3b Water piping — single-zone system
type expansion tank (Figure 4) | (Figure 5) |
1.Ensure expansion tank size will handle boiler and system water volume and temperature. Tank must be located in boiler return piping as close to boiler as possible, before inlet side of circulator. See tank manufacturer’s instructions for details.
2.Install an automatic air vent in air vent tapping as shown.
1.Ensure expansion tank size will handle boiler and system water volume and temperature. See tank manufacturer’s instructions for details.
2.Connect tank to ½” NPT tapping located behind supply outlet, using ½” NPT piping. Pitch any horizontal piping up towards tank 1 inch per 5 feet of piping.
Undersized expansion tanks cause system water to be lost from relief valve and makeup water to be added through fill valve. Eventual section failure can result.