Honeywell L7224A,C, L7248A,C,L installation instructions Checkout, Troubleshooting

Page 7

L7224A,C; L7248A,C,L OIL ELECTRONIC AQUASTAT® CONTROLLERS

NOTE: This feature is blocked if a Domestic Hot Water demand occurs. Domestic Hot Water demands are serviced immediately, without any delay.

NOTE: When the Aquastat is connected to the oil primary and/or thermostat via the EnviraCOM bus, the Anti Short-Cycle time does not apply to recycle events such as loss of airflow or flame. It applies only to loss of demand.

ZR-Domestic Hot Water (DHW) Request

The ZR terminal can be selected to service an indirect water heater heat request. This parameter is set via the 3 digit display (see Adjusting Settings section of this document). A heat request via the ZR terminal will have priority over all other features such as the Anti Short- Cycle feature or those enabled by the Outdoor Reset Module (See form #69-2335 for more information).

Frost Protection

The Frost Protection function protects the boiler and potentially the boiler plumbing from possible damage which may occur should the water in the system begin to freeze. The Frost Protection feature is enabled only in the L7248 (cold start models). The feature default setting is enabled (ON), but can be disabled using the 3-digit display. See “Adjusting Settings” on page 5.

When the Boiler temperature drops to the Frost Protection Limit temperature (fixed 40 °F), the burner is forced on. The Circulator and ZC outputs remain in the same state as before the Frost Protection function was enabled. They can be either ON or OFF during the Frost Protection cycle.

When the Boiler temperature reaches the Frost Protection Limit temperature plus a fixed 10 °F differential, the burner is turned off unless requested to stay on due to a different demand.

Thermal Purge Operation

The intent of thermal purge is to insure usable residual heat in the boiler is circulated until it is sufficiently depleted from the system before the burner is allowed to fire. To that end, on a call for heat, the burner is held off while the circulator runs until the boiler temperature drops to the thermal purge temperature or a time delay is exceeded. Both of these parameters are adjustable. When the boiler temperature reaches the thermal purge temperature, the burner is allowed to fire. Thermal purge is only applied to cold start Aquastat models (L7248) and will not interfere with domestic hot water call for heat or boilers equipped with Honeywell outdoor reset accessories. For warm start models where a Low Limit must be set, thermal purge is not applied.

In addition to the thermal purge temperature and thermal purge time delay parameters, two other conditions release the Aquastat from thermal purge in order to maintain comfort in the space:

The boiler temperature has dropped 10 °F from the beginning of the thermal purge.

Boiler temperature is cooling at a rate greater than 5 °F/minute while the circulator is running.

The thermal purge feature applies to single zone as well as multi-zone applications.

Thermal Purge Settings

Some thermal purge parameters are configurable using the 3 digit display. See “Adjusting Settings” on page 5. Thermal purge may be disabled by setting the thermal purge temperature limit to "OFF".

Table 5. Thermal Purge Settings.

 

 

 

 

Parameter name

Minimum value

Maximum Value

Default

 

 

 

 

 

 

 

 

Boiler temperature drop

Not adjustable

Not adjustable

10 °F

 

 

 

 

Thermal purge temperature limit

120 °F (or OFF)

160 °F

140 °F (L7248)

 

 

 

 

Thermal purge temperature rate of drop

Not adjustable

Not adjustable

5 °F/minute

 

 

 

 

Thermal purge time delay

1 minute

10 minutes

2 minutes

 

 

 

 

Thermal Purge and Domestic Hot Water

The thermal purge feature is automatically disabled whenever there is a call for domestic hot water from the Zr terminal to ensure hot water is available in a timely manner. See “ZR-Domestic Hot Water (DHW) Request” on page 7.

Pump Cycling

The Pump Cycling feature exercises the system pump for 15 seconds after a non-adjustable five day period of no boiler activity. The Pump Cycling feature default setting is enabled (ON) but can be disabled (OFF) using the 3-digit display. See “Adjusting Settings” on page 5.

CHECKOUT

Put the system into operation and observe at least one complete cycle to make sure that the controller operates properly. See TROUBLESHOOTING section to use LED to assist in determining system operation.

TROUBLESHOOTING

When attempting to diagnose system performance, reference to the LED display can help to identify specific areas not working properly. The LED display will scroll Err, followed by a digit (1-8). Refer to Table 10 and 11 for a description of each error and suggested actions.

7

68-0281EFS—05

Image 7
Contents Environmental Ratings SpecificationsApplication DOE Compliance and OperationWhen Installing this Product InstallationMounting Flush-Mounted Aquastat Replacement New InstallationWell-Mounted Aquastat Replacement Fuse WiringReplacement Sensor Installation OperationDefinition Adjusting SettingsAdjustable Features DisplayLow Limit and Circulator Controller Anti Short-Cycle FeatureOperation High Limit ControllerCheckout TroubleshootingLine Voltage Indirect Tank Aquastat Time is applied, see Table Zone Request ZR terminal is connected toMinute Check Action LED Error Codes Aquastat EnviraCOMCause/Action Alarm Troubleshooting Guide SystemIf no 120 Vac, check C1-C2 see above ConditionIf no 120 Vac, replace control Set ELL to On for External Low Limit seeTH9421C L7248L multizone system with circulator connections Outdoor Domestic HOT Reset Module L7248L External Low Limit connections Automation and Control Solutions Homologations Caractéristiques TechniquesCaractéristiques électriques TionMontage Lors de linstallation du produitSerrer fermement la vis de lattache Nouvelle installationLes modèles à montage horizontal Installation du capteur de rechangeGénéral CâblageFonctionnement FusibleAfficheur RéglagesTableau 3. Caractéristiques réglables Tableau 4. Définitions de la lecture de laffichage FonctionnementRégulateur Limite haute Régulateur de Limite basse et de circulateurFonctionnement de la purge thermique Fonction Anti-court cycleZR Demande deau chaude domestique Protection contre le gelThermique Taux de chute de température de purge VérificationDépannage Limite de température de purgeLa température de la chaudière dépasse la Le thermostat fait une demande de chaleurMinute ou si le délai de purge thermique tPt a expiré Cycles expire une fois la demande en chaleur satisfaiteMédiaire de la borne ZR Action Réponse du système Diaire de la borne ZR Action Réponse du systèmeAquastat Cause/Action EnviraCOM AlarmeCondition liée Système Au diagnostic Vérifier Action Codes derreur DELRemplacer le régulateur La chaudière Lafficheur est 120 V c.a. à C1-C2Est chaude, la PompeL7224A,C système multizones avec connexions du circulateur Capteur ’EXTÉRIEUR Circulateur L7228l système multizones avec connexions du circulateur ’EXTÉRIEUR Domestique Solutions de régulation et d’automatisation Parámetros ambientales AplicaciónespecificacionesCumplimiento y funcionamiento de acuerdo con el DOE Clasificación eléctricaCuando instale este producto InstalaciónMontaje Instalación Instalación nuevaDesconecte la energía eléctrica y Reemplazo del Aquastat montado a rasReemplazo del Aquastat montado en cilindro Instalación del sensor de reemplazoFuncionamiento CableadoPantalla Ajuste de las configuracionesTabla 3. Características regulables Tabla 4. Definiciones de la lectura de la pantalla Función de ciclo anticorto FuncionamientoControlador de límite máximo Controlador de límite mínimo y circuladorVerificación Localización Y Solución DE ProblemasTermostato Configuración de límiteSi corresponde Condiciones de error Órdenes de calefacción delMás de 60 segundos Condición de errorEl error desaparece automáticamente Rendimiento del sistema disminuirá148 EnviraCOM 1, 2, 3, verifique el cableado del sensor Emite una orden de calefacción MáximoCableado de B1 Err9a Reinicio exterior Err 11aCondición de Sistema Diagnóstico Verificación Acción Tabla 11. Guía de localización y solución de problemasSensor Circulador Módulo DE Aquastat DEL Reinicio Exterior Tanque Indirecto ELL=OFF Apagado Panel DE Reproducción Automatización y control desenlace