Honeywell L7224A,C, L7248A,C,L installation instructions Condition, If no 120 Vac, replace control

Page 11

L7224A,C; L7248A,C,L OIL ELECTRONIC AQUASTAT® CONTROLLERS

Table 11. Troubleshooting Guide

System

Diagnostic

 

 

Condition

Condition

Check

Action

 

 

 

 

Boiler is hot,

Display is ON.

120 Vac at C1-C2

120 Vac at C1-C2, check wiring to pump.

house is cold.

 

 

Wiring OK, is pump running?

 

 

 

If not, replace the pump.

 

 

 

If pump is running, check for trapped air or

 

 

 

closed zone valves.

 

 

 

 

 

 

Boiler below the Low Limit

 

 

temperature, wait for boiler to go

 

 

 

above Low Limit temperature.

 

 

 

 

 

 

 

Boiler above LL? If yes, check for

If no 120 Vac, replace control.

 

 

120 Vac between ZC and L2.

If yes, check zone relays, circulators and

 

 

 

wiring.

 

 

 

 

 

 

ELL setting (L7248L only)

Set ELL to Off for multizone system (see Fig.

 

 

 

11).

 

 

 

Set ELL to On for External Low Limit (see

 

 

 

Fig. 13).

 

 

 

 

 

 

Boiler above LL? If yes, check 120

If no 120 Vac, check C1-C2 (see above).

 

 

Vac at ZR-L2 (only L7248L with

If yes, check the External Low Limit control.

 

 

ELL set On)

 

 

 

 

 

Boiler is hot,

Display is ON.

Boiler Demand signal from the

24 Vac on T-T (or 0 Vac on ZR-L2), check

no hot potable

 

water heater (either 120 Vac at

wiring to water heater

water.

 

ZR-L2, or 0 Vac on T-T; depends

Wiring OK, check the water heater

 

 

on installation and “duu” setting)

 

 

 

 

 

 

 

“duu” setting

Set duu to ON if 120 Vac water heater

 

 

 

demand is connected to ZR

 

 

 

Set duu to OFF if open/closed water heater

 

 

 

demand is connected to T-T

 

 

 

 

 

 

Check DHW Module and DHW

DHW Module not properly connected and/or

 

 

Sensor

DHW Sensor improperly positioned

 

 

 

 

ZONE 2

TO ADDITIONAL R845A

 

 

RELAYS FOR OTHER ZONES

 

CIRCULATOR

 

 

 

 

 

1

L1

L7224

 

L2 (HOT)

R845A RELAY ZONE 2

 

 

6

 

 

 

5

 

 

 

3

 

SENSOR

 

 

 

 

4

 

 

 

1

 

 

ZR

 

 

L1

 

 

LINE

2

 

 

 

VOLTAGE

L2

 

 

CIRCULATOR

C2

 

ZONE 2

 

 

 

 

 

LOW VOLTAGE

 

B2

 

THERMOSTAT

 

 

 

 

1 POWER SUPPLY. PROVIDE DISCONNECT

LINE

C1

 

MEANS AND OVERLOAD

VOLTAGE

B1

PROTECTION AS REQUIRED.

OIL BURNER

 

RELAY

ZC

 

 

 

 

 

2 CONTROL CASE MUST BE CONNECTED

 

 

TO EARTH GROUND. USE GROUNDING

 

 

SCREW PROVIDED.

 

 

 

 

LOW

 

VOLTAGE

2

THERMOSTAT

T

T 3

2

1

LINE

M27115

Fig. 9. L7224A,C multizone system with circulator connections.

11

68-0281EFS—05

Image 11
Contents Environmental Ratings SpecificationsApplication DOE Compliance and OperationMounting InstallationWhen Installing this Product Well-Mounted Aquastat Replacement New InstallationFlush-Mounted Aquastat Replacement Fuse WiringReplacement Sensor Installation OperationDefinition Adjusting SettingsAdjustable Features DisplayLow Limit and Circulator Controller Anti Short-Cycle FeatureOperation High Limit ControllerCheckout TroubleshootingLine Voltage Indirect Tank Aquastat Minute Zone Request ZR terminal is connected toTime is applied, see Table Check Action LED Error Codes Aquastat EnviraCOMCause/Action Alarm Troubleshooting Guide SystemIf no 120 Vac, check C1-C2 see above ConditionIf no 120 Vac, replace control Set ELL to On for External Low Limit seeTH9421C L7248L multizone system with circulator connections Outdoor Domestic HOT Reset Module L7248L External Low Limit connections Automation and Control Solutions Homologations Caractéristiques TechniquesCaractéristiques électriques TionMontage Lors de linstallation du produitSerrer fermement la vis de lattache Nouvelle installationLes modèles à montage horizontal Installation du capteur de rechangeGénéral CâblageFonctionnement FusibleTableau 3. Caractéristiques réglables RéglagesAfficheur Tableau 4. Définitions de la lecture de laffichage FonctionnementRégulateur Limite haute Régulateur de Limite basse et de circulateurFonctionnement de la purge thermique Fonction Anti-court cycleZR Demande deau chaude domestique Protection contre le gelThermique Taux de chute de température de purge VérificationDépannage Limite de température de purgeLa température de la chaudière dépasse la Le thermostat fait une demande de chaleurMinute ou si le délai de purge thermique tPt a expiré Cycles expire une fois la demande en chaleur satisfaiteMédiaire de la borne ZR Action Réponse du système Diaire de la borne ZR Action Réponse du systèmeAquastat Cause/Action EnviraCOM AlarmeCondition liée Système Au diagnostic Vérifier Action Codes derreur DELRemplacer le régulateur La chaudière Lafficheur est 120 V c.a. à C1-C2Est chaude, la PompeL7224A,C système multizones avec connexions du circulateur Capteur ’EXTÉRIEUR Circulateur L7228l système multizones avec connexions du circulateur ’EXTÉRIEUR Domestique Solutions de régulation et d’automatisation Parámetros ambientales AplicaciónespecificacionesCumplimiento y funcionamiento de acuerdo con el DOE Clasificación eléctricaMontaje InstalaciónCuando instale este producto Instalación Instalación nuevaDesconecte la energía eléctrica y Reemplazo del Aquastat montado a rasReemplazo del Aquastat montado en cilindro Instalación del sensor de reemplazoFuncionamiento CableadoTabla 3. Características regulables Ajuste de las configuracionesPantalla Tabla 4. Definiciones de la lectura de la pantalla Función de ciclo anticorto FuncionamientoControlador de límite máximo Controlador de límite mínimo y circuladorVerificación Localización Y Solución DE ProblemasTermostato Configuración de límiteSi corresponde Condiciones de error Órdenes de calefacción delMás de 60 segundos Condición de errorEl error desaparece automáticamente Rendimiento del sistema disminuirá148 EnviraCOM 1, 2, 3, verifique el cableado del sensor Emite una orden de calefacción MáximoCableado de B1 Err9a Reinicio exterior Err 11aCondición de Sistema Diagnóstico Verificación Acción Tabla 11. Guía de localización y solución de problemasSensor Circulador Módulo DE Aquastat DEL Reinicio Exterior Tanque Indirecto ELL=OFF Apagado Panel DE Reproducción Automatización y control desenlace