilot outage problem Pilot and main burner extinguish while in operationElectrical Connection Figure DVS-36 & DVS-42 Intermittent Pilot Wiring DiagramTo Turn OFF GAS to Appliance Checkout SpecificationsOperation Trial for IgnitionMain Burner Operation Safety LockoutARC Length Action Ignition System ChecksDVS-36 & DVS-42 Intermittent Pilot Troubleshooting RF Standing Pilot Operating Instructions RF Wiring Diagram RF Standing Pilot Lighting Instructions Please Note Maintenance and ServiceDVS-30 Parts List HOW to Order Repair Parts#41 Orifice NAT DVS-36 Parts ListDVS-42 Parts List Parts View Louvers Accessory PartsVariable Speed Blower Installation Instructions Blower Motor FBB1A Blower Installation Optional Single Speed Blower Installation InstructionsParts List Optional Fresh Air Intake Kit Figure Optional Fresh AIR Intake KIT DVFB-AK-30, FB-AK-2Example of Installation DVS-BL-30-2, DVS- BL-36-2, DVS-BL-42-2 Installing Optional Brick LinerParts List Brick Liner KIT