15 Troubleshooting

With proper installation, operation, and maintenance your gas appliance will provide years of trouble-free service. If you do experience a problem, this troubleshooting guide will assist a qualified service technician in the diagnosis of a problem and the corrective action to be taken. This troubleshooting guide can only be used by a qualified service technician. Contact your dealer to arrange a service call by a qualified service technician.

A. Intellifire Ignition System

Symptom

Possible Cause

Corrective Action

 

 

 

1. Pilot won’t light.

A. Incorrect wiring.

Verify “S” wire (white) for sensor and “I” wire (orange) for ignitor are

The ignitor/module

 

connected to correct terminals on module and pilot assembly.

makes noise, but no

 

 

B. Loose connections or electrical

Verify no loose connections or electrical shorts in wiring from mod-

spark.

 

shorts in the wiring.

ule to pilot assembly. Verify connections underneath pilot assembly

 

 

are tight; also verify connections are not grounding out to metal

 

 

chassis, pilot burner, pilot enclosure, mesh screen if present, or any

 

 

other metal object.

 

 

 

 

C. Ignitor gap is too large.

Verify gap of igniter to right side of pilot hood. The gap should be

 

 

approximately .17 in. or 1/8 in. (3 mm).

 

 

 

 

D. Module.

Turn ON/OFF rocker switch or wall switch to OFF position. Remove

 

 

ignitor wire “I” from module. Place a grounded wire about 3/16 in. (5

 

 

mm) away from “I” terminal on module. Place ON/OFF rocker switch

 

 

or wall switch in ON position. If there is no spark at “I” terminal module

 

 

must be replaced. If there is a spark at “I” terminal, module is fine.

 

 

Inspect pilot assembly for shorted sparker wire or cracked insulator

 

 

around electrode. Replace pilot if necessary.

 

 

 

2. Pilot won’t light,

A. No power or transformer installed

Verify that transformer is installed and plugged into module. Check

there is no noise or

incorrectly.

voltage of transformer under load at spade connection on module

spark.

 

with ON/OFF switch in ON position. Acceptable readings of a good

 

 

transformer are between 3.2 and 2.8 volts AC.

 

 

 

 

B. A shorted or loose connection in

Remove and reinstall the wiring harness that plugs into module.

 

wiring configuration or wiring har-

Verify there is a tight fit. Verify pilot assembly wiring to module. Re-

 

ness.

move and verify continuity of each wire in wiring harness. Replace

 

 

any damaged components.

 

 

 

 

C. Improper wall switch wiring.

Verify that 110/VAC power is “ON” to junction box.

 

 

 

 

D. Module not grounded.

Verify black ground wire from module wire harness is grounded to

 

 

metal chassis of appliance.

 

 

 

 

E. Module.

Turn ON/OFF rocker switch or wall switch to OFF position. Remove

 

 

ignitor wire “I” from module. Place ON/OFF rocker switch or wall

 

 

switch in ON position. If there is no spark at “I” terminal module

 

 

must be replaced. If there is a spark at “I” terminal, module is fine.

 

 

Inspect pilot assembly for shorted sparker wire or cracked insulator

 

 

around electrode.

 

 

 

3. Pilot sparks, but

A. Gas supply.

Verify that incoming gas line ball valve is “open”. Verify that inlet

Pilot will not light.

 

pressure reading is within acceptable limits, inlet pressure must not

 

 

exceed 14 in. W.C.

 

 

 

 

B. Ignitor gap is too large.

Verify gap of igniter to right side of pilot hood. The gap should be

 

 

approximately .17 in. or 1/8 in. (3 mm).

 

 

 

 

C. Module is not grounded.

Verify module is securely grounded to metal chassis of appliance.

 

 

 

 

D. Module voltage output / Valve/Pilot

Verify battery voltage is at least 2.7 volts. Replace batteries if volt-

 

solenoid ohms readings.

age is below 2.7.

 

 

 

64

Heat & Glo • SL-750TRSFHHIPI2156-900 Rev. F • 11/08

Image 64
Contents HOT Surfaces What to do if you smell gasHot glass will cause burns Homeowner Reference Information CongratulationsXxxxxxxx Table of Contents User GuideAppliance Setup TroubleshootingFinishing Reference MaterialsCONDITIONS, Exclusions & Limitation of Liability Limited Lifetime Warranty Listing and Code Approvals Installation of Carbon Monoxide Detectors Requirements for the Commonwealth of MassachusettsOperating Instructions User Guide Gas Fireplace SafetyYour Fireplace Fixed Glass Assembly Remote Controls, Wall Controls and Wall SwitchesFan Kit optional Clear SpaceLighting Instructions IPI Final inspection byWhat to do if YOU Smell GAS GAS ValveIssue Solutions Frequently Asked QuestionsAfter Fireplace is Lit Maintenance and Service Maintenance Tasks-HomeownerGlass Cleaning Remote ControlMaintenance Tasks-Qualified Service Technician Gasket Seal and Glass Assembly InspectionVenting LogsEither cobrahead or SIT Getting Started Typical Appliance SystemDesign and Installation Considerations Tools and Supplies NeededInspect Appliance and Components Any such action may cause a fire hazardFraming and Clearances Selecting Appliance LocationConstructing the Appliance Chase ClearancesMantel and Wall Projections TOP ViewTermination Locations Vent Termination Minimum Clearances= Area Where Terminal is not Permitted = Vent Terminal = AIR Supply InletVent Information and Diagrams Approved PipeVent Table Key Use of ElbowsUse of Flex Vent In. ClearanceMinimum Maximum Top Vent Horizontal Termination Two Elbows SL-750TRSFHHIPITop Vent Horizontal Termination Three Elbows V1 Minimum H1 Maximum H1 + H2 Maximum V1 + V2 MinimumTop Vent Vertical Termination No Elbow = 60 ft. Max .3 m Exhaust restrictor InstructionsTop Vent Vertical Termination Two 90º Elbows Minimum Maximum + V 2 MinimumTop Vent Vertical Termination Three 90º Elbows H1+ H2 Maximum V1 + V2 MinimumTop Vent Vertical Termination Four 90º Elbows V1 Min H1 Max V2 Min H2 Max V3 MinH1 Maximum V1 Minimum H1 + H2 Maximum Rear Vent Vertical Termination One Elbow Rear Vent Horizontal Termination Three ElbowsH1 Maximum V1 Minimum H2+ H3 H1+ H2+ H3 Maximum H1+ H2 Maximum V1 Minimum Rear Vent Vertical Termination Two ElbowsH1 Maximum V1 Minimum H1 + H2 Vent Clearances and Framing Pipe Clearances to CombustiblesWall Penetration Framing Combustible Wall PenetrationInstall the Ceiling Firestop Pipe DVP SLPFlat Ceiling Installation Install Attic Insulation ShieldVaulted Ceiling Installation Appliance Preparation Top VentRear Vent Cut the metal retaining band and fold the sides outSecuring and Leveling the Appliance 13 Proper Positioning and Securing of an ApplianceInstalling Vent Pipe DVP and SLP Pipe Attach Vent to the Firebox AssemblyAssemble Vent Sections DVP Pipe Only Assemble Pipe SectionsAssemble Vent Sections SLP Pipe Only Assemble Slip SectionsSecure the Vent Sections Disassemble Vent SectionsInstall Decorative Ceiling Components SLP only Install Metal Roof Flashing Assemble and Install Storm CollarInstall RF4-8 SLP-FSInstall Decorative Wall Components SLP only Install Vertical Termination CapHeat Shield Requirements for Horizontal Termination Ansi Z223.1 and CAN/CGA-B149 installation codes Install Horizontal Termination Cap DVP and SLP PipeRefer to of this manual Gas Information Fuel ConversionGas Pressure Gas ConnectionWiring Requirements Intellifire Ignition System WiringOptional Accessories Requirements Electrical InformationElectrical Service and Repair With battery back-upJunction Box Installation Wall Switch Installation for Fan OptionalFinishing To install the Splatter GuardSplatter Guard To Close the Lower Access Panel To Remove the Splatter Guard14 Wall Projection Acceptable on one side of opening Facing Material 16 Facing MaterialsDoors TemplateElevated Hearth Systems Appliance Setup Step Install RefractoryStep Install the Log Assembly LOG NotchesNotch Install Trim and/or Surround Air Shutter SettingSymptom Possible Cause Corrective Action TroubleshootingIntellifire Ignition System Ues to spark, and main Reference Materials Appliance Dimension DiagramLocation Inches Millimeters Vent Components Diagrams DVP vent componentsDVP-TRAP Horizontal Termination CapRF6M RF12M BEK DVP-BEK2COOL-ADD DVP-TRAPFLDVP-TV SLP-HRC-SS SLP-HRC-ZC-SS Horizontal Termination CAP DVP-HRC-SS DVP-HRC-ZC-SS Horizontal Termination CAPDVP-TB1 Elbow Extended Heat ShieldRF4-8 Roof Flashing Ceiling FirestopWall Thimble-Black Snorkel Black Support Box-BlackAdapter Log Set Assembly Service PartsService Parts List At DepotIPI Valve Assembly Contact Information