Honeywell L7224A,C installation instructions Application, Specifications, Environmental Ratings

Page 1

L7224A,C; L7248A,C,L

Oil Electronic

Aquastat® Controllers

INSTALLATION INSTRUCTIONS

APPLICATION

The L7224A,C and L7248A,C,L 2012 Compliant Oil Electronic Aquastat® Controllers provide electronic temperature sensing in a UL limit-rated control with a single sensing probe. The L7224A,C and L7248A,C,L control the circulator, oil burner and boiler temperature. The L7224/L7248 is “Outdoor Temperature Reset” ready which is enabled when connected to the W8735S1000 Outdoor Reset Kit. Outdoor Reset with the L7224/L7248 is intended for all applications except for tankless coil systems for domestic hot water. Compliance to 2012 DOE regulation ensures efficiency is maximized without interfering with domestic hot water demand.

The L7224A,C and L7248A,C,L replace the L8124A, L8124C, L7124A,C, L7148A and L8148A Controllers. The L7224A,C and L7248A,C,L series controls provide status and diagnostic information through an LED display combined with LED lights as well as EnviraCOM™ communications enabled thermostats and diagnostic tools to enhance the diagnostic process.

L7224/L7248 Aquastat Controllers are intended for use in residential-type applications.

IMPORTANT

Use of Outdoor Temperature Reset on a tank- less coil application requiring a Low Limit setting will result in reduced system effectiveness and efficiency.

SPECIFICATIONS

Electrical Ratings: Voltage: 120 Vac, 60 Hz.

Power: 7 VA maximum at 120 Vac plus external loads.

Thermostat current: 100 mA nominal at 24 Vac. Burner Relay:

7.4A at 120 Vac Full Load Amperage (FLA);

44.4A inrush Locked Rotor Amperage (LRA); Less Ignition Load: 360 VA.

Circulator Relay:

7.4A at 120 Vac FLA; 44.4 A inrush LRA. Zone Controller (ZC): 7.4 A at 120 Vac FLA;

44.4A inrush LRA.

NOTE: All loads combined cannot exceed 2000 VA.

Environmental Ratings:

Temperature: -30 °F to +150 °F (-34 °C to +66 °C).

Humidity: 0 to 95% relative humidity, noncondensing.

Approvals:

Underwriters Laboratories Inc. Component Recognized.

Canadian Underwriters Laboratories Inc. Component

Recognized.

2012 DOE Compliance and Operation

Operation of this control may delay the burner operation while the residual heat is circulated out of the boiler.

NOTE: This operation may be different than earlier electronic Aquastat® revisions which did not implement thermal purge.

68-0281EFS-05

Image 1
Contents Application SpecificationsDOE Compliance and Operation Environmental RatingsWhen Installing this Product InstallationMounting Flush-Mounted Aquastat Replacement New InstallationWell-Mounted Aquastat Replacement Replacement Sensor Installation WiringOperation FuseAdjustable Features Adjusting SettingsDisplay DefinitionOperation Anti Short-Cycle FeatureHigh Limit Controller Low Limit and Circulator ControllerCheckout TroubleshootingLine Voltage Indirect Tank Aquastat Time is applied, see Table Zone Request ZR terminal is connected toMinute Cause/Action Alarm LED Error Codes Aquastat EnviraCOMTroubleshooting Guide System Check ActionIf no 120 Vac, replace control ConditionSet ELL to On for External Low Limit see If no 120 Vac, check C1-C2 see aboveTH9421C L7248L multizone system with circulator connections Outdoor Domestic HOT Reset Module L7248L External Low Limit connections Automation and Control Solutions Caractéristiques électriques Caractéristiques TechniquesTion HomologationsMontage Lors de linstallation du produitSerrer fermement la vis de lattache Nouvelle installationLes modèles à montage horizontal Installation du capteur de rechangeFonctionnement CâblageFusible GénéralAfficheur RéglagesTableau 3. Caractéristiques réglables Régulateur Limite haute FonctionnementRégulateur de Limite basse et de circulateur Tableau 4. Définitions de la lecture de laffichageZR Demande deau chaude domestique Fonction Anti-court cycleProtection contre le gel Fonctionnement de la purge thermiqueDépannage VérificationLimite de température de purge Thermique Taux de chute de température de purgeMinute ou si le délai de purge thermique tPt a expiré Le thermostat fait une demande de chaleurCycles expire une fois la demande en chaleur satisfaite La température de la chaudière dépasse laMédiaire de la borne ZR Action Réponse du système Diaire de la borne ZR Action Réponse du systèmeCondition liée Système Au diagnostic Vérifier Action AlarmeCodes derreur DEL Aquastat Cause/Action EnviraCOMEst chaude, la La chaudière Lafficheur est 120 V c.a. à C1-C2Pompe Remplacer le régulateurL7224A,C système multizones avec connexions du circulateur Capteur ’EXTÉRIEUR Circulateur L7228l système multizones avec connexions du circulateur ’EXTÉRIEUR Domestique Solutions de régulation et d’automatisation Cumplimiento y funcionamiento de acuerdo con el DOE AplicaciónespecificacionesClasificación eléctrica Parámetros ambientalesCuando instale este producto InstalaciónMontaje Instalación Instalación nuevaReemplazo del Aquastat montado en cilindro Reemplazo del Aquastat montado a rasInstalación del sensor de reemplazo Desconecte la energía eléctrica yFuncionamiento CableadoPantalla Ajuste de las configuracionesTabla 3. Características regulables Tabla 4. Definiciones de la lectura de la pantalla Controlador de límite máximo FuncionamientoControlador de límite mínimo y circulador Función de ciclo anticortoVerificación Localización Y Solución DE ProblemasSi corresponde Condiciones de error Configuración de límiteÓrdenes de calefacción del TermostatoEl error desaparece automáticamente Condición de errorRendimiento del sistema disminuirá Más de 60 segundosCableado de B1 Err9a Emite una orden de calefacción MáximoReinicio exterior Err 11a 148 EnviraCOM 1, 2, 3, verifique el cableado del sensorCondición de Sistema Diagnóstico Verificación Acción Tabla 11. Guía de localización y solución de problemasSensor Circulador Módulo DE Aquastat DEL Reinicio Exterior Tanque Indirecto ELL=OFF Apagado Panel DE Reproducción Automatización y control desenlace