L7224A,C; L7248A,C,L OIL ELECTRONIC AQUASTAT® CONTROLLERS
SENSOR WIRES
BOILER
IMMERSION SENSOR
WELL
M22026
WIRING
WARNING
Electrical Shock Hazard.
Can cause serious injury or death.
Disconnect power supply before making wiring connections to prevent electrical shock or equipment damage.
All wiring must comply with local electrical codes and ordinances. Do not exceed the specifications in the Application section when wiring this control. Use wire rated for 194 °F (90 °C) or higher.
Fig. 4. Replacement sensor installation.
Replacement Sensor Installation
Turn off all power and:
1. | Carefully disconnect sensor from circuit board by |
2. | pulling gently on the connector. |
Gently pull sensor from thermo well and through cir- | |
3. | cuit board by pulling on leadwires. |
Carefully align replacement sensor with hole in cir- | |
| cuit board and guide through Aquastat case and |
4. | into well. (See Fig. 5). |
Make sure sensor is fully seated to bottom of well | |
| (See Fig. 4). Use a small pencil to measure depth of |
IMPORTANT
The terminals on these Aquastat Controllers are approved for use with copper wire only.
Follow the appropriate wiring diagrams shown on the inside of the front cover of the L7224A,C; L7248A,C,L or in Fig.
Refer to Fig. 6 for Connections for the optional Outdoor Reset Module and the Domestic Hot Water (DHW) module. In subsequent wiring diagrams these modules will be displayed with a dotted line signifying that they are optional.
5. | sensor in well, if necessary. |
Connect sensor to circuit board by pressing con- | |
| nector on sensor unit into mating connector on cir- |
6. | cuit board (See Fig. 5). |
For remote sensors | |
| trollers) be sure to use 121571AA Clamp (see |
| Accessories) to securely hold sensor in place. |
| THERMOSTAT | ENVIRACOMTM | |
| TERMINALS | TERMINALS | |
| T |
|
|
| T | 3 |
|
|
| 2 |
|
|
| 1 | DISPLAY |
ZR | LINE |
|
|
L1 |
|
|
|
|
|
| SENSOR |
| T |
|
| T | 3 |
|
| 2 |
|
| 1 |
ZR | LINE |
|
L1 |
|
|
L2 |
|
|
C2 |
|
|
B2 |
|
|
C1 |
|
|
B1 |
|
|
ZC |
|
|
OUTDOOR RESET MODULE
1 2 3 OT OT
C7089U1006
OUTDOOR
SENSOR
DOMESTIC HOT WATER MODULE
1 2 3 TS TS
TEMPERATURE SENSOR
M29651
L2 | CONNECTOR | |
C2 | RELAYS | |
B2 |
| |
C1 | SENSOR HOLES | |
B1 | ||
FUSE | ||
| ||
ZC |
| |
| M32187 |
Fig. 5. Circuit board, showing sensor connection and
well holes for vertical mount models.
Fuse
The 1 Amp fuse located near the transformer is intended to protect the EnviraCOM circuit from incorrect wiring. The Aquastat will continue to function should the fuse blow or be removed though no EnviraCOM communication will be possible on the bus and Err 6 will be displayed. See Table 10.
Fig. 6. Wiring the Outdoor Reset Module and the
Domestic Hot Water Module.
OPERATION
General
The L7224A,C and L7248A,C,L Oil Electronic Aquastat Controllers are primary safety
For boilers that do include a remotely (flush) mounted control, the wiring may be completed with conduit or routed behind the boiler sheet metal.
4 |