GOLD CGs
3c Water piping — multiple zones
Piping multiple zones | Piping for radiant heating | |
Follow instructions on pages 14 and 15 to install near- | systems or converted gravity | |
boiler or | systems | |
radiant heating systems or converted gravity sys- | ||
tems, below, if applicable.) | Converted gravity (or steam) systems | |
See Figure 6 or Figure 7, page 17, to complete instal- | ||
Whenever possible, use the primary/secondary piping | ||
lation. | ||
| shown in Figures 8 or 9 on page 19. This piping design | |
Zoning with circulators (Figure 6) | allows changing boiler flow rate without affecting pri- | |
(return temp over 130°F) | mary circuit flow rate. | |
If Figures 8 or 9 cannot be used, use the | ||
1. Size each circulator to individual circuit require- | ||
piping shown in Figure 10 or Figure 11 on page 21. You | ||
ments. | ||
can also use the piping shown in Figure 12 on page 23 | ||
2. Do not install circulator on boiler (except for pri- | ||
mary/secondary piping). | ||
system will not cause heat distribution problems. | ||
3. Install isolation (balancing) valves to adjust flow to | ||
Failure to prevent low return water | ||
distribute heat to all zones. | ||
temperature to the boiler could | ||
4. Install and wire a separate relay for each zone cir- | ||
cause corrosion of the boiler sec- | ||
culator. | ||
tions or burners, resulting in severe | ||
| ||
| personal injury, death or substantial | |
Zoning with zone valves (Figure 7) | property damage. | |
| ||
(return temp over 130°F) | Radiant heating systems | |
1. Install isolation (balancing) valves to adjust flow to | Preferably, use primary/secondary piping, as shown | |
distribute heat to all zones. | in Figures 8 or 9 on page 19. Alternatively, use the | |
2. Provide a separate | method of either Figure 10 or Figure 11 on page 21. | |
zone valves. Size the transformer to handle the total | Do not use the piping of Figure 12 | |
rated load of all connected zone valves. | because this method does not control radiant system | |
| supply temperature. | |
| If radiant system tubing has no oxygen barrier, a heat | |
| exchanger must be used. |
Radiant heating system piping should include a means of regulating the boiler return water temperature and the system supply temperature (such as provided by an injection pumping control). Boiler return water temperature will be adequately controlled using the methods shown in this manual provided the system supply temperature is relatively constant.
DO NOT apply the methods in this manual if the system is equipped with an outdoor reset control. Instead, provide controls and piping which can regulate the boiler return water temperature at no less than 130°F regardless of system supply temperature. Contact your
16
Part number