Waterford Appliances T25-NG Manufactured Mobile Home Additional Requirements, This includes

Page 6

INSTALLATION

Thermostat. Some areas may have further requirements, check local codes before installation.

5)This appliance is Listed for Alcove installa- tions, maintain minimum Alcove clearances

as follows, minimum width of 33-1/2" (851mm), a maximum depth of 24" (610mm), and minimum ceiling height of 41-1/2" (1054mm).

6)We recommend that you plan your installa- tion on paper using exact measurements for clearances and floor protection before actually installing this appliance. Have a qualified building inspector review your plans before installation.

MANUFACTURED

MOBILE HOME

ADDITIONAL

REQUIREMENTS

1)Ensure that structural members are not cut or weakened during installation.

2)Ensure proper grounding using the #8 ground lug provided.

3)Appliance must be anchored to the floor with the supplied anchoring methods.

GENERAL SAFETY

INFORMATION

1)The appliance installation must conform with local Canadian Electrical Code.

2)The appliance when installed, must be elec- trically grounded in accordance with local codes, or in the absence of local codes with the current National Electrical Code, ANSI/ NFPA 70 or CSA C22.1 Canadian Electrical Code.

3)The appliance should be inspected for shipping damage before use andserviced annually by a professional service per- son. More frequent cleaning may be re- quired due to excessive lint from carpeting, bedding material, etc. It is imperative that control compartments, and circulating air passageways of the appliance be kept clean and free from excessive lint from carpeting.

4)See general construction and assembly instructions. The appliance and vent should be enclosed when installed in or passing through a living area, where children may come in contact with it.

5)This appliance must be connected to the

specified vent and termination cap to the outside of the building envelope. Never vent to another room or inside a building. Make sure that the vent is fitted as per the instruc- tions starting on page 9.

6)Inspect the venting system annually for blockage and any signs of deterioration.

7)Venting terminals shall not be recessed into a wall or siding.

8)Any safety glass removed for servicing must be replaced prior to operating the appliance.

9)To prevent injury, do not allow anyone who is unfamiliar with the operation to use the fireplace.

Emissions from burning wood or gas could contain chemicals known to the State of California to cause cancer, birth defects or other reproductive harm.

INSTALLATION

CHECKLIST

1)Check Clearances to Combustibles (page 6), location of unit (page 7) and venting requirements (pages 9-20).

2)a) Carefully unpack the unit from the pack- aging.

EXTREME CARE NEEDS TO BE TAKENWHENHANDLINGPOR- CELAIN ENAMEL PARTS OR CERAMIC LOGS TO AVOID DAMAGE. DAMAGE TO THESE PARTS IS NOT COVERED UN- DER WARRANTY.

b)Use a 7/16" wrench to remove the two lag bolts used to secure the stove to the pallet.

c)Locate the 4 leg levelling bolts supplied with the stove. Fit these bolts to the underside of the legs as shown. These levelling bolts can be used to level the stove on an uneven surface.

3)Install Optional Fan, see page 7.

4)Install venting: Check all venting require-

ments, pages 9 to 20. Minimum Horizontal Vent Kit, page 11, Vertical Termination Co- Linear Flex System, page 13, DV Stove Horizontal Vent Kit (page 14), and the Dura- Vent Termination Kits, page 15. Converting

a Class-A MetalChimney orMasonry Chim- ney to a Direct Vent System, page 21.

5)Make gas connections, page 24. Test the pilot. Must be as per diagram, page 26.

6)Test Gas Pressure, page 24.

7)Install logs where indicated on page 27.

8)Install Optional Side Shelves, page 27.

9)Install optional Remote Control, or Wall Ther- mostat, pages 27 and 28.

10)Final check, page 28.

Before leaving this unit with the customer, the installer must ensure that the appliance is firing correctly and operation fully explained to customer.

This includes:

1)Clocking the appliance to ensure the cor- rect firing rate (rate noted on label), first burning the appliance for 15 minutes.

2)If required, adjusting the primary air to ensure that the flame does not carbon. First allow the unit to burn for 15-20 min. to stabilize.

CAUTION: Any alteration to the product that causes sooting or carboning that results in damage is not the responsibil- ity of the manufacturer and is not a war- ranty issue.

CLEARANCES TO COMBUSTIBLES

The clearances listed are MINIMUM distances. Measure the clearance to both the appliance and the chimney connector. The farthest distance is correct if the two clearances do not coincide.

For example, if the appliance is set as indicated in one of the figures but the connector is too close, move the stove until the correct clear- ance to the connector is obtained.

This appliance may be installed only with the clearances as shown in the situations pic- tured. Do not combine clearances from one type of installation with another in order to achieve closer clearances.

This unit can be installed on a solid combustible surface like a wood floor. This unit can also be installed directly on carpeting or vinyl.

6

Waterford TARA T25 Direct Vent Freestanding Gas Stove

Image 6
Contents Tara Direct Vent Freestanding Gas Stove Waterford To the New Owner Table of Contents Safety Label Copy of Safety Label for Tara T25 Gas StoveSave These Instructions InstallationSpecifications Information for Mobile Manufactured Homes After First SaleManufactured Mobile Home Additional Requirements General Safety InformationInstallation Checklist Clearances to CombustiblesOptional FAN Installation Locating Your GAS StoveTara Clearances Installation Combustion and Ventilation AIR Exterior Vent Terminal Minimum components for a Horizontal Installation Planning Your venting InstallationFor your particular installation Quired. Other parts may be requiredHorizontal Installations Below Grade Snorkel InstallationSnorkel Terminations Vertical Termination with CO-LINEAR Flex System DescriptionAlternate Approved Caps DV Stove Horizontal Vent KIT Qty. DescriptionPlanning Your Dura-Vent Installation DURA-VENT Termination KITRigid Pipe Venting Components Alternate Horizontal Termination CapsRigid Pipe Venting Components List 4DT-AJBRigid Pipe Venting Horizontal Terminations Rigid Pipe Venting Vertical TerminationsFor both Residential & Manufactured Homes/Mobile Homes DURA-VENT Horizontal Installations Vent RestrictorTermination Support Extensions Round Rdse or Square Sqse Offset ChartCathedral Ceilings Round Support RDS Square Support SQSConverting a Masonry Chimney Converting a Factory Built Metal ChimneyHigh Elevation System Data Tara T25Conversion KIT From Natural GAS To Propane GAS Pipe Pressure TestingGAS Connection Valve DescriptionReplace yellow Natural Gas label with red Propane label Optional Front Grill Aeration AdjustmentRemoving Cast Iron Front Panel Securing Cast Iron Front PanelLOG Installation Optional Side ShelfOptional Wall Thermostat Thermostat Wire Table Optional Remote ControlWiring Diagram Tara Final CheckOperating Instructions Sounds General Vent Maintenance MaintenanceMaintenance Instructions LOG ReplacementValve Maintenance Glass ReplacementFAN Maintenance Installing Valve AssemblyParts List Replacement / Spare Parts ListPage Warranty ConditionsRegister your Waterford online at