IDEAL INDUSTRIES HE12, HE24, HE18, HE15 manual General Open Vent System Requirements, Balancing

Page 10

GENERAL

3 OPEN VENT SYSTEM REQUIREMENTS

The system should be vented directly off the boiler flow pipe, as close to the boiler as possible. The cold feed entry should be inverted and MUST be positioned between the pump and the vent, and not more than 150mm (6") away from the vent connection.

Note. Combined feed and vent pipes may also be fitted.

There should be a minimum height 450mm (18") of open vent above the cistern water level. If this is not possible refer to Frame 5. The vertical distance between the highest point of the system and the feed/expansion cistern water level MUST not be less than 450 mm (18"). The pump must be fitted on the flow side of the boiler.

A suitable pump is a domestic circulator capable of providing a maximum 11oC (20oF) temperature differential across the boiler with the whole of the heating circuit open (e.g. Grundfos UPS 15/50, 15/60 or equivalent). With the minimum flow circuit allowed by the controls the differential must not exceed 25 oC. (18oC for the HE15)

The vertical distance between the pump and feed/expansion cistern MUST comply with the pump manufacturer's minimum requirements, to avoid cavitation. Should these conditions not apply either lower the pump position or raise the cistern above the minimum requirement specified by Ideal Stelrad Group. The isolation valves should be fitted as close to the pump as possible.

Return & flow connections

load 30 - 60 = 22 mm load 70 - 80 = 28 mm

4 SCHEMATIC PIPEWORK AND SYSTEM BALANCING

The boiler does not normally need a bypass but at least some radiators on the heating circuit, of load at least 10% of the minimum boiler output, must be provided with twin lockshield valves so that this minimum heating load is always available (see footnote re. thermostatic radiator valves).

Balancing

1.Set the programmer to ON for both CH

and HW. Turn the cylinder thermostat down. Close the manual or thermostatic valves on all radiators, leaving the twin lockshield valves (on the radiators referred to above) in the open position. Turn up the room thermostat and adjust these lockshield valves to give boiler flow and return temperatures not more than

20 oC apart. These valves should now be left as set.

2.Open all manual or thermostatic radiator valves and adjust the lockshield valves on remaining radiators to give around

11oC temperature drop at each radiator.

3.Turn up the cylinder thermostat and

adjust the cylinder balancing valve so that the cylinder achieves a maximum flow consistent with adequate flow to the radiators. Check that with only the domestic hot water loop in circuit a differential temperature of 20 oC across the boiler is not exceeded.

4.Adjust room and cylinder thermostats and programmer to NORMAL settings.

10

icos - Installation & Servicing

Image 10
Contents Installation and servicing Icos Installation & Servicing 15, Frame 12 Packaging Removal 15, Frame 11 Unpacking17, Frame 16 Wall Mounting Template General Key to symbolsBoiler Data Boiler Size HE 12, HE 15, HE 18, HE Icos Rear Flue only General Boiler Water ConnectionsSide Flue only Operation SafetyGeneral Introduction Safe HandlingLocation of Boiler Flue InstallationGeneral Safe Handling of Substances GAS SupplyWater Circulation System TerminalAIR Supply Boiler Control InterlocksGeneral Open Vent System Requirements Schematic Pipework and System BalancingBalancing General Safety ValveSealed System Requirements Pressure GaugeSealed System Requirements Water Treatment Icos boiler range have an Aluminium alloy heat exchangerInstallation Boiler Assembly Exploded viewPack Contents Installation UnpackingUnpack and check the contents Pack a Contents Packaging RemovalDetermining the Flue Length and Flue Packs Required Installation Front and Bottom Panel RemovalFlue Kits Flue Assembly Exploded View Wall Mounting TemplateSetting the Flue Side Installation Preparing the WallSetting the Flue Rear Wall thicknesses of 210 to 435mmFitting the KIT Pack D Flue extension duct kit contentsFlue Extension Ducts General arrangementCondensate Pipe Termination Configurations Installation Condensate DrainFront View Condensate Pipe Termination Configurations Connecting the Flue to the Boiler Installation Mounting the BoilerFlues over 1 metre long Roof Flue KIT Contents / Options Flue OutletTerminal Position Minimum Dimension Installation Flue Terminal PositionFlat roof with structure Installation Flue Arrangement Installation Assembling the Roof Flue KIT Gaskets in the Boiler Flue Outletare Correctly FittedInstallation GAS Connection Electrical ConnectionsMains Connector Socket Installation Internal WiringIncoming mains wiring detail Supplied in hardware pack Fixed to boilerInstallation Pictorial Wiring Diagram Functional Flow Wiring DiagramElectrical Installation GAS Installation Installation External Electrical ControlsCommissioning and Testing Room ThermostatInstallation Initial Lighting FasciaHanding Over Installation General ChecksWater Circulation System Knob Setting Flow Temperature Central HeatingBoiler Front Panel Removal Servicing Servicing ScheduleBoiler Sealing PANEL/ Bottom Panel Removal Servicing FAN and Venturi Assembly Removal and Cleaning Burner Removal and CleaningReassembly Servicing Cleaning the Condensate S TrapCleaning the Heat Exchanger Reassemble the boiler in the following orderWhen replacing ANY component Servicing Replacement of ComponentsGeneral Refer to Frame Servicing FAN ReplacementBurner Replacement Remove the boiler front and sealingServicing Ignition Electrode Replacement Flame Detection Electrode ReplacementBurner Injector Replacement Servicing Spark Generator ReplacementGAS Control Valve Replacement Mains Switch Replacement Servicing Control BOX ReplacementTo change the user control only Servicing Overheat Thermostat Replacement Flue Thermistor ReplacementServicing Combustion Chamber Insulation Replacement Servicing Heat Exchanger Replacement Servicing Boiler Sealing Panel Seal Replacement Condensate S Trap ReplacementAlternating H n Fault Finding Fault Finding Chart Main MenuAlternating H E GO to Frame Alternating H9 Alternating L9 Board Error Fault FindingFlame Error 70 L.....FFlow Thermistor Error Overheat Error73 L....8..... FAN Error 72 L.......APhase Reversal Error Flame Detection Short Circuit Error76 H.....4...... Flue Thermistor Error 75 H......FShort List of Parts GC Part No Description Qty Product NoBoiler Casing Assembly List of Parts Controls Assembly Burner AssemblyIcos Installation & Servicing Installer Notification Guidelines Page Page Technical Training Certified ProductUsers guide To light the boiler Refer to Frame Minimum ClearancesOperation For short periods Knob Setting Flow Temperature Minimum Maximum 180For longer periods Problem Solution Points for the Boiler User
Related manuals
Manual 52 pages 43.45 Kb

HE12, HE15, HE18, HE24 specifications

The IDEAL INDUSTRIES HE series, comprising the HE24, HE18, HE15, and HE12 models, represents a significant advancement in the field of electrical testing and measurement tools. These versatile testers stand out in professional environments for their high accuracy, user-friendly interfaces, and advanced features designed to enhance efficiency and reliability in electrical inspections.

The HE24 is the flagship model, boasting an extensive range of functionalities. It includes advanced digital multimeter capabilities, allowing for precise measurements of voltage, current, and resistance. Its True RMS feature ensures accurate readings, even with non-linear loads. The HE24 also incorporates advanced connectivity options, including Bluetooth technology, enabling users to transfer data wirelessly to smartphones or tablets for further analysis. The large, backlit display enhances visibility in various lighting conditions, making it an ideal tool for both indoor and outdoor use.

The HE18 model, while slightly more streamlined than the HE24, still offers robust capabilities. It features multiple testing modes, including continuity and diode testing, catering to a wide range of electrical tasks. The HE18 also utilizes a user-friendly interface, allowing technicians to navigate easily through various functions. Equipped with a protective rubber housing, this model is durable and built to withstand the rigors of frequent use on job sites.

The HE15 and HE12 models represent the compact, entry-level offerings in the HE series. Designed for the budget-conscious user, these models retain essential functionalities such as basic voltage and current measuring capabilities while prioritizing ease of use. The HE15 includes a simple LED indicator to signal when measurements are being taken, promoting straightforward operation. Additionally, the HE12 features a lightweight design, making it the perfect tool for on-the-go technicians.

All models in the IDEAL INDUSTRIES HE series are engineered with safety in mind, adhering to stringent international testing standards. They provide superior insulation resistance and a high degree of accuracy, mitigating the risks associated with electrical work. Furthermore, their IP-rated enclosures ensure protection against dust and moisture, enhancing longevity.

In conclusion, the IDEAL INDUSTRIES HE24, HE18, HE15, and HE12 series represent a comprehensive range of electrical testing tools that cater to professionals' varied needs. With their combination of advanced features, user-friendly designs, and safety compliance, these models are excellent choices for any electrical technician aiming for accuracy and efficiency in their work.