Honeywell L7248A,C,L Órdenes de calefacción del, Termostato, Terminó, Minuto, Diferencial

Page 44

CONTROLADORES ELECTRÓNICOS PARA ACEITE L7224A,C; L7248A,C,L AQUASTAT®

 

 

 

 

 

 

 

 

AQUASTAT DEL TANQUE INDIRECTO

MÓDULO DE

 

 

 

 

 

DE VOLTAJE DE LÍNEA

 

 

L1

 

 

 

 

 

 

 

 

 

 

 

 

REINICIO EXTERIOR

 

(CON CORRIENTE)

 

 

 

 

 

 

 

 

 

 

 

50022037-002

 

 

 

L1

 

 

 

 

 

 

 

 

 

CIRCULADOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(CON

 

 

 

 

 

 

 

 

 

DEL TANQUE

 

1 2 3 OT OT

 

1

 

CORRIENTE) L2

 

 

 

 

 

 

 

 

 

INDIRECTO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L2

SENSOR DE

 

 

2

EXTERIORES

 

T

 

C7089U

 

T

3

 

 

 

 

 

2

 

 

 

1

SENSOR

 

 

 

 

ZR

LINE

 

 

L1

 

 

CIRCULADOR

L2

 

 

DE VOLTAJE

 

 

DE LÍNEA

C2

 

 

 

 

 

 

B2

 

 

RELÉ DEL

C1

 

 

QUEMADOR

 

 

 

DE ACEITE

B1

 

 

DE VOLTAJE

 

 

 

DE LÍNEA

ZC

 

 

1 EL MÓDULO DE REINICIO EXTERIOR ES OPCIONAL.

2 PARA MEJOR DESEMPEÑO CONFIGURE DUU= ON (ENCENDIDO).

MS32023

Fig. 8. L7224A,C; L7248L de una sola zona de calor con tanque de agua indirecto y circuladores. Módulo de

reinicio exterior opcional.

Tabla 6. Secuencia de funcionamiento de los controladores L7224/L7248.

Acción

Respuesta del sistema

Órdenes de calefacción del

El circulador arranca cuando la temperatura del agua es superior a la configuración del

termostato.

límite inferior (si fuese pertinente) o superior al límite de temperatura de purga térmica

 

(tPL) si la función de purga térmica está habilitada. Se verifica la temperatura de la

 

caldera. El quemador se enciende cuando la temperatura del agua es inferior a la

 

configuración del límite máximo menos el diferencial o está en el límite de la

 

temperatura de purga térmica (tPL) o por debajo de él en calderas de arranque en frío si

 

el límite de temperatura de purga térmica está habilitado. Si el tPL está habilitado, el

 

quemador puede también encenderse si la temperatura de la caldera está

 

descendiendo a razón de 10 °F o más por minuto o si el retardo de purga térmica (tPt)

 

terminó.

 

Si se habilita el tiempo de ciclo anticorto, el quemador no se encenderá hasta que

 

transcurra el tiempo del ciclo anticorto configurado entre los ciclos, luego de que se

 

haya cumplido la orden de calefacción anterior.

 

 

La temperatura de la caldera

El quemador se apaga. El quemador se enciende nuevamente cuando la temperatura

supera el límite máximo.

del agua desciende por debajo de la configuración de límite máximo menos el

 

diferencial. Si la purga térmica está habilitada, el quemador se enciende bien cuando se

 

alcance el límite de temperatura de la purga térmica, el retardo de la purga térmica haya

 

terminado o el índice de enfriamiento de la temperatura de la caldera exceda de 10 °F/

 

minuto.

 

 

El termostato está a gusto.

El circulador y el quemador se apagan.

 

 

La temperatura de la caldera

El quemador se enciende y el circulador se apaga. El quemador se detiene cuando la

desciende por debajo de la

temperatura del agua supera la configuración de límite mínimo. El quemador se enciende

configuración de límite

cuando la temperatura del agua es inferior a la configuración de límite máximo menos el

mínimo menos el diferencial

diferencial.

(si corresponde).

 

 

 

Condiciones de error 1-5.

Si se detecta una condición de error, todas las salidas, excepto el ZC, se cierran. El

 

quemador está apagado. El controlador continúa funcionando y se enciende nuevamente

 

cuando el error se soluciona. Durante la secuencia de verificación del error, el sistema

 

controla si hay variaciones en el sensor o corrosión en las conexiones.

 

 

Condición de error 6.

La comunicación EnviraCOM no está disponible.

 

 

68-0281EFS—05

10

Image 44
Contents Specifications ApplicationDOE Compliance and Operation Environmental RatingsMounting InstallationWhen Installing this Product Well-Mounted Aquastat Replacement New InstallationFlush-Mounted Aquastat Replacement Wiring Replacement Sensor InstallationOperation FuseAdjusting Settings Adjustable FeaturesDisplay DefinitionAnti Short-Cycle Feature OperationHigh Limit Controller Low Limit and Circulator ControllerTroubleshooting CheckoutLine Voltage Indirect Tank Aquastat Minute Zone Request ZR terminal is connected toTime is applied, see Table LED Error Codes Aquastat EnviraCOM Cause/Action AlarmTroubleshooting Guide System Check ActionCondition If no 120 Vac, replace controlSet ELL to On for External Low Limit see If no 120 Vac, check C1-C2 see aboveTH9421C L7248L multizone system with circulator connections Outdoor Domestic HOT Reset Module L7248L External Low Limit connections Automation and Control Solutions Caractéristiques Techniques Caractéristiques électriquesTion HomologationsLors de linstallation du produit MontageNouvelle installation Serrer fermement la vis de lattacheInstallation du capteur de rechange Les modèles à montage horizontalCâblage FonctionnementFusible GénéralTableau 3. Caractéristiques réglables RéglagesAfficheur Fonctionnement Régulateur Limite hauteRégulateur de Limite basse et de circulateur Tableau 4. Définitions de la lecture de laffichageFonction Anti-court cycle ZR Demande deau chaude domestiqueProtection contre le gel Fonctionnement de la purge thermiqueVérification DépannageLimite de température de purge Thermique Taux de chute de température de purgeLe thermostat fait une demande de chaleur Minute ou si le délai de purge thermique tPt a expiréCycles expire une fois la demande en chaleur satisfaite La température de la chaudière dépasse laDiaire de la borne ZR Action Réponse du système Médiaire de la borne ZR Action Réponse du systèmeAlarme Condition liée Système Au diagnostic Vérifier ActionCodes derreur DEL Aquastat Cause/Action EnviraCOMLa chaudière Lafficheur est 120 V c.a. à C1-C2 Est chaude, laPompe Remplacer le régulateurL7224A,C système multizones avec connexions du circulateur Capteur ’EXTÉRIEUR Circulateur L7228l système multizones avec connexions du circulateur ’EXTÉRIEUR Domestique Solutions de régulation et d’automatisation Aplicaciónespecificaciones Cumplimiento y funcionamiento de acuerdo con el DOEClasificación eléctrica Parámetros ambientalesMontaje InstalaciónCuando instale este producto Instalación nueva InstalaciónReemplazo del Aquastat montado a ras Reemplazo del Aquastat montado en cilindroInstalación del sensor de reemplazo Desconecte la energía eléctrica yCableado FuncionamientoTabla 3. Características regulables Ajuste de las configuracionesPantalla Tabla 4. Definiciones de la lectura de la pantalla Funcionamiento Controlador de límite máximoControlador de límite mínimo y circulador Función de ciclo anticortoLocalización Y Solución DE Problemas VerificaciónConfiguración de límite Si corresponde Condiciones de errorÓrdenes de calefacción del TermostatoCondición de error El error desaparece automáticamenteRendimiento del sistema disminuirá Más de 60 segundosEmite una orden de calefacción Máximo Cableado de B1 Err9aReinicio exterior Err 11a 148 EnviraCOM 1, 2, 3, verifique el cableado del sensorTabla 11. Guía de localización y solución de problemas Condición de Sistema Diagnóstico Verificación AcciónSensor Circulador Módulo DE Aquastat DEL Reinicio Exterior Tanque Indirecto ELL=OFF Apagado Panel DE Reproducción Automatización y control desenlace