INSTALLATION

from the rear of the unit to the wall. It is also important to note the wall thickness. (The wall thimble is suitable for 2 x 4 or 2 x 6 wall construction.) Select the amount of vertical rise desired for "vertical-to-horizontal" type instal- lations.

The minimum clearance of 1-1/4" (32mm) is required between the outer wall of the vent pipe and nearby combustible surfaces. Be sure to check the vent termination clearance require-

ments from decks, windows, soffits, gas reg- ulators, air supply inlets and public walkways as specified in the Exterior Vent Terminal Locations on page 9 and in your local building codes.

To determine the length of vent pipe required for vertical installations, measure the distance from the unit flue outlet to the ceiling, the ceiling thickness, the vertical rise in an attic or second storey, and allow for sufficient vertical height

above the roof line.

For multi-storey applications, fire stops are required at each floor level. If an offset is needed, additional pipe, elbows and supports will be required.

Do not exceed the maximum number of elbows. One 90o for horizontal terminations and two 45o for vertical termination.

RIGID PIPE VENTING COMPONENTS

Parts not supplied by Dura-Vent 946-506/P Vent Guard (Optional)

640-530 Riser Vent Terminal (Optional)

948-128 Vinyl Siding Shield for Riser Vent Terminal

946-228 Horizontal Square Termination Cap

You will require the following components with your new Waterford Direct Vent Free- standing Gas Stove. Please review your prod- uct to make sure you have everything you need. In the event that you are missing any part, contact your dealer.

Note: These are the minimum pieces required. Other parts may be re- quired for your particular installa- tion. See page 15 for a list of vent parts.

If installing termination on a siding covered wall, a vinyl siding standoff or furring strips can be used in order to ensure that the termi- nation is not recessed into siding.

The vinyl siding standoff is required for walls with vinyl siding.

Dura-Vent Basic

Horizontal Kit # 970

1 90o Elbow

1Wall Thimble Cover

1Horiz. Sq. Term. Cap

Minimum components for a Dura-Vent Horizontal Installation:

A)Dura-Vent Horizontal Termination Cap

B)Round Support Box/Wall Thimble

C)Pipe Length (length varies)

D)90o Elbow

E)Pipe Length (Min. 24")

F)Adapter (Part # 946-219)

G)45o Elbow (Part # 945B)

Minimum components for a Dura-Vent Vertical Termination:

H)Dura-Vent Vertical Termination Kit See page 16 for pipe lengths.

Alternate Horizontal

Termination Caps

AstroCap

Part# 946-523/P

Alternate

Horizontal

Riser Vent

Terminal

Part# 640-530/P

When using piping other than Simpson Dura-Vent, 3 screws must be used to secure rigid pipe to adaptor.

WARNING:

Do not combine venting components from different venting systems.

However use of the the AstroCapTM and FPI Riser is acceptable with all systems.

This product has been evaluated by Intertek for using a Dura-Vent Flue Adaptor in conjunction with Selkirk Direct-Temp and Ameri Vent Direct venting systems. Use of these systems with the Direct Vent GS starting collar is deemed acceptable and does not affect the Intertek WHI listing of components.

The FPI AstroCapTM and FPI Riser Vent terminal is certified for installations using FPI venting systems as well as Simpson Dura-Vent®, Direct Vent GS, American Metal Products, Ameri Vent Direct vent and Selkirk Direct-Temp. FPITM, and FPI AstroCapTM are the proprietary trademarks of FPI Fireplace Products International Ltd. Dura-Vent® and Direct Vent GS are registered and/or proprietary trademarks of Simpson Dura-Vent Co. Inc.

16

Waterford TARA T25 Direct Vent Freestanding Gas Stove

Image 16
Contents Tara Direct Vent Freestanding Gas Stove Waterford To the New OwnerTable of Contents Safety Label Copy of Safety Label for Tara T25 Gas StoveInstallation SpecificationsSave These Instructions Information for Mobile Manufactured Homes After First SaleGeneral Safety Information Installation ChecklistManufactured Mobile Home Additional Requirements Clearances to CombustiblesLocating Your GAS Stove Optional FAN InstallationTara Clearances Installation Combustion and Ventilation AIR Exterior Vent Terminal Planning Your venting Installation For your particular installationMinimum components for a Horizontal Installation Quired. Other parts may be requiredBelow Grade Snorkel Installation Horizontal InstallationsSnorkel Terminations Description Vertical Termination with CO-LINEAR Flex System Alternate Approved Caps DV Stove Horizontal Vent KIT Qty. DescriptionPlanning Your Dura-Vent Installation DURA-VENT Termination KITRigid Pipe Venting Components Alternate Horizontal Termination CapsRigid Pipe Venting Components List 4DT-AJBRigid Pipe Venting Vertical Terminations Rigid Pipe Venting Horizontal TerminationsFor both Residential & Manufactured Homes/Mobile Homes DURA-VENT Horizontal Installations Vent RestrictorTermination Offset Chart Cathedral CeilingsSupport Extensions Round Rdse or Square Sqse Round Support RDS Square Support SQSConverting a Masonry Chimney Converting a Factory Built Metal ChimneyHigh Elevation System Data Tara T25GAS Pipe Pressure Testing GAS ConnectionConversion KIT From Natural GAS To Propane Valve DescriptionReplace yellow Natural Gas label with red Propane label Aeration Adjustment Removing Cast Iron Front PanelOptional Front Grill Securing Cast Iron Front PanelOptional Side Shelf LOG InstallationOptional Wall Thermostat Optional Remote Control Wiring Diagram TaraThermostat Wire Table Final CheckOperating Instructions Sounds Maintenance Maintenance InstructionsGeneral Vent Maintenance LOG ReplacementGlass Replacement FAN MaintenanceValve Maintenance Installing Valve AssemblyParts List Replacement / Spare Parts ListPage Warranty ConditionsRegister your Waterford online at