L7224A,C; L7248A,C,L OIL ELECTRONIC AQUASTAT® CONTROLLERS
.
Table 8. Controller Operating Sequence with External Low Limit device connected trough the ZR terminal.
Action | System Response |
Zone Request (ZR) terminal is connected to | Boiler temperature is checked. Burner starts when water temperature |
L1 (External Low Limit call for heat). | is below High Limit setting. Circulator turns off. |
|
|
Boiler temperature exceeds the High Limit. | Burner is turned off. Burner restarts when the water temperature |
| drops below the High Limit setting minus the Differential. |
Zone Request input is
Low Limit is satisfied).
Table 9. L7224 Controller Operating Sequence with Domestic Hot Water connected trough the ZR terminal.
Action | System Response |
Zone Request (ZR) terminal is connected to | Boiler temperature is checked. Burner starts when water temperature |
L1 (Domestic Hot Water calls for heat). | is below High Limit setting. |
|
|
Boiler temperature exceeds the High Limit. | Burner is turned off. Burner restarts when the water temperature |
| drops below the High Limit setting minus the Differential. |
|
|
Zone Request input is | Burner is turned off. |
(Domestic Hot Water is satisfied). |
|
|
|
Table 10. LED Error Codes.
Aquastat |
| EnviraCOM |
Error Code | Cause/Action | Alarm |
|
|
|
Err1 | Aquastat sensor fault; check water sensor. | 18 |
|
|
|
Err2 | ECOM fault; check EnviraCOM™ wiring. | 18 |
|
|
|
Err3 | Excessive electrical noise or frequency out of range. Hardware fault; replace controller. | 18, 58 |
|
|
|
Err4 | B1 fault; check B1 wiring/voltage. | 64 |
|
|
|
Err5 | Low Line; check | 59 |
|
|
|
Err6a | Warning: Fuse; check ECOM wires, replace fuse. | 92 |
Err7 | Warning: EEPROM, HL, LL, Hdf, Ldf; reset to default values. | N/A |
|
|
|
Err 8b | Repeated B1 fault (voltage present at B1 when output is turned off); check B1 wiring/voltage. | 25 |
Err9a | Warning: Outdoor Reset System failure; communication to Outdoor Reset Module lost, | 50, 53, 149 |
| Outdoor Reset Module failure, multiple outdoor temperature sensors detected on the bus, or |
|
| outdoor temperature sensor failure. Check EnviraCOM wiring (1, 2, 3), check sensor wiring. |
|
|
|
|
Err 10a | Warning: Boost Failure; Boost Mode active at least once per cycle for the last 60 consecutive | 150 |
| cycles. Check Outdoor Reset curve settings. |
|
Err 11a | DHW Module/Sensor failure; communication to DHW Module lost, DHW Module failure, or | 146, 147, |
| temperature sensor failure. Check EnviraCOM wiring (1, 2, 3), check sensor wiring. | 148 |
aWarnings are generated to enunciate the system is not operating optimally, but the Aquastat is still operating and maintaining boiler temperature. In the instance where an Outdoor Reset Module is used, the warnings may indicate a reset curve setting error one or more features is not running optimally, and the Aquastat is reverting to default settings or has stopped running the Outdoor Reset algorithms. The warnings are cleared when the issue(s) is resolved.
bTo clear Err 8 condition, depress and hold all three user keys simultaneously for 60 seconds. Err 8 condition clears and display returns to normal. Err 8 condition is designed to catch welded relays on the Aquastat and will normally only occur near end of life for the control. If Err 8 condition has occurred early in the controls life, be sure to check for voltage feedback to B1 when B1 should be off and check current draw on b terminal to be sure oil burner is not draw- ing excessive current. Err 8 condition will keep repeating if B1 fault is not cleared.
Table 11. Troubleshooting Guide
System | Diagnostic |
|
|
Condition | Condition | Check | Action |
|
|
|
|
Boiler is cold, | Display is OFF. | 120 Vac System power. | Turn system power on. |
house is cold. |
|
|
|
Display is ON. | 24 Vac | No 24 V; replace control. | |
|
|
|
|
|
| 24 V present; disconnect | Boiler starts, check wiring and thermostat. |
|
| thermostat, short |
|
|
|
|
|
|
| 120 Vac at | • If no, replace control. |
|
|
| • If yes, check burner and wiring. |
|
|
|
|
|
| Refer to Err on display. | — |
|
|
|
|
10 |