A.O. Smith HW 610 warranty Purging and Sizing, Correct GAS

Page 21

TO TRAP ANY DIRT OR FOREIGN MATERIAL IN THE GAS SUPPLY LINE, A DIRT LEG (SOMETIMES CALLED DRIP LEG or sediment trap) MUST BE INCORPORATED IN THE PIPING, see Figure 1 on page 6. The dirt leg must be readily accessible and not subject to freezing conditions. INSTALL IN ACCORDANCE WITH RECOMMENDATIONS OF SERVING GAS SUPPLIERS. (Refer to National Fuel Gas Code, ANSI Z223.1 or CAN/CSA-B 149.1 Installation Codes.

To prevent damage, care must be taken not to apply too much torque when attaching gas supply pipe to the gas valve gas inlet.

Fittings and unions in the gas line must be the metal to metal type.

Apply joint compounds (pipe dope) sparingly and only to the male threads of pipe joints. Do not apply compound to the first two threads. Use compounds resistant to the action of liquefied petroleum gases.

THE BOILER AND ITS GAS CONNECTIONS MUST BE LEAK TESTED BEFORE PLACING THE BOILER IN OPERATION. Use soap and water solution or other material acceptable for the purpose in locating gas leaks. DO NOT USE MATCHES, CANDLES, FLAME OR OTHER SOURCES OF IGNITION FOR THIS PURPOSE.

DISCONNECT THE BOILER AND ITS MAIN MANUAL GAS SHUTOFF VALVE FROM THE GAS SUPPLY PIPING SYSTEM DURING ANY PRESSURE TESTING OF THE GAS SUPPLY SYSTEM OVER 1/2 PSIG (3.5kPa). THE GAS SUPPLY LINE MUST BE CAPPED WHEN NOT CONNECTED TO THE BOILER.

THE BOILER MUST BE ISOLATED FROM THE GAS SUPPLY PIPING SYSTEM BY CLOSING ITS MAIN MANUAL GAS SHUTOFF VALVE DURING ANY PRESSURE TESTING OF THE GAS SUPPLY PIPING SYSTEM AT TEST PRESSURES EQUAL TO OR LESS THAN 1/2 PSIG (3.5kPa).

PURGING AND SIZING

Gas line purging is required with new piping or systems in which air has entered.

CAUTION

PURGING SHOULD BE PERFORMED BY PERSONS EXPERIENCED IN THIS TYPE GAS SERVICE TO AVOID RISK OF FIRE OR EXPLOSION. PURGE DISCHARGE MUST NOT ENTER CONFINED AREAS OR SPACES WHERE IGNITION CAN OCCUR. THE AREA MUST BE WELL VENTILATED AND ALL SOURCES OF IGNITION MUST BE INACTIVATED OR REMOVED.

1.CORRECT GAS

Make sure the gas on which the boiler will operate is the same as that specified on the boiler rating plate. Do not install the boiler if equipped for a different type gas — consult your supplier.

2A. SIZING GAS SUPPLY LINE (For single boiler installations and for installations of multiples of two or three of same size boilers).

Use table 7, or CAN/CSA B149.1 (current edition) to size iron pipe or equivalent gas supply line. Table 7 is based on a pressure drop of 0.3 inches of water and a specific gravity of 0.60 approximately that of natural gas. (LP gas has an S.G. of about 1.53). If the service pressure is five inches water column or less, use one pipe size larger in order to minimize pressure drop in the line.

TABLE 7.

MAXIMUM CAPACITY OF PIPE IN CUBIC FEET OF GAS PER

HOUR (BASED UPON A PRESSURE DROP OF 0.3 INCH WATER COLUMN AND 0.6 SPECIFIC GRAVITY GAS)

Distance

 

 

Nominal Iron Pipe Size (Inches)

 

from Gas

 

 

 

 

 

 

 

 

 

 

 

 

Meter

 

 

 

 

 

 

 

 

 

1/2

3/4

1

1 1/4

1 1/2

2

2 1/2

3

4

 

 

10

(3)

132

278

520

1,050

1,600

3,050

4,800

8,500

17,500

20

(6)

92

190

350

730

1,100

2,100

3,300

5,900

12,000

30

(9)

73

152

285

590

890

1,650

2,700

4,700

9,700

40(12)

63

130

245

500

760

1,450

2,300

4,100

8,300

50 (15)

56

115

215

440

670

1,270

2,000

3,600

7,400

60 (18)

50

105

195

400

610

1,150

1,850

3,250

6,800

70 (21)

46

96

180

370

560

1,050

1,700

3,000

6,200

80 (24)

43

90

170

350

530

990

1,600

2,800

5,800

90 (27)

40

84

160

320

490

930

1,500

2,600

5,400

100

(30)

38

79

150

305

460

870

1,400

2,500

5,100

125

(38)

34

72

130

275

410

780

1,250

2,200

4,500

150

(45)

31

64

120

250

380

710

1,130

2,000

4,100

175

(53)

28

59

110

225

350

650

1,050

1,850

3,800

200

(60)

26

55

100

210

320

610

980

1,700

3,500

*The heating value of Natural Gas is approximately 1,050 Btu/Ft.3. Propane (LP) Gas has a heating value of approximately 2,500 Btu/Ft3. 1 cu. meter=35.31 cu. feet.

Where it is necessary to use more than the average number of pipe fittings i.e. elbows, tees, and valves in gas supply line, use a pipe larger than specified to compensate for increased pressure drop.

2B. SIZING GAS SUPPLY LINE (For multiples of over three boilers of same size or for multiple installations of two or more mixed sizes).

Capacities in cubic feet per hour of 0.60 specific gravity gas for different sizes and lengths are shown in table 7. No additional allowance is necessary for an ordinary number of fittings.

Applications of the gravity factor converts the figures given in table 7 to capacities with another gas of different specific gravity. Such application is accomplished by multiplying the capacities given in table 7 by the multipliers shown in table 8 on page 22.

To determine the size of each section of gas piping in a system within the range of table 7 proceed as follows:

Determine the gas demand of each appliance to be attached to the piping system. When table 7 is to be used to select the piping size, calculate the gas demand in terms of cubic feet per hour for each piping system outlet. The gas demand for an appliance can be found by dividing its heat input rate by the gas’s heating value.

Obtain or determine the length of piping from the gas meter or service regulator to the appliance(s).

21

Image 21
Contents Tennessee Waltz Parkway Ashland City, TN Models HW 300, 399, 420, 520, 610Important Definitions Safe INSTALLATION, USE and ServiceGeneral Safety Table of Contents Propane Natural Dimensions and Capacity Data27.7 33.3 Recovery CapacitiesHigh Altitude Installations IntroductionLIQUefied petroleum gas models Controls and Function High Limit Switch Safety Flow Switch Manual Reset High LimitThermal Balancer GPM LPMSafety Relief Valves Tank Temperature Control Thermometers GeneralDrain Valve Not Supplied Required AbilityCanadian Installations Confined Space S. InstallationsAIR Requirements Unconfined SpaceTypical Boiler Installation Installation ClearancesVenting LevelingConnecting Boiler to a Common Vent Vent Pipe InstallationDraft Hood Vent ConnectionVenting Sidewall Optional Power Vent System Multiple Vent TableVenting System Model HW-300 Boiler Combined Vent Sizing TablesConventional Installations System InstallationsLINEAR-TEMP Installations ONE Boiler Installed Independent of the Primary SystemSchematic of the LINEAR-TEMPSYSTEM NO. Suggested Items for InstallationBoiler Inlet Outlet Sizes Minimum Branch Sizes to BoilersGAS Connections Correct GAS Purging and SizingSpecific Multiplier Gravity ExampleGAS Pressure Regulators Model Rated Manifold Pressure Number Input Natural PropaneWiring Connections WiringD. System HW 300 toSingle Stage I.I.D. Honeywell GAS Valve HW 300 thru 670. Natural and Propane GAS U.S. & CanadaLINEAR-TEMP Installations Boilers and Secondary Circulator are Controlled by Page MODELS, Jucntion BOX W/4 Terminals Canadian MODELS, Junction BOX W/6 TerminalsCanadian MODELS, Junction BOX W/6 Terminals Schematic MODELS, Junction BOX W/4 Terminals MODELS, Junction BOX W/4 Terminals Piping Wiring Figures 16 and 17 on Pages 24Commercial Boiler with Vertical Tank USE this Table for Correct Pump and Water Pipe SizeCommercial Boiler with Horizontal Tank Commercial Boiler with Vertical TANK, CER-TEMP Wiring Figures 21 to 27 on Pages 28 toHW-300 HW-399 HW-420 HW-520 Three HW-520s, HW-610s or HW-670s UP-FLOW Model USE this Table for Correct Pump and Water Pipe Size Filling the System Operation and START-UP InstructionsPilot and Main Burner Main BurnerPilot Burner Electronic Ignition Checking and Adjusting the Input Consumption RateRefer to Operating at Full Input or Full Capacity Stage Main Burner Operation Flame Current Sensed For Your Safety Read Before Lighting URN Pilo T Firing VA LVE Counterclockwise SET T HE Thermostat to Lowwest SettingGeneral Maintenance Manual Reset High Limit Switch Continuity TestRelief Valve PRE-TROUBLESHOOTING Cleaning and Flushing InstructionsHOT Water Supply Boilers Preventive Maintenance Internal ContaminantsCER-TEMP 80 Recovery System Checkout Procedure TroubleshootingYES Is ceramic insulator surrounding the electrode in good Burner ignition problems?Condition not cracked or broken? Is there excessive draft conditions that may cause pilotMV & MV/PV? Replace pilot burner assembly Location of LEDs Flame LED Yellow LED Status and TroubleshootingStatus LED Green OFFNo Call for Heat Not applicable None OFF Conditions and Exceptions Limited Warranty