L7224A,C; L7248A,C,L OIL ELECTRONIC AQUASTAT® CONTROLLERS
A separate electromechanical
On the L7224 models, the High Limit, Low Limit, Low Limit Differential, and Anti
The overall range of the High Limit is from 130 °F to 240 °F (54 °C to 116 °C). Select devices may have different ranges. Some models have limited ranges on the High Limit setpoint; this limited range is listed on the device label.
Some models also have a Low Limit and Low Limit Differential adjustment. The range of the Low Limit is from 110 °F to 220 °F (43 °C to 104 °C). Select devices may have different ranges.
The Zr setting can be set to DHW, Zoning, or for tankless coil applications depending on the L7224/L7248.
If a W8735S1000 AquaReset™ Outdoor Reset Module is installed, the reset curve can be set by entering the minimum outdoor temperature, minimum (boiler) temperature, and maximum outdoor temperature on the
The L7224A,C and L7248A,C,L are designed for use with 24 Vac electronic and electromechanical thermostats or EnviraCOM™ enabled thermostats, and have
Adjusting Settings
To discourage unauthorized changing of Aquastat settings, a procedure to enter the ADJUSTMENT mode is required. To enter the ADJUSTMENT mode, press the UP, DOWN, and I buttons (Refer to Fig. 5) simultaneously for three seconds. Press the I button until the feature requiring adjustment is displayed:
| Table 3. Adjustable Features. |
|
|
Display | Definition |
HL_ | High Limit. |
|
|
Hdf | High Limit Differential. |
|
|
LL_ | Low Limit. (L7224A, C) |
|
|
Ldf | Low Limit Differential (L7224A, C) |
|
|
ELL | External Low Limit (L7248L only) |
|
|
duu | ZR input configured as external Domestic Hot |
| Water (DHW) request (ON/OFF) (L7224A,C/ |
| L7248L) |
|
|
ASC | Anti |
| disabled. |
|
|
otL* | Outdoor Temperature Low (minimum) |
| parameter for the outdoor reset curve (°F or °C) |
|
|
otH* | Outdoor Temperature High (maximum) |
| parameter for outdoor reset curve (°F or °C) |
|
|
btL* | Boiler Temperature Low (minimum) parameter |
| for outdoor reset curve |
|
|
bP* | Boost Period (minutes). “OFF” is displayed if |
| Boost is inactive |
|
|
bS* | Boost step (°F or °C) shown only if Boost is |
| active (bP=ON) |
|
|
UUS* | Warm Weather Shutdown Temperature |
| (°F or °C) |
|
|
tPL** | Thermal Purging Limit Temperature (°F or °C), |
| “OFF” if disabled |
|
|
tPt** | Termal Purging Time Delay (minutes), shown |
| only if tPL is enabled |
|
|
PC | Pump Cycling (ON / OFF) |
|
|
Temperature units (°F or °C) | |
|
|
*Settings available for adjustment on the
Module is installed.
**Settings available for adjustment only when the W8735S1000 AquaReset Outdoor Reset Kit is NOT installed.
Then press the UP and/or DOWN buttons to move the set point to the desired value, to change between °F and °C, or to enable (On) or disable (Off) the External Low Limit. After 60 seconds without any button inputs, the control will automatically return to the RUN mode.
Display
In the RUN mode, the Aquastat will flash “bt” (boiler temp) followed by the temperature (i.e., 220), followed by °F or °C.
To read boiler settings, press the I key to read the parameter of interest. For example, press I and High Limit (HL) is displayed, followed by a
After approximately 60 seconds without any key presses, the display will enter a dim display mode. To return to the bright display mode, simply press any key.