DVS 30-2 DVS-36 & DVS-42 Framing and Finishing, Installing Firestops Figures 35, 36, 37

Page 21

DVS-36 & DVS-42 FRAMING AND FINISHING

Installing Support Brackets (Figure 34)

A horizontal pipe support MUST BE used for each 3 feet of horizontal run. The pipe supports should be placed around 8 inch diameter pipe and nailed in place to framing members. There MUST BE a 3 inch clearance to combustibles above 8 inch diameter pipe and elbows and 1 inch clearance on both sides and bottom of 8 inch pipe to combustibles on all horizontal pipe sections and elbows.

Vertical runs of this vent systems must be supported every 4 feet above the appliance flue outlet by wall brackets attached to the 8 inch vent pipe and secured with nails or screws to structural framing members.

PIPE STRAP

 

STUD WALL

48"

1" MIN.

(1219mm)

(25.4mm)

FLUE OUTLET

Figure 34

10 3/8

12 3/8

Installing Firestops (Figures 35, 36, 37 and 38)

Firestops are required for safety whenever the vent system passes through an interior wall, an exterior wall, or a ceiling. These firestops act as a firebreak heat shield and as a means to insure that minimum clearances are maintained to the vent system.

Cut a 10-3/8 inch x 12-3/8 inch hole in wall. Position firestop (SD- 1249) on interior side of wall for 10-3/8 inch x 12-3/8 inch hole. Attention: Wall firestop hole is off-set towards bottom of wall opening. Secure with nails or screws. Continue the vent run through the firestop. (See Figure 35)

Vertical runs of this system which pass through ceilings require the use of ONE (1) ceiling firestop at the hole in each ceiling through which the vent passes.

Position a plumb bob directly over the center of the vertical vent component and mark the ceiling to establish the center point of the vent. Drill a hole or drive a nail through this center point and check the floor above for any obstructions such as wiring or plumbing runs. Reposition the fireplace and vent system, if necessary, to accommodate ceiling joists and/or obstructions.

EXISTING CEILING JOISTS

NEW FRAMING

 

"

10

1/2

 

267mm

10

1/2"

 

267mm

CEILING BELOW

Figure 36

101/2"

267mm

10

1/2"

 

267mm

NAILS, 4 REQUIRED

WALL FIRESTOP

 

HOLE IS OFF-SET TOWARDS

 

BOTTOM OF WALL OPENING.

CEILING FIRESTOP

 

Figure 35

Figure 37

 

13369-1-0203

Page 21

Image 21
Contents Installation Instructions Table of Contents Important Safety Information LP-GAS Warning Odor Safety Information for Users of LP-GASIntroduction Fireplace Dimensions Model DVS-30/DVS-36/DVS-42 SpecificationsHeater Baffle is Used on DVS-36 & DVS-42 only Fireplace Component InstallationClearances Mantel Chart FigureLocating Fireplace Clearances FigureInstalling a New Main Gas Cock GAS SupplyChecking Manifold Pressures Venting Fireplace InstallationExample a Example BFraming Figure Three 3 basic types of installationsFinishing Figure Vent Runs Figures 14, 15, 16, 17Installation Vertical Sidewall Application Positioning the Fireplace Cutting the Hole Figures 22 MAXVertical Sidewall Installations Termination ClearancesInformation on Various Venting Routes and Components Vent Clearances Installing Vent Components Figure Vent System IdentificationInner flue joints do not require any sealant Installing Support Brackets Figure Installing Firestops Figures 30, 31, 32DVS-30 Framing and Finishing DVS-30 Framing and Finishing DVS-36 & DVS-42 Framing and Finishing Installing Firestops Figures 35, 36, 37DVS-36 & DVS-42 Framing and Finishing Vertical Termination For All Models Installing the Vent System in a ChaseReassembly and Resealing Vent Pipe System LOG PlacementVertical Through the Roof Applications Figure Glass RemovalDVS-30 Placement of glowing embers Glass ReplacementDVS-36 and DVS-42 Placement of glowing embers TOP View of LOG SETStanding Pilot Operating Instructions Flame AppearanceMillivolt System Figures 48 Recommended Wire Gauges Standing Pilot Wiring Diagram What to do if YOU Smell GAS Standing Pilot Lighting InstructionsFrequent pilot outage problem Standing Pilot TroubleshootingPilot and main burner extinguish while in operation Glass sootsElectrical Connection Figure DVS-36 & DVS-42 Intermittent Pilot Wiring DiagramTo Turn OFF GAS to Appliance Operation SpecificationsTrial for Ignition CheckoutMain Burner Operation Safety LockoutARC Length Action Ignition System ChecksDVS-36 & DVS-42 Intermittent Pilot Troubleshooting RF Standing Pilot Operating Instructions RF Wiring Diagram RF Standing Pilot Lighting Instructions Please Note Maintenance and ServiceDVS-30 Parts List HOW to Order Repair Parts#41 Orifice NAT DVS-36 Parts ListDVS-42 Parts List Parts View Louvers Accessory PartsVariable Speed Blower Installation Instructions Blower Motor FBB1A Blower Installation Optional Single Speed Blower Installation InstructionsParts List Optional Fresh Air Intake Kit Figure Optional Fresh AIR Intake KIT DVFB-AK-30, FB-AK-2Example of Installation Parts List Installing Optional Brick LinerBrick Liner KIT DVS-BL-30-2, DVS- BL-36-2, DVS-BL-42-2