M. Install Horizontal Termination Cap (DVP and SLP Pipe)
WARNING! Risk of Fire! The telescoping flue section of the termination cap MUST be used when connecting vent.
•
Failure to maintain overlap may cause overheating and fire.
• | Vent termination must not be recessed in the wall. Siding |
| may be brought to the edge of the cap base. |
• | Flash and seal as appropriate for siding material at |
| outside edges of cap. |
Note: When using termination caps with
| HEAT SHIELD OR | HEAT SHIELD | |
| EXTENDED | ||
| |||
| HEAT SHIELD | ||
WALL SHIELD | OVERLAP | ||
| |||
|
| ||
FIRESTOP |
|
|
SLIP SECTION
CAN BE EXTENDED
• When installing a horizontal termination cap, follow |
the cap location guidelines as prescribed by current |
INNER VENT
OUTER VENT
SHEATHING
ANSI Z223.1 and |
and refer to Section 6 of this manual. |
CAUTION! Risk of Burns! Local codes may require in- stallation of a cap shield to prevent anything or anyone from touching the hot cap.
NOTICE: For certain exposures which require superior resistance to
INTERIOR | EXTERIOR |
VENT DEPTH FROM BACK OF APPLIANCE TO
OUTSIDE SURFACE OF EXTERIOR WALL
(SEE CHART BELOW)
Figure 10.25 Venting through the wall
Termination Cap Specification Chart (depth without using additional pipe sections)
| ||||
| Top Vent | Rear Vent | Top Vent | Rear Vent |
| Depth | Depth | Depth | Depth |
| N/A | N/A | ||
| 5 in. | |||
|
|
| ||
SL Series |
|
|
|
|
|
|
| ||
| Top Vent | Rear Vent | Top Vent | Rear Vent |
| Depth | Depth | Depth | Depth |
| N/A | N/A | ||
| ||||
|
|
|
48 | Heat & Glo • |