Modu-Fire® Gas-Fired Boiler
4.Turn power switch on. If a red warning indica- tor is illuminated, see call for
4.2.2 Normal Shut Down Procedures
1.Close all manual gas valves.
2.Turn off electric power.
4.2.3 Emergency Shut Off
Main and pilot gas cocks should be closed immedi- ately if an emergency situation occurs; see Section 4.2.1 for the location of the gas cocks.
If overheating occurs or the gas supply fails to shut off, do not turn off or disconnect the electrical sup-
Operation
ply to the pump. Instead, shut off the gas supply at a location external to the boiler.
4.3TYPICAL BOILER OPERATING CONDITIONS
|
| Natural Gas | |
Model | Input | (1030 Btu/cu. Ft.) | |
Rating | Gas | Output | |
No. | (Btu/hr) | Rate | Capacity |
|
| (CFH) | (Btu/Hr.) |
1000 | 1,000,000 | 971 | 850,000 |
1500 | 1,500,000 | 1,456 | 1,275,000 |
2000 | 2,000,000 | 1,942 | 1,700,000 |
23