Honeywell L7248A,C,L LED Error Codes Aquastat EnviraCOM, Cause/Action Alarm, Check Action

Page 10

L7224A,C; L7248A,C,L OIL ELECTRONIC AQUASTAT® CONTROLLERS

.

Table 8. Controller Operating Sequence with External Low Limit device connected trough the ZR terminal.

Action

System Response

Zone Request (ZR) terminal is connected to

Boiler temperature is checked. Burner starts when water temperature

L1 (External Low Limit call for heat).

is below High Limit setting. Circulator turns off.

 

 

Boiler temperature exceeds the High Limit.

Burner is turned off. Burner restarts when the water temperature

 

drops below the High Limit setting minus the Differential.

Zone Request input is de-energized (External Burner is turned off.

Low Limit is satisfied).

Table 9. L7224 Controller Operating Sequence with Domestic Hot Water connected trough the ZR terminal.

Action

System Response

Zone Request (ZR) terminal is connected to

Boiler temperature is checked. Burner starts when water temperature

L1 (Domestic Hot Water calls for heat).

is below High Limit setting.

 

 

Boiler temperature exceeds the High Limit.

Burner is turned off. Burner restarts when the water temperature

 

drops below the High Limit setting minus the Differential.

 

 

Zone Request input is de-energized

Burner is turned off.

(Domestic Hot Water is satisfied).

 

 

 

Table 10. LED Error Codes.

Aquastat

 

EnviraCOM

Error Code

Cause/Action

Alarm

 

 

 

Err1

Aquastat sensor fault; check water sensor.

18

 

 

 

Err2

ECOM fault; check EnviraCOM™ wiring.

18

 

 

 

Err3

Excessive electrical noise or frequency out of range. Hardware fault; replace controller.

18, 58

 

 

 

Err4

B1 fault; check B1 wiring/voltage.

64

 

 

 

Err5

Low Line; check L1-L2, 110 Vac.

59

 

 

 

Err6a

Warning: Fuse; check ECOM wires, replace fuse.

92

Err7

Warning: EEPROM, HL, LL, Hdf, Ldf; reset to default values.

N/A

 

 

 

Err 8b

Repeated B1 fault (voltage present at B1 when output is turned off); check B1 wiring/voltage.

25

Err9a

Warning: Outdoor Reset System failure; communication to Outdoor Reset Module lost,

50, 53, 149

 

Outdoor Reset Module failure, multiple outdoor temperature sensors detected on the bus, or

 

 

outdoor temperature sensor failure. Check EnviraCOM wiring (1, 2, 3), check sensor wiring.

 

 

 

 

Err 10a

Warning: Boost Failure; Boost Mode active at least once per cycle for the last 60 consecutive

150

 

cycles. Check Outdoor Reset curve settings.

 

Err 11a

DHW Module/Sensor failure; communication to DHW Module lost, DHW Module failure, or

146, 147,

 

temperature sensor failure. Check EnviraCOM wiring (1, 2, 3), check sensor wiring.

148

aWarnings are generated to enunciate the system is not operating optimally, but the Aquastat is still operating and maintaining boiler temperature. In the instance where an Outdoor Reset Module is used, the warnings may indicate a reset curve setting error one or more features is not running optimally, and the Aquastat is reverting to default settings or has stopped running the Outdoor Reset algorithms. The warnings are cleared when the issue(s) is resolved.

bTo clear Err 8 condition, depress and hold all three user keys simultaneously for 60 seconds. Err 8 condition clears and display returns to normal. Err 8 condition is designed to catch welded relays on the Aquastat and will normally only occur near end of life for the control. If Err 8 condition has occurred early in the controls life, be sure to check for voltage feedback to B1 when B1 should be off and check current draw on b terminal to be sure oil burner is not draw- ing excessive current. Err 8 condition will keep repeating if B1 fault is not cleared.

Table 11. Troubleshooting Guide

System

Diagnostic

 

 

Condition

Condition

Check

Action

 

 

 

 

Boiler is cold,

Display is OFF.

120 Vac System power.

Turn system power on.

house is cold.

 

 

 

Display is ON.

24 Vac T-T

No 24 V; replace control.

 

 

 

 

 

 

24 V present; disconnect

Boiler starts, check wiring and thermostat.

 

 

thermostat, short T-T.

 

 

 

 

 

 

 

120 Vac at B1-B2

If no, replace control.

 

 

 

If yes, check burner and wiring.

 

 

 

 

 

 

Refer to Err on display.

 

 

 

 

68-0281EFS—05

10

Image 10
Contents DOE Compliance and Operation SpecificationsApplication Environmental RatingsWhen Installing this Product InstallationMounting Flush-Mounted Aquastat Replacement New InstallationWell-Mounted Aquastat Replacement Operation WiringReplacement Sensor Installation FuseDisplay Adjusting SettingsAdjustable Features DefinitionHigh Limit Controller Anti Short-Cycle FeatureOperation Low Limit and Circulator ControllerTroubleshooting CheckoutLine Voltage Indirect Tank Aquastat Time is applied, see Table Zone Request ZR terminal is connected toMinute Troubleshooting Guide System LED Error Codes Aquastat EnviraCOMCause/Action Alarm Check ActionSet ELL to On for External Low Limit see ConditionIf no 120 Vac, replace control If no 120 Vac, check C1-C2 see aboveTH9421C L7248L multizone system with circulator connections Outdoor Domestic HOT Reset Module L7248L External Low Limit connections Automation and Control Solutions Tion Caractéristiques TechniquesCaractéristiques électriques HomologationsLors de linstallation du produit MontageNouvelle installation Serrer fermement la vis de lattacheInstallation du capteur de rechange Les modèles à montage horizontalFusible CâblageFonctionnement GénéralAfficheur RéglagesTableau 3. Caractéristiques réglables Régulateur de Limite basse et de circulateur FonctionnementRégulateur Limite haute Tableau 4. Définitions de la lecture de laffichageProtection contre le gel Fonction Anti-court cycleZR Demande deau chaude domestique Fonctionnement de la purge thermiqueLimite de température de purge VérificationDépannage Thermique Taux de chute de température de purgeCycles expire une fois la demande en chaleur satisfaite Le thermostat fait une demande de chaleurMinute ou si le délai de purge thermique tPt a expiré La température de la chaudière dépasse laDiaire de la borne ZR Action Réponse du système Médiaire de la borne ZR Action Réponse du systèmeCodes derreur DEL AlarmeCondition liée Système Au diagnostic Vérifier Action Aquastat Cause/Action EnviraCOMPompe La chaudière Lafficheur est 120 V c.a. à C1-C2Est chaude, la Remplacer le régulateurL7224A,C système multizones avec connexions du circulateur Capteur ’EXTÉRIEUR Circulateur L7228l système multizones avec connexions du circulateur ’EXTÉRIEUR Domestique Solutions de régulation et d’automatisation Clasificación eléctrica AplicaciónespecificacionesCumplimiento y funcionamiento de acuerdo con el DOE Parámetros ambientalesCuando instale este producto InstalaciónMontaje Instalación nueva InstalaciónInstalación del sensor de reemplazo Reemplazo del Aquastat montado a rasReemplazo del Aquastat montado en cilindro Desconecte la energía eléctrica yCableado FuncionamientoPantalla Ajuste de las configuracionesTabla 3. Características regulables Tabla 4. Definiciones de la lectura de la pantalla Controlador de límite mínimo y circulador FuncionamientoControlador de límite máximo Función de ciclo anticortoLocalización Y Solución DE Problemas VerificaciónÓrdenes de calefacción del Configuración de límiteSi corresponde Condiciones de error TermostatoRendimiento del sistema disminuirá Condición de errorEl error desaparece automáticamente Más de 60 segundosReinicio exterior Err 11a Emite una orden de calefacción MáximoCableado de B1 Err9a 148 EnviraCOM 1, 2, 3, verifique el cableado del sensorTabla 11. Guía de localización y solución de problemas Condición de Sistema Diagnóstico Verificación AcciónSensor Circulador Módulo DE Aquastat DEL Reinicio Exterior Tanque Indirecto ELL=OFF Apagado Panel DE Reproducción Automatización y control desenlace