|
|
| Section 1: Set Up and Assembly |
Clearance Diagrams - 30” Metro | Dim | 30" Metro | |
|
| A1 | 28 3/4" (73cm) |
|
| to front of stove | |
|
|
| |
|
| A2 | 31 1/4" (79 cm) |
|
| to edge of oven door handle | |
|
|
| |
|
| B | 36 1/8" (92cm) |
|
| C | 29 3/4" (76cm) |
|
| D | 17 1/2" (45cm) |
|
| E1 | standard 40 5/8" (103cm) |
|
| E2 | low profile: 38" (97cm) |
|
| E3 | high back w/shelf: |
|
| 56 1/8" (143cm) | |
|
|
| |
Clearances | Figure 1 |
| Table 1 |
|
|
|
•Oven door vents must be 2" from any combustible. Door vents are required on Metro units to allow oven door ventilation.
•Minimum distance between the range and a side wall above the cooking top surface is 6” (see dim "O" in Table 2 below)
Electrical requirements:
•Electrical hookup must be done by a licenced electrician
•240 Volts 60Hz 4.1 kW three prong plug for U.S. and four prong for Canadian installations. (5
Gas Requirements:
•Gas
•Pressure requirements: Natural gas: 6” W.C. (min); LP gas: 11” W.C. (min)
• Connection: 1/2” NPT • 5/8” minimum diameter flex line.
•An accessible manual shut off valve must be installed at the appliance.
•Natural Gas/Propane Conversion kits are available - must be done by a licensed gas fitter
For proper performance a 450 CFM vent hood is required on all 30" Legacy ranges to en- sure adequate and proper ventilation. For su- perior ventilation we recommend using a 36” hood, how- ever a 30” hood is adequate.
Anti Tip Bracket: When properly in- stalled, will pre- vent stove from
bracket included with every stove.
Dim | 30" Metro |
G | Maximum 26"" (66cm) |
Q
tipping forward if downward force is applied to an open door.
H | 36" (92.5cm) | |
|
| |
I | 10" (25cm) | |
|
| |
J | 30 3/4" (78cm) | |
| * | |
K | 5 5/8"(14.5cm) | |
|
| |
L | 2" (5cm) | |
|
| |
M | 15" (38cm) | |
|
| |
N | 10" (51cm) | |
|
| |
O | 6" (15cm) min left and right side | |
|
| |
P | 13" (33cm) | |
|
| |
Q | SPECIFY WIDTH OF HOOD | |
|
| |
R | 24" (61 cm) | |
|
| |
S | 30" min to 36" max | |
for standard and high back guard | ||
| ||
|
| |
S1 | 30" min to | |
| for low profile back guard only | |
|
| |
T | 18" (45cm) |
P
T |
R
O
G S S 1
N
KJ
Gas Inlet
L
I
Edges of counter top
m ust be finished
cupboard depth m ust not exceed
H26”
M
Note: If range must stand beside a refrigerator, it is important for proper air circulation.There must be at least 5” (125 mm) of space between the two appliances.
*U.S. models only: J=30 1/4”
Table 2 | Figure 2 | 5 |