Pentax N-0751M-OD installation manual Supply water piping, Drain piping, Hot water piping

Page 18

Installation and service must be performed by a qualified plumber. In the

10. Water Piping Commonwealth of Massachusetts, this product must be installed by a licensed plumber or gas fitter in accordance with the Massachusetts Plumbing and Fuel Gas Code 248 CMR Sections 2.00 and 5.00. Observe all applicable codes.

This appliance suitable for potable water and space heating applications. Do not use this appliance if any part has been underwater. Immediately call a qualified service technician to inspect the appliance and replace any part of the control system and gas control which has been under water.

If the water heater is installed in a closed water supply system, such as one having a backflow preventer in the cold water supply line, means shall be provided to control thermal expansion. Contact the water supplier or a local plumb- ing inspector on how to control this situation.

A pressure relief valve must be installed near the hot water outlet that is rated in accordance with and complying with either The Standard for Relief Valves and Automatic Shutoff Devices for Hot Water Supply Systems, ANSI Z21.22, or The ANSI/ASME Boiler and Pressure Vessel Code, Section IV ( Heating Boilers ). This pressure relief valve must be capable of an hourly Btu rated temperature steam discharge of 199,900 Btuh. Multiple valves may be used. The pressure relief capacity must not exceed 150 psig. No valve shall be placed between the relief valve and the water heater. The relief valve must be installed such that the discharge will be conducted to a suitable place for disposal when relief occurs. No reducing coupling or other restriction may be installed in the discharge line. The discharge line must be installed to allow complete drainage of both the valve and the line. If this unit is installed with a separate storage vessel, the separate vessel must have its own temperature and pressure relief valve. This valve must also comply with The Standard for Relief Valves and Automatic Gas Shutoff Devices for Hot Water Supply Systems, ANSI Z21.22. (in the U.S. only). A temperature relief valve is not required, but if one is used, do not install the valve with the probe directly in the flow of water. This may cause unwarranted discharge of the valve.

Piping and components connected to the water heater shall be suitable for use with potable water. Toxic chemicals, such as those used for boiler treatment, shall not be introduced into the potable water.

A water heater used to supply potable water may not be connected to any heating system or components previously used with a nonpotable water heating appliance.

When water is required in one part of the system at a higher temperature than in the rest of the system, means such as a mixing valve shall be installed to temper the water to reduce the scald hazard.

Flush water through the pipe to clean out metal powder, sand and dirt before connecting it.

Take appropriate heat insulation measures (e.g., wrapping with heat insulation materials, using electric heaters) according to the climate of the region to prevent the pipe from freezing.

Use a union coupling or flexible pipe for connecting the pipes to reduce the force applied to the piping.

Do not use piping with a diameter smaller than the coupling.

When feed water pressure is too high, insert a depressurizing valve, or take water hammer prevention measure.

Avoid using joints as much as possible to keep the piping simple.

Avoid piping in which an air holdup can occur.

If installing the unit on a roof:

About lower-level hot water supply

If the unit is installed on a roof to supply water to the levels below, make sure that the water pressure supplied to the unit does not drop below 29 psi. It may be necessary to install a pump system to ensure that the water pressure is maintained at this level.

Check the pressure before putting the unit into operation.

Failure to supply the proper pressure to the unit may result in noisy operation, shorter lifetime of the unit, and may cause the unit to shut down frequently.

Supply water piping

Do not use PVC, iron, or any piping which has been treated with chromates, boiler seal or other chemicals.

Mount a check valve and a shut off valve (near the inlet).

In order for the client to use the water heater comfortably, 98.1 to 491 kPa (14 to 70 PSI) of pressure is needed from the water supply.

Be sure to check the water pressure. If the water pressure is low, the water heater cannot perform to its full capability, and may become a source of trouble for the client.

Drain piping

Expansion water may drop from the pressure prevention device and wet the floor. If neces- sary, provide drain piping or use a drain hose to remove the water.

Hot water piping

Do not use lead, PVC, iron or any piping which has been treated with chromates, boiler seal or other chemicals.

The longer the piping, the greater the heat loss. Try to make the piping as short as possible.

Use mixing valves with low water resistance. Use shower heads with low pressure loss.

If necessary, use a pump or other means to en- sure that the supply water pressure to the inlet of the heater does not fall below 29 PSI when the maximum amount of water is being demanded. Also install a pressure meter on the inlet. If this is not done, local boiling will occur inside the water heater causing abnormal sounds and decreasing the durability of the heat exchanger.

18

Image 18
Contents Installation Manual CanadaEach See p Remote Controller Outdoor Junction BoxPart Shape Part Shape Outdoor Vent Cap VC4-1Controller to only one System DiagramTypical Plumbing UnitsBefore Installation Choosing Installation Site With corrugatedProhibited Be sure to do Installation Clearances Min 75mm 200mm Or Min 75mm 3 more600mm 24 or more Maintain the following clearance from both combustible When installing the unit on a balcony, etc., secure anSuch as the wall of the second floor where the unit is out Non-combustible materialsVent Terminal 9m 3 above any forced air inlet within Window, or gravity air inlet into any buildingFor N-0751M- OD Installation Be damaged and may become highly dangerousLocating Screw Holes Mounting Vent Piping ClearancesAppliance Adapters Horizontal Vent Termination Vertical Vent TerminationCombustion Air Openings supplying indoor airMeasuring Gas Pressure Gas Meter Gas PipingGas Pressure Gas ConnectionGas Line Sizing for a Noritz Gas Water Heater Supply water piping Drain pipingHot water piping Plumbing Applications For Space Heating PurposesElectrical Wiring Breaker InstallationGround Remote Controller Remove the front cover of the water heater 4 screwsHeard 2 sec. and 50 C 122 F appears on the display Connecting Remote Controller Cord to Unit Remote controller cordRelay connection with larger pumps 85 W Connecting the pump control wireWire Tag Pump ControlWiring Throughway Coupling Cord Remote controller can be connected to eitherConnecting the Quick Connect Cord to the two units Unit a or BMaintenance Periodically check the following to ensure properOperation of the water heater Handling after trial operation Lighting InstructionsShutdown Instructions Dimensions 0751M0751M-OD Connection of Remote Controller Cord For InstallersIncluded Parts List White ConnectorInstallation Remote Controller Cord Rear SideController cord outside the junction box Box NutTie the redundant length of the remote Close the junction boxNatural Gas and Propane Installation Code Nscngpic Pas évitée, entraînera des blessures graves ou mortellesProduits Être nécessaires à l’installation Pièce Forme Commencer l’installation Pièce FormeVoir p.21 Ce document Cordon de Télécommande Boîte de dérivation Extérieure de la TélécommandePlomberie type Télécommande à Un seul des AppareilsSchéma du système Remarque Raccordez laVérifiez le gaz Avant l’installationCheck-up Vérifiez la qualité de l’alimentation en eauChoix du site d’installation Interdit Veillez à ’exécuter Dégagement pour linstallation De calorifugeage matière incombustible autre que le Indique la distance lors de linstallation dune plaqueLorsque vous installez lunité sur un balcon, etc., laissez Métal, dune épaisseur de 2.5mm 0.1 ou plus ouEntrée d’alimentati on en air 2m 4 dessous, 1.2m Maintenez les dégagements suivants parRapport aux ouvertures d’un bâtiment Horizontalement à partir de, ou 0.3mInstallation dun boîtier encastré avec Encastr 3m 1 dessous, 0.3mCache déposé Fixation au mur Dégagement Installation du tuyau d’évent uniquementTuyauterie de l’évent Adaptateurs d’appareilBouche de l’évent horizontal Bouche de l’évent verticalAir comburant Ouvertures alimentant en air intérieurPression du gaz Mesure de la pression du gaz Compteur à gazRaccordement de gaz Adapté de UC1997 Conduite d’eau Plomberie Pour le chauffage du bâtimentAdressez-vous à un électricien Qualifié pour l’installation électriqueInstallation du disjoncteur TerreTélécommande Coupez lalimentation électrique du chauffe-eauRaccordement du cordon de télécommande à l’unité Cordon de télécommandeAttache Câble 18AWG Raccordement du câble de commande de la pompe Connexion par relais avec de grandes pompes 85WBranchement du cordon de raccordement rapide aux deux unités Connecteur Attache Ouverture pour Cordon de Câbles CouplageVérifiez régulièrement les points suivants pour Garantir un bon fonctionnement du chauffe-eauManipulation après le test de fonctionnement Instructions d’allumageInstructions d’arrêt 10mm Nom des pièces Quantité Télécommande Garniture du mur Pour les installateursRemarques sur l’emplacement d’installation RemarqueInstallation La boîte Attachez le cordon de la télécommandeÉcrou de Qui dépasse à l’extérieur de la boîte de

N-0751M-OD, N-0751M specifications

The Pentax N-0751M and N-0751M-OD are advanced digital cameras designed primarily for outdoor and rugged environments. These models exemplify the blend of functionality and durability that Pentax is known for, appealing to both photography enthusiasts and professionals who require reliable equipment in demanding conditions.

One of the standout features of the N-0751M and its counterpart, the N-0751M-OD, is their robust construction. Built to withstand harsh environments, these cameras are weather-resistant, ensuring that they can handle rain, dust, and extreme temperatures. This makes them ideal for nature photographers, adventure enthusiasts, and even those who work in challenging conditions.

The N-0751M series is equipped with a high-resolution sensor that captures stunning images with remarkable clarity and detail. The camera features an advanced image processing engine that enhances color accuracy and dynamic range, allowing users to create vibrant and lifelike photos. This sensor also performs exceptionally well in low-light environments, making it versatile for various shooting situations.

Another key characteristic of the N-0751M and N-0751M-OD is their fast and responsive autofocus system. This ensures that users can quickly lock onto their subjects, which is critical for capturing fleeting moments, whether in wildlife photography or action sports. The cameras also come with multiple autofocus modes and options, providing photographers with the flexibility to choose the best setting for their shooting style.

In terms of usability, the N-0751M series features an intuitive interface with customizable settings that allow users to adapt the camera to their personal preferences. The ergonomic design promotes comfort during extended shooting sessions, making it easy to navigate through menus and settings quickly.

For connectivity, the N-0751M and N-0751M-OD come equipped with Wi-Fi capabilities, facilitating easy sharing and remote control through a smartphone app. This enables photographers to transfer images wirelessly and control the camera from a distance, enhancing the shooting experience.

In summary, the Pentax N-0751M and N-0751M-OD embody the perfect combination of durability, image quality, and user-friendly technology. With robust features that cater to professional demands, these cameras stand out as reliable tools for capturing stunning images in any environment. Whether for work or passion, photographers can count on the N-0751M series to deliver superior performance and exceptional results.