L7224A,C; L7248A,C,L OIL ELECTRONIC AQUASTAT® CONTROLLERS
Table 11. Troubleshooting Guide
System | Diagnostic |
|
|
Condition | Condition | Check | Action |
|
|
|
|
Boiler is hot, | Display is ON. | 120 Vac at | • 120 Vac at |
house is cold. |
|
| • Wiring OK, is pump running? |
|
|
| • If not, replace the pump. |
|
|
| • If pump is running, check for trapped air or |
|
|
| closed zone valves. |
|
|
|
|
|
| Boiler below the Low Limit | — |
|
| temperature, wait for boiler to go |
|
|
| above Low Limit temperature. |
|
|
|
|
|
|
| Boiler above LL? If yes, check for | • If no 120 Vac, replace control. |
|
| 120 Vac between ZC and L2. | • If yes, check zone relays, circulators and |
|
|
| wiring. |
|
|
|
|
|
| ELL setting (L7248L only) | • Set ELL to Off for multizone system (see Fig. |
|
|
| 11). |
|
|
| • Set ELL to On for External Low Limit (see |
|
|
| Fig. 13). |
|
|
|
|
|
| Boiler above LL? If yes, check 120 | • If no 120 Vac, check |
|
| Vac at | • If yes, check the External Low Limit control. |
|
| ELL set On) |
|
|
|
|
|
Boiler is hot, | Display is ON. | Boiler Demand signal from the | • 24 Vac on |
no hot potable |
| water heater (either 120 Vac at | wiring to water heater |
water. |
| • Wiring OK, check the water heater | |
|
| on installation and “duu” setting) |
|
|
|
|
|
|
| “duu” setting | • Set duu to ON if 120 Vac water heater |
|
|
| demand is connected to ZR |
|
|
| • Set duu to OFF if open/closed water heater |
|
|
| demand is connected to |
|
|
|
|
|
| Check DHW Module and DHW | • DHW Module not properly connected and/or |
|
| Sensor | DHW Sensor improperly positioned |
|
|
|
|
ZONE 2 | TO ADDITIONAL R845A |
|
| |
RELAYS FOR OTHER ZONES |
| |||
CIRCULATOR |
| |||
|
|
| ||
| 1 | L1 | L7224 | |
| L2 (HOT) | |||
R845A RELAY ZONE 2 |
|
| ||
6 |
|
|
| |
5 |
|
|
| |
3 |
| SENSOR |
| |
|
|
| ||
4 |
|
|
| |
1 |
|
| ZR | |
|
| L1 | ||
|
| LINE | ||
2 |
|
| ||
| VOLTAGE | L2 | ||
|
| CIRCULATOR | C2 | |
| ZONE 2 |
| ||
|
|
| ||
| LOW VOLTAGE |
| B2 | |
| THERMOSTAT |
| ||
|
|
| ||
1 POWER SUPPLY. PROVIDE DISCONNECT | LINE | C1 | ||
| ||||
MEANS AND OVERLOAD | VOLTAGE | B1 | ||
PROTECTION AS REQUIRED. | OIL BURNER |
| ||
RELAY | ZC | |||
|
| |||
|
|
| ||
2 CONTROL CASE MUST BE CONNECTED |
|
| ||
TO EARTH GROUND. USE GROUNDING |
|
| ||
SCREW PROVIDED. |
|
|
|
| LOW |
| VOLTAGE |
2 | THERMOSTAT |
T
T 3
2
1
LINE
M27115
Fig. 9. L7224A,C multizone system with circulator connections.
11 |