Weil-McLain 550-110-260/0107 manual 3c Water piping multiple zones, Systems or converted gravity

Page 16

GOLD CGs Gas-Fired Water Boiler — Boiler Manual

3c Water piping — multiple zones

Piping multiple zones

Piping for radiant heating

Follow instructions on pages 14 and 15 to install near-

systems or converted gravity

boiler or single-zone piping. (Also refer to Piping for

systems

radiant heating systems or converted gravity sys-

tems, below, if applicable.)

Converted gravity (or steam) systems

See Figure 6 or Figure 7, page 17, to complete instal-

Whenever possible, use the primary/secondary piping

lation.

 

shown in Figures 8 or 9 on page 19. This piping design

Zoning with circulators (Figure 6)

allows changing boiler flow rate without affecting pri-

(return temp over 130°F)

mary circuit flow rate.

If Figures 8 or 9 cannot be used, use the boiler-bypass

1. Size each circulator to individual circuit require-

piping shown in Figure 10 or Figure 11 on page 21. You

ments.

can also use the piping shown in Figure 12 on page 23

2. Do not install circulator on boiler (except for pri-

(system-bypass), if the reduced flow rate in the heating

mary/secondary piping).

system will not cause heat distribution problems.

3. Install isolation (balancing) valves to adjust flow to

Failure to prevent low return water

distribute heat to all zones.

temperature to the boiler could

4. Install and wire a separate relay for each zone cir-

cause corrosion of the boiler sec-

culator.

tions or burners, resulting in severe

 

 

personal injury, death or substantial

Zoning with zone valves (Figure 7)

property damage.

 

(return temp over 130°F)

Radiant heating systems

1. Install isolation (balancing) valves to adjust flow to

Preferably, use primary/secondary piping, as shown

distribute heat to all zones.

in Figures 8 or 9 on page 19. Alternatively, use the

2. Provide a separate 24-volt transformer to power the

method of either Figure 10 or Figure 11 on page 21.

zone valves. Size the transformer to handle the total

Do not use the piping of Figure 12 (system-bypass),

rated load of all connected zone valves.

because this method does not control radiant system

 

supply temperature.

 

If radiant system tubing has no oxygen barrier, a heat

 

exchanger must be used.

Radiant heating system piping should include a means of regulating the boiler return water temperature and the system supply temperature (such as provided by an injection pumping control). Boiler return water temperature will be adequately controlled using the methods shown in this manual provided the system supply temperature is relatively constant.

DO NOT apply the methods in this manual if the system is equipped with an outdoor reset control. Instead, provide controls and piping which can regulate the boiler return water temperature at no less than 130°F regardless of system supply temperature. Contact your Weil-McLain representative for suggested piping and control methods. Failure to prevent cold return water temperature to the boiler could cause corrosion damage to the sections or burners, resulting in possible severe personal injury, death or substantial property dam- age.

16

Part number 550-110-260/0107

Image 16
Contents Gold CGs How it works Gold CGs Gas-Fired Induced-Draft Water Boiler Contents Please read before proceeding InstallerUser Installations must follow these codes 1a Prepare boiler location codes & checklistBefore locating the boiler, check the following 1b Prepare boiler location clearances When removing boiler from an existing common vent system 1c Prepare boiler location vent systemCGs special vent system Vent system1d Prepare boiler location contamination Products to avoid1e Prepare boiler location air openings Combustion air optionsSpecial considerations Sizing air openingsSizing air openings for CGs installations 2a Prepare boiler placement & setup Orifice replacement procedurePlace boiler/crate near position Inspect orifices and burners2b Prepare boiler pressure test Hydrostatic pressure testDrain and remove fittings Prepare boiler for test3a Water piping general information 3b Water piping single-zone system 3c Water piping multiple zones Piping multiple zones Piping for radiant heatingSystems or converted gravity SystemsReturn water 130F or higher Temperature gauges Valve adjustment Figures 8 and 9 only3d Piping low temp systems Primary/secondary preferred bypass piping methodPrimary/secondary piping Valve adjustment BOILER-bypass piping methodFigures 8 SYSTEM-bypass piping method 3e Water piping refrigeration systems Prevent chilled water from enteringVenting and combustion air Connecting gas supply piping to boiler Gas pipingNatural Gas Propane GasField wiring Electrical installation must comply withWiring connections ThermostatFreeze protection when used 7a Start-up preparationCheck for gas leaks Verify water chemistry7b Start-up operate boiler Inspect system water piping Inspect base insulationFinal check before starting boiler Start the boiler7c Start-up if boiler doesn’t start Check burner flamesCheck for Pilot burner flame FigureCheck-out procedure checklist Installation and service certificate9a Operation sequence 9b Operation wiring diagrams Schematic wiring diagramLadder wiring diagram 9c Operating instructions CGs-3 to CGs-6 9c Operating instructions CGs-3 to CGs-6 9c Operating instructions CGs-3 to CGi-6 10a Service and maintenance schedule Verify Proper Operation After Servicing10b Service & maintenance annual start-up Burners, base and inlet air box Condensate drain systemInducer motor Oiled-bearing circulators10b Service & maint. annual start-up Boiler relief valve Relief valve, typicalCleaning boiler heating surfaces Review with ownerBefore troubleshooting 11a Troubleshooting procedureCheck the following 11b Troubleshooting air pressure switch Air pressure switchCheck pressure switch setting Troubleshooting air pressure reading11c Troubleshooting control module Control indicator lights Lockout modesControl indicator lights NON-LOCKOUT modes Troubleshooting the control moduleControl module connections 11d Troubleshooting control module lights Chart 1 Troubleshooting Power light statusChart 2 Tstat Circ & Power lights flashing Chart 3 Press Switch & Power lights flashing Chart 4 Flame & Power lights flashing Item 8 , Does blower motor operate? Verify Sequence of operation, , 12a Replacement parts Section assembly Base Jacket Trim Controls12b Replacement parts section assembly Section assembly12c Replacement parts base Base assemblyDescription Weil-McLain Part number 12d Replacement parts jacket Jacket assemblyBoiler Model Weil-McLain part number 12e Replacement parts trim Part number12f Replacement parts controls Propane gas components13a Dimensions Dimensional drawing13b Ratings DOEHandling ceramic fiber and fiberglass materials Removal of Combustion Chamber Lining or Base Panels