Hearth and Home Technologies HUDBAY-FS Vent Information, Venting Components, Use of Elbows

Page 10

5 Vent Information

A. Venting Components

In order to comply with applicable codes and product warranties, use only following venting components:

Hearth & Home Technologies (HHT)

Security Chimney's Secure Vent Chimney System

Selkirk Metalbestos

AmeriVent

Simpson Dura-Vent (SDV)

DO NOT USE FIELD-FABRICATED VENTING COMPONENTS. Refer to the venting manufacturer’s

instructions.

This product is approved to be vented either horizontally, through the side wall or vertically through the roof. You may vent through a Class A or masonry chimney if an approved adapter is used.

This appliance is a direct vent heater. All combustion air must come directly from the outside of the building. The vent pipe for this unit consists of an inner and an outer pipe. The inner pipe carries the appliance exhaust out of the system, and the outer pipe brings fresh combustion air into the appliance.

A round support box/wall thimble or heat shield is required when the venting passes through a combus- tible wall.

A support box or ceiling firestop is required when the venting passes through a ceiling.

Roof flashing and a storm collar are required when vent- ing passes through the roof.

Follow instructions provided with the venting for instal- lation of these items.

B. Use of Elbows

CAUTION

ALL vent configuration specifications MUST be followed.

This product is tested and listed to these specifications.

Appliance performance will suffer if specifications are not followed.

Diagonal runs have both vertical and horizontal vent aspects when calculating the effects. Use the rise for the vertical aspect and the run for the horizontal aspect. (See Figure

5.1.)

Two 45° elbows may be used in place of one 90° elbow. On 45° runs, one foot of diagonal is equal to 8-1/2 in. (216mm) horizontal run and 8-1/2 in. (216mm) vertical run. A length of straight pipe is allowed between two elbows. (See Figure

5.1.)

Vertical

 

 

.

 

 

in

 

.

1/2

12

in

 

8

 

 

-

8-1/2 in.

Horizontal

Figure 5.1

WARNING

Fire Hazard. Explosion Risk. Asphyxiation Risk.

Do NOT connect this gas appliance to a chimney flue serving a separate solid-fuel or gas burning appliance.

Vent this appliance directly outside.

Use separate vent system for this appliance.

May impair safe operation of this appliance or other appliances connected to the flue.

C. Measuring Standards

Vertical and horizontal measurements were made using the following standards.

Pipe measurements are from center line to center line.

Horizontal terminations are measured to the outside of the mounting surface (flange of termination cap). See Figure 4.1 on page 8.

Vertical terminations are measured to the top of the last pipe before termination cap.

Horizontal pipe installed level with 1/4 in. rise.

 

 

 

 

Page 10

Quadra-Fire • Hudson Bay • 7003-121 Rev. i

10/08

Image 10
Contents Do not Discard this Manual What to do if you smell gasDo Discardnot Welcome to the Quadra-Fire Family Table of Contents 1Listing and Code Approvals BELOW. Keep Clear of ALL Obstructions Requirements for the Commonwealth of MassachusettsManufacturer Requirements Getting Started Design & Installation ConsiderationsTools will apply to every installation Inspect Appliance & ComponentsSelecting Appliance Location Appliance Location and ClearancesClearances 4Termination Locations Vent Termination Minimum ClearancesAlcove Applications Use of Elbows Vent InformationVenting Components Measuring StandardsHow to Use the Vent Graph Vertical Distance from Appliance to to the 90 ElbowHorizontal Termination StepCenter Hole Line Wallcenter Thimbleline Fold Strap Here Sheet Metal Screw Direct Vent Pipe Vertical TerminationStep Wood Screws Twist-lock the vent cap and seal Cathedral Ceiling Class a Metal Chimney Existing Masonry Chimney Retro Connector Fuel Conversions Gas InformationConverting to LP Gas Valve Regulator Replacement Remove pilot hood and set asideGas Pressures PressureGas Connection Check for GAS LeaksStanding Pilot Ignition System Wiring Recommendation for WireConnecting to the Appliance Wire Size Max. LengthRED 28 711 MM ValveDoor Crown Installation Appliance SetupAccessories Remove Shipping MaterialsGrille Installation Brick Set InstallationPositioning the Logs 13 Log SetMineral Wool Blower Installation 23 Blower Wiring DiagramGlass Replacement Damper AdjustmentShutter Adjustment Door Frame with Glass Assembly ReplacementBefore Lighting Appliance Operating InstructionsControls For Your Safety Read Before Lighting Lighting ApplianceInitial Break-in Procedure Frequently Asked QuestionsAfter Appliance is Lit Troubleshooting Symptom Possible Cause Corrective ActionBe Placed in this Opening Maintaining and Servicing Your Appliance After servicingMaintenance Tasks Inspect Necessary. USE Caution When CLEANING/HANDLING Ceramic BurnerAppliance Dimension Diagram Reference MaterialsVent Components Diagram SLP Series Vent ComponentsVent Components List MiscellaneousRD. Service Parts List Stocked At DepotValve Components Pedestal Components DepotDescription Serial # Part Number CONDITIONS, Exclusions & Limitation of Liability Limited Lifetime Warranty Serial Number Date Purchased Date Installed Dealer Telephone Hudson Bay Direct Vent Gas Appliance