A.O. Smith HW 610 warranty Combined Vent Sizing Tables, Model HW-300 Boiler

Page 17

TABLE 5, COMBINED VENT SIZING TABLES

MODEL HW-300 BOILER

 

Input: 300,000 Btuh

 

 

 

 

 

 

Draft Hood Outlet 8"

 

 

 

 

Required Connector or

Smoke Pipe Diameter

 

 

 

 

 

 

Connector

 

Total Vent Height (Measured in Feet Above Draft Hood)

 

 

10

 

15

20

30

 

40

50

60

 

80

 

100

 

Rise in Feet

 

 

 

 

 

 

 

 

 

Connector Diameter (in Inches)

 

 

 

 

 

 

 

 

 

 

 

 

 

1

10

 

10

10

10

 

10

10

10

 

10

 

10

 

2

10

 

10

10

10

 

10

10

10

 

10

 

10

 

3

10

 

10

10

10

 

10

10

10

 

10

 

10

 

4 or more

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Number

Total Input

 

Total Vent Height (Measured in Feet Above Draft Hood)

 

if Units

10

 

15

20

30

 

40

50

60

 

80

 

100

Btuh x 1000

 

 

 

 

Combined

 

 

Manifold and Common Vent Diameter (in Inches)

 

 

 

 

 

2

600

14

 

12

12

12

 

10

10

10

 

10

 

10

3

900

16

 

14

14

14

 

12

12

12

 

12

 

12

4

1200

18

 

16

16

14

 

14

14

14

 

12

 

12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MODEL HW-399 BOILER

 

 

 

 

 

 

 

 

Input: 399,000 Btuh

 

 

 

 

 

 

Draft Hood Outlet 10"

 

 

 

 

Required Connector or

Smoke Pipe Diameter

 

 

 

 

 

 

Connector

 

Total Vent Height (Measured in Feet Above Draft Hood)

 

 

10

 

15

20

30

 

40

50

60

 

80

 

100

 

Rise in Feet

 

 

 

 

 

 

 

 

 

Connector Diameter (in Inches)

 

 

 

 

 

 

 

 

 

 

 

 

 

1

12

 

12

12

12

 

12

12

12

 

12

 

12

 

2

12

 

12

12

10

 

10

10

10

 

10

 

10

 

3

12

 

10

10

10

 

10

10

10

 

10

 

10

 

4 or more

10

 

10

10

10

 

10

10

10

 

10

 

10

Number

Total Input

 

Total Vent Height (Measured in Feet Above Draft Hood)

 

if Units

10

 

15

20

30

 

40

50

60

 

80

 

100

Btuh x 1000

 

 

 

 

Combined

 

 

Manifold and Common Vent Diameter (in Inches)

 

 

 

 

 

2

798

14

 

14

14

12

 

12

12

12

 

12

 

12

3

1197

18

 

16

16

14

 

14

14

14

 

14

 

12

4

1596

20

 

20

18

16

 

16

16

14

 

14

 

14

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MODEL HW-420 BOILER

 

 

 

 

 

 

 

 

Input: 420,000 Btuh

 

 

 

 

 

 

Draft Hood Outlet 10"

 

 

 

 

Required Connector or

Smoke Pipe Diameter

 

 

 

 

 

 

Connector

 

Total Vent Height (Measured in Feet Above Draft Hood)

 

 

10

 

15

20

30

 

40

50

60

 

80

 

100

 

Rise in Feet

 

 

 

 

 

 

 

 

 

Connector Diameter (in Inches)

 

 

 

 

 

 

 

 

 

 

 

 

 

1

12

 

12

12

12

 

12

12

12

 

12

 

12

 

2

12

 

12

12

10

 

10

10

10

 

10

 

10

 

3

12

 

10

10

10

 

10

10

10

 

10

 

10

 

4 or more

10

 

10

10

10

 

10

10

10

 

10

 

10

Number

Total Input

 

Total Vent Height (Measured in Feet Above Draft Hood)

 

if Units

10

 

15

20

30

 

40

50

60

 

80

 

100

Btuh x 1000

 

 

 

 

Combined

 

 

Manifold and Common Vent Diameter (in Inches)

 

 

 

 

 

2

840

14

 

14

14

12

 

12

12

12

 

12

 

12

3

1260

18

 

16

16

14

 

14

14

14

 

14

 

12

4

1680

20

 

20

18

16

 

16

16

14

 

14

 

14

 

 

 

 

 

 

 

 

 

 

 

 

 

MODEL HW-520 BOILER

 

 

 

 

 

 

 

 

Input: 520,000 Btuh

 

 

 

 

 

 

Draft Hood Outlet 10"

 

 

 

 

Required Connector or

Smoke Pipe Diameter

 

 

 

 

 

 

Connector

 

Total Vent Height (Measured in Feet Above Draft Hood)

 

 

10

 

15

20

30

 

40

50

60

 

80

 

100

 

Rise in Feet

 

 

 

 

 

 

 

 

 

Connector Diameter (in Inches)

 

 

 

 

 

 

 

 

 

 

 

 

 

1

14

 

14

14

12

 

12

12

12

 

12

 

12

 

2

12

 

12

12

12

 

12

12

12

 

12

 

12

 

3

12

 

12

12

12

 

10

10

10

 

10

 

10

 

4 or more

12

 

12

12

12

 

10

10

10

 

10

 

10

Number

Total Input

 

Total Vent Height (Measured in Feet Above Draft Hood)

 

if Units

10

 

15

20

30

 

40

50

60

 

80

 

100

Btuh x 1000

 

 

 

 

Combined

 

 

Manifold and Common Vent Diameter (in Inches)

 

 

 

 

 

2

1040

16

 

16

14

14

 

14

14

12

 

12

 

12

3

1560

20

 

18

18

16

 

16

14

14

 

14

 

14

4

2080

22

 

22

20

18

 

18

18

16

 

16

 

14

5

2600

26

 

24

22

20

 

20

18

18

 

18

 

18

6

3120

28

 

26

24

22

 

22

20

20

 

18

 

18

7

3640

30

 

28

26

24

 

24

22

22

 

20

 

20

8

4160

32

 

30

28

26

 

24

24

22

 

22

 

20

MODEL HW-610 BOILER

 

Input: 610,000 Btuh

 

 

 

 

 

 

Draft Hood Outlet 12"

 

 

 

 

Required Connector or

Smoke Pipe Diameter

 

 

 

 

 

 

Connector

 

Total Vent Height (Measured in Feet Above Draft Hood)

 

 

10

 

15

20

30

 

40

50

60

 

80

 

100

 

Rise in Feet

 

 

 

 

 

 

 

 

 

Connector Diameter (in Inches)

 

 

 

 

 

 

 

 

 

 

 

 

 

1

16

 

14

14

14

 

14

14

14

 

14

 

14

 

2

14

 

14

14

14

 

14

12

12

 

12

 

12

 

3

14

 

14

12

12

 

12

12

12

 

12

 

12

 

4 or more

12

 

12

12

12

 

12

12

12

 

12

 

12

Number

Total Input

 

Total Vent Height (Measured in Feet Above Draft Hood)

 

if Units

10

 

15

20

30

 

40

50

60

 

80

 

100

Btuh x 1000

 

 

 

 

Combined

 

 

Manifold and Common Vent Diameter (in Inches)

 

 

 

 

 

2

1220

18

 

18

16

16

 

14

14

14

 

14

 

14

3

1830

22

 

20

20

18

 

18

16

16

 

16

 

14

4

2440

26

 

24

22

20

 

20

18

18

 

18

 

16

5

3050

28

 

26

26

24

 

22

22

20

 

20

 

18

6

3660

32

 

28

28

26

 

24

24

22

 

22

 

20

7

4270

34

 

32

30

28

 

26

24

24

 

22

 

22

8

4880

36

 

34

32

30

 

28

26

26

 

24

 

24

9

5490

38

 

36

34

30

 

30

28

28

 

26

 

24

10

6100

40

 

38

36

32

 

30

30

28

 

26

 

26

11

6710

42

 

38

38

34

 

32

30

28

 

28

 

26

12

7320

44

 

42

38

36

 

34

32

32

 

30

 

28

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MODEL HW-670 BOILER

 

 

 

 

 

 

 

Input: 660,000 or 670,000 Btuh

 

 

 

 

Draft Hood Outlet 12"

 

 

 

 

Required Connector or

Smoke Pipe Diameter

 

 

 

 

 

 

Connector

 

Total Vent Height (Measured in Feet Above Draft Hood)

 

 

10

 

15

20

30

 

40

50

60

 

80

 

100

 

Rise in Feet

 

 

 

 

 

 

 

 

 

Connector Diameter (in Inches)

 

 

 

 

 

 

 

 

 

 

 

 

 

1

16

 

14

14

14

 

14

14

14

 

14

 

14

 

2

14

 

14

14

14

 

14

12

12

 

12

 

12

 

3

14

 

14

12

12

 

12

12

12

 

12

 

12

 

4 or more

12

 

12

12

12

 

12

12

12

 

12

 

12

Number

Total Input

 

Total Vent Height (Measured in Feet Above Draft Hood)

 

if Units

10

 

15

20

30

 

40

50

60

 

80

 

100

Btuh x 1000

 

 

 

 

Combined

 

 

Manifold and Common Vent Diameter (in Inches)

 

 

 

 

 

2

1220

18

 

18

16

16

 

14

14

14

 

14

 

14

3

1830

22

 

20

20

18

 

18

16

16

 

16

 

14

4

2440

26

 

24

22

20

 

20

18

18

 

18

 

16

5

3050

28

 

26

26

24

 

22

22

20

 

20

 

18

6

3660

32

 

28

28

26

 

24

24

22

 

22

 

20

7

4270

34

 

32

30

28

 

26

24

24

 

22

 

22

8

4880

36

 

34

32

30

 

28

26

26

 

24

 

24

9

5490

38

 

36

34

30

 

30

28

28

 

26

 

24

10

6100

40

 

38

36

32

 

30

30

28

 

26

 

26

11

6710

42

 

38

38

34

 

32

30

28

 

28

 

26

12

7320

46

 

44

40

38

 

36

34

34

 

32

 

30

Known: (5) model HW-610 boilers. (See illustration). Connector rise - 2' (Note 1' is minimum). Total vent height 30'.

Problem: Determine diameter of connector, manifold and common vent.

Procedure: Enter the top of the HW-610 table (total vent height) at 30' and the side at 2' (connector rise). A 14" connector diameter is indicated for each connector rise.

To determine the manifold and common vent size, enter table on this page (total vent height) at 30 and the side at 5 boilers. A manifold diameter of 24" (610 mm) is indicated.

17

Image 17
Contents Tennessee Waltz Parkway Ashland City, TN Models HW 300, 399, 420, 520, 610Important Definitions Safe INSTALLATION, USE and ServiceGeneral Safety Table of Contents Propane Natural Dimensions and Capacity Data27.7 33.3 Recovery CapacitiesLIQUefied petroleum gas models High Altitude InstallationsIntroduction Controls and Function High Limit Switch Safety Flow Switch Manual Reset High LimitThermal Balancer GPM LPMSafety Relief Valves Tank Temperature Control Thermometers GeneralDrain Valve Not Supplied Required AbilityCanadian Installations Confined Space S. InstallationsAIR Requirements Unconfined Space Typical Boiler Installation Installation Clearances Venting LevelingConnecting Boiler to a Common Vent Vent Pipe InstallationDraft Hood Vent ConnectionVenting System Venting Sidewall Optional Power Vent SystemMultiple Vent Table Model HW-300 Boiler Combined Vent Sizing TablesConventional Installations System InstallationsLINEAR-TEMP Installations ONE Boiler Installed Independent of the Primary SystemSchematic of the LINEAR-TEMPSYSTEM NO. Suggested Items for InstallationBoiler Inlet Outlet Sizes Minimum Branch Sizes to BoilersGAS Connections Correct GAS Purging and SizingSpecific Multiplier Gravity ExampleGAS Pressure Regulators Model Rated Manifold Pressure Number Input Natural PropaneWiring Connections WiringD. System HW 300 toSingle Stage I.I.D. Honeywell GAS Valve HW 300 thru 670. Natural and Propane GAS U.S. & CanadaLINEAR-TEMP Installations Boilers and Secondary Circulator are Controlled by Page MODELS, Jucntion BOX W/4 Terminals Canadian MODELS, Junction BOX W/6 TerminalsCanadian MODELS, Junction BOX W/6 Terminals Schematic MODELS, Junction BOX W/4 Terminals MODELS, Junction BOX W/4 Terminals Piping Wiring Figures 16 and 17 on Pages 24Commercial Boiler with Vertical Tank USE this Table for Correct Pump and Water Pipe SizeCommercial Boiler with Horizontal Tank Commercial Boiler with Vertical TANK, CER-TEMP Wiring Figures 21 to 27 on Pages 28 toHW-300 HW-399 HW-420 HW-520 Three HW-520s, HW-610s or HW-670s UP-FLOW Model USE this Table for Correct Pump and Water Pipe Size Filling the System Operation and START-UP InstructionsPilot and Main Burner Main BurnerPilot Burner Electronic Ignition Refer to Operating at Full Input or Full Capacity Checking and Adjusting the InputConsumption Rate Stage Main Burner Operation Flame Current Sensed For Your Safety Read Before Lighting URN Pilo T Firing VA LVE Counterclockwise SET T HE Thermostat to Lowwest SettingRelief Valve General MaintenanceManual Reset High Limit Switch Continuity Test PRE-TROUBLESHOOTING Cleaning and Flushing InstructionsHOT Water Supply Boilers Preventive Maintenance Internal ContaminantsCER-TEMP 80 Recovery System Checkout Procedure TroubleshootingYES Is ceramic insulator surrounding the electrode in good Burner ignition problems?Condition not cracked or broken? Is there excessive draft conditions that may cause pilotMV & MV/PV? Replace pilot burner assembly Location of LEDs Flame LED Yellow LED Status and TroubleshootingStatus LED Green OFFNo Call for Heat Not applicable None OFF Conditions and Exceptions Limited Warranty