| Installation |
|
| ||
|
|
|
|
To change to manual operation press EXIT for 5 seconds.
The LED above the hand symbol lights up. Change the firing rate of the boiler with or
. |
|
The firing rate increases as long as | is pressed. |
The firing rate decreases as long as | is |
pressed. |
|
LED's on the control indicate if the firing rate is increasing or decreasing.
To change back to automatic operation press EXIT for 5 seconds.
Manual operation can only be activated if the burner relay is on. If the control sets the burner relay to off
during manual operation, then the control is changed to automatic operation.
Parameter Level
To access the parameter level press and hold the PGM button for longer than two (2) seconds. The parameters available in this level are used for proper functioning of the boiler with the system.
Within the parameter level you can go to the next parameter by pressing PGM.
The parameters and their functions are listed in Ta- ble 1 on the following page. The actual parameters available depend on the configuration of the control.
18