DVS-36 & DVS-42 INTERMITTENT PILOT TROUBLESHOOTING

If the pilot does not light, or the pilot flame current is not at least 1.0 uA and steady, the module will not energize the second main valve and the main burner will not light.

Safety Lockout

S8600H provides 100 percent shutoff, or safety lockout. A timer starts timing the moment the trial for ignition starts. Ignition spark continues only until the timed trial for ignition period ends. Then the module goes into safety lockout. Lockout de-energizes the first main valve operator and closes the first main valve in the gas control, stopping pilot gas flow. The control system must be reset by setting the thermostat below room temperature for one minute or by turning off power to the module for one minute.

Main Burner Operation

When the pilot flame is established, a flame rectification circuit is completed between the sensor and burner ground. The flame sensing circuit in the module detects the flame current, shuts off the spark generator and energizes the second main valve operator. The second main valve opens and gas flows to the main burner, where it is ignited by the pilot burner. The flame current also holds the safety lockout timer in the reset (normal) operating condition.

When the call for heat ends, both main valve operators are de- energized, and both main valves in the gas control close.

CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.

S8600H NORMAL OPERATING SEQUENCE

START

STAGE 1

Trial for Ignition

STAGE 2

Main Burner

Operation

END

Thermostat, Wall Switch,

Remote, Etc. Calls For Heat

POWER INTERRUPTION

System shuts off. Restarts when

power is restored.

PILOT FLAME FAILURE Second main operator closes. Module starts trial for ignition.

Spark Generator Powered

First Valve (Pilot)

Operator Opens

PILOT BURNER OPERATION

Pilot burner lights.

Pilot burner does not light

Module senses flame current.

 

 

OR

MODULE

RESPONSE

 

 

 

 

S8600H

After 90 seconds*pilot valve

 

 

closes, spark stops.

 

 

 

 

* Lockout timing is stamped on module.

IF FLAME CURRENT SENSED

Spark generator off.

Second valve operator (Main) opens.

MAIN BURNER OPERATION Module monitors pilot

flame current.

THERMOSTAT SATISIFIED Valves close.

Pilot and main burners are off.

Page 34

13369-1-0203

Image 34
Contents Installation Instructions Table of Contents Important Safety Information Safety Information for Users of LP-GAS LP-GAS Warning OdorIntroduction Specifications Fireplace Dimensions Model DVS-30/DVS-36/DVS-42Fireplace Component Installation Heater Baffle is Used on DVS-36 & DVS-42 onlyLocating Fireplace Mantel Chart FigureClearances Clearances FigureGAS Supply Installing a New Main Gas CockChecking Manifold Pressures Example a InstallationVenting Fireplace Example BFinishing Figure Three 3 basic types of installationsFraming Figure Vent Runs Figures 14, 15, 16, 17Installation Vertical Sidewall Application Positioning the Fireplace MAX Cutting the Hole Figures 22Termination Clearances Vertical Sidewall InstallationsInformation on Various Venting Routes and Components Vent Clearances Vent System Identification Installing Vent Components FigureInner flue joints do not require any sealant Installing Firestops Figures 30, 31, 32 Installing Support Brackets FigureDVS-30 Framing and Finishing DVS-30 Framing and Finishing Installing Firestops Figures 35, 36, 37 DVS-36 & DVS-42 Framing and FinishingDVS-36 & DVS-42 Framing and Finishing Installing the Vent System in a Chase Vertical Termination For All ModelsVertical Through the Roof Applications Figure LOG PlacementReassembly and Resealing Vent Pipe System Glass RemovalDVS-36 and DVS-42 Placement of glowing embers Glass ReplacementDVS-30 Placement of glowing embers TOP View of LOG SETFlame Appearance Standing Pilot Operating InstructionsMillivolt System Figures 48 Recommended Wire Gauges Standing Pilot Wiring Diagram Standing Pilot Lighting Instructions What to do if YOU Smell GASPilot and main burner extinguish while in operation Standing Pilot TroubleshootingFrequent pilot outage problem Glass sootsDVS-36 & DVS-42 Intermittent Pilot Wiring Diagram Electrical Connection FigureTo Turn OFF GAS to Appliance Trial for Ignition SpecificationsOperation CheckoutSafety Lockout Main Burner OperationIgnition System Checks ARC Length ActionDVS-36 & DVS-42 Intermittent Pilot Troubleshooting RF Standing Pilot Operating Instructions RF Wiring Diagram RF Standing Pilot Lighting Instructions Maintenance and Service Please NoteHOW to Order Repair Parts DVS-30 Parts ListDVS-36 Parts List #41 Orifice NATDVS-42 Parts List Parts View Accessory Parts LouversVariable Speed Blower Installation Instructions Blower Motor Optional Single Speed Blower Installation Instructions FBB1A Blower InstallationParts List Optional Fresh AIR Intake KIT DVFB-AK-30, FB-AK-2 Optional Fresh Air Intake Kit FigureExample of Installation Brick Liner KIT Installing Optional Brick LinerParts List DVS-BL-30-2, DVS- BL-36-2, DVS-BL-42-2