Patterson-Kelley MOD-04 owner manual Normal Shut Down Procedures, Emergency Shut Off

Page 26

Modu-Fire®Gas-Fired Boiler

4.Turn power switch on. If a red warning indica- tor is illuminated, see call for factory-trained personnel to troubleshoot the problem and im- plement corrective action. Wait five minutes before attempting to reset boiler.

4.2.2 Normal Shut Down Procedures

1.Close all manual gas valves.

2.Turn off electric power.

4.2.3 Emergency Shut Off

Main and pilot gas cocks should be closed immedi- ately if an emergency situation occurs; see Section 4.2.1 for the location of the gas cocks.

If overheating occurs or the gas supply fails to shut off, do not turn off or disconnect the electrical sup-

Operation

ply to the pump. Instead, shut off the gas supply at a location external to the boiler.

4.3TYPICAL BOILER OPERATING CONDITIONS

 

 

Natural Gas

Model

Input

(1030 Btu/cu. Ft.)

Rating

Gas

Output

No.

(Btu/hr)

Rate

Capacity

 

 

(CFH)

(Btu/Hr.)

1000

1,000,000

971

850,000

1500

1,500,000

1,456

1,275,000

2000

2,000,000

1,942

1,700,000

23

Image 26
Contents PATTERSON-KELLEY Modu-FireGas-Fired Boiler Table of Contents What to do if you smell gas Introduction/Safety Modu-FireGas-Fired BoilerBurn, Fire, and Explosion Hazards SafetyElectrical Hazards Chemical Hazards Modu-FireGas-Fired Boiler SafetyCrush Hazards Modu-FireGas-Fired Boiler Safety Pressure Hazards Slip, Fall HazardsPlacement Storage Prior to InstallationInstallation Initial InspectionModu-FireGas-Fired Boiler Installation ClearancesCombustion AIR Automatic Vent Damper Vent ElbowsBarometric Damper Flue ConnectionRemoving an Existing Boiler Pipe Capacity for Natural Gas Piping Design Modu-FireGas-Fired Boiler Gas Supply Piping by InstallerGas Bleeds and Vents by Installer Boiler Water Piping by Installer Boiler Inlet and Outlet ConnectionsInspection Flushing and FillingWater Quality Test of Limit Controls Test of Ignition Safety SystemTest of Low Water Cut-off 12.1A Configuring the Local Controller Test of Low Gas Pressure SwitchTest of High Gas Pressure Switch For example, assume the following settings Configuration level Is pressed Table of Parameters 12.1B Optional Remote Control Installation Air Flow AdjustmentsBasic Combustion Adjustment Procedure Control Panel Front Lighting ProceduresModu-FireGas-Fired Boiler Operation Normal Shut Down Procedures Emergency Shut OffMonthly During Operation Maintenance WeeklyDaily Semi-AnnuallyMaintenance AnnuallyPilot Tube Ceramic Spider Ignition Electrode Standard Modulating Modu-FireGas-Fired Boiler Maintenance IRI ModulatingLoss of Power Do not Table of Contents for this Section Parts/Technical SupportCustomer Connections Customer Customer Input Analog Connections Customer Alarm Safety Flame Interlock Start 2 # Interlock Start 1 # Alarm Safety Flame Interlock Start 2 # Interlock Start 1 # Customer Connections Page Page Main Assembly Part Modu-Fire Gas-Fired Boiler Parts/Technical SupportLocal Control Panel Modu-FireGas-Fired Boiler Parts/Technical Support Modu-FireGas-Fired Boiler Parts/Technical Support Gas Trains No.PartStandard Gas Train 1500 IRI Gas Train IRI Gas Train 1500 Modu-FireGas-Fired Boiler Parts/Technical Support Cabinet No. PartLimited Warranty Limited WarrantyMODU-FIREBOILER