3d Piping — low temp systems (continued)
Figure 12 System-bypass piping
Zoning with zone valve or circulators, return water 130°F or higher. (Alternative to boiler-bypass piping Figures 10 and 11, page 21)
3 System or zone circulator
7 System temperature valves (see instructions to the left for adjusting valves)
8 Blend temperature gauge
9 Relief valve
10 Automatic air vent (with
11 Fill valve
12
3e Water piping — refrigeration systems
Prevent chilled water from entering
Figure 13 Piping refrigeration systems
Install boiler so that chilled medium is piped in parallel with the heating boiler. Use appropriate valves to prevent chilled medium from entering boiler. See Figure 13 for typical installation of balancing valve and check valve.
If boiler is connected to heating coils located in air han- dling units where they can be exposed to refrigerated air, use flow control valves or other automatic means to prevent gravity circulation during cooling cycle.