Heat & Glo LifeStyle TIARAP-CTO Cut and bend flashing as needed to fit Sealant adhesive

Page 21

CAUTION

Ensure that existing chimney is functionally sound and clean.

Have inspection done by qualified chimney sweep or professional installer BEFORE converting to direct vent appliance.

Step 1.

Before cutting any holes, assemble the desired sections of direct vent pipe to determine the center of the masonry penetration.

Step 2.

Once the center point of the penetration has been determined, cut a 6 in. (152mm) diameter hole in the masonry. If the hole is too large, the retro connector might not mount properly; if the hole is too small, the appliance might starve for intake air. If there is a frame wall in front of the masonry wall, cut and frame a 10 in. (254mm) square opening in the wall (centered around the 6 in. (152mm) masonry opening). If there is sheet rock only (no studs) in front of the masonry the 10 in. (254mm) opening is still needed, but does not need to be framed. If the hole is framed a round support box/wall thimble is required. This allows the retro connector to mount directly on the masonry and provide the correct clearances to combustibles (Figure 5.25).

Studwall

10 in. x 10 in. (254mm x 254mm)

framed opening in wallMasonry Chimney

Retro Connector

Wall Thimble Cover

(4) Masonry Bolts

(Not Included)

NOTE: For hearth applications refer to page 19, Figure 5.24 for the use of a co-axial to co-linear appliance connector.

Figure 5.25

Cut and bend flashing as needed to fit

Figure 5.26

Sealant adhesive

 

Step 4.

To determine the length of flex needed, measure from 3 in. (76mm) above the top of the flashing down to the level of the opening. Add the distance from the center of the chimney out through the wall. Cut a piece of 4 in. (102mm) flex to this length (extended to its nominal length). Be sure to leave 2-3 in. (51-76mm) of flex above the existing chimney to allow for connection to the termination kit.

Step 5.

Connect the flex liner to the top adapter using three sheet metal screws (Figure 5.21 page 19).

Step 6.

Feed the flex liner through the flashing into the chimney. Carefully feed the flex liner down the chimney to the bottom and out the opening in the masonry wall, forming an angle to line up the flex liner with the vent opening on the appliance.

WARNING

Fire Risk.

Explosion Risk.

Do not let the flex liner sag below the level at which it will connect to the appliance or connector. This could allow hot gas to become trapped and potentially become a fire hazard. The flex liner path should always be sloped up toward the termination cap.

Step 3.

Secure the flashing to the top of the masonry chimney using a bead of non-hardening sealant-adhesive. If the flashing is larger than the top of the chimney, cut and fold flashing as needed to fit chimney (Figure 5.26).

Step 7.

If additional lengths of flex liner are needed to span the chimney height, use a flex coupler to connect the pieces of flex liner together. Connect the flex to the coupler by using four sheet metal screws for each side (Figure 5.27, on the next page).

August 1, 2008

Heat & Glo · Tiara Petite B · 7026-101K

Page 21

Image 21
Contents Installation and Operation What to do if you smell gasHot glass will cause burns Location Hang tag attached to rear of appliance CongratulationsTable of Contents 1Listing and Code Approvals Requirements for the Commonwealth of Massachusetts Getting Started Design & Installation ConsiderationsTools and Supplies Needed Inspect Appliance & ComponentsAppliance Location and Clearances Selecting Appliance LocationClearances to Combustibles Vent Termination Minimum Clearances 4Termination LocationsAlcove Applications Venting Components Vent InformationUse of Elbows Measuring StandardsVenting Guidelines How to Use the Vent GraphStep Horizontal Termination203mm Vinyl Siding Direct Vent Pipe Vertical TerminationCeiling Joists Framing 2 in mm Long Wood Screws Twist-lock the vent cap and seal Level Cathedral Ceiling Support Box Cathedral CeilingClass a Metal Chimney Type a & B Co-Axial to Co-Linear Type C Up & Out InstallationExisting Masonry Chimney Type D Hearth MountCut and bend flashing as needed to fit Sealant adhesive Flex Liner Flex Coupler Sheet Metal Screws Slim Line Wall Thimble Installing Slim Line Trim Ring and Heat ShieldAssembling Slim Line Trim Ring and Heat Shield NextFIG. C Minimum Clearance Gas Information Wire clipFuel Conversions Converting to LP GasScrews Rubber Gasket Identification Label F Valve Regulator ReplacementGas Connection Gas PressuresHigh Altitude Installations Connecting to the Appliance Recommendation for WireStanding Pilot Ignition System Wiring Wire Size Max. LengthTo access the module Ignition Module Access and Battery ReplacementAppliance Setup Remove Shipping Materials Flue Restrictor InstallationLeg Leveling System Intake Damper Operation Positioning the Logs Intake Air Shutter AdjustmentMineral Wool AccessoriesKIT Contents Blower InstallationAugust 1 Heat & Glo · Tiara Petite B · 7026-101K 19 Complete Assembly Glass Replacement Warming Shelves InstallationOperating Instructions Before Lighting ApplianceControls Lighting Appliance For Your Safety Read Before LightingFrequently Asked Questions Initial Break-in ProcedureAfter Appliance is Lit Symptom Possible Cause Corrective Action TroubleshootingBe Placed in this Opening After servicing Maintaining and Servicing ApplianceNecessary. USE Caution When CLEANING/HANDLING Ceramic Burner Maintenance Tasks InspectReference Materials Appliance Dimension DiagramSL-D Series Vent Components Vent Components DiagramHHT SL-P Vent Components ListTermination Caps & Kits Description Tiara Petite BService Parts List cont’d. Tiara Petite B Tiara Petite B Cast Parts Individual Pieces Accessories Date of Service Performed By Description of Service Service and Maintenance LogLimited Lifetime Warranty Heat & GLO GAS Appliance Products Warranty PolicyTiara Petite B Contact InformationDealer Telephone