L7224A,C; L7248A,C,L OIL ELECTRONIC AQUASTAT® CONTROLLERS
Table 4. Display readout definitions.
Text | Description | Display |
Err | Error Code (if one is present) | |
|
|
|
bT | Boiler Temperature | |
|
|
|
HL | High Limit 1 | |
HdF | High Limit Differential | |
|
|
|
LL | Low Limit (L7224 only) | |
|
|
|
Ldf | Low Limit Differential (L7224 only) | |
|
|
|
tt | Local Thermostat Status | |
|
|
|
ttE | EnviraCOM Thermostat Status | |
|
|
|
brn | B1 (Burner) output (ON or OFF) | |
|
|
|
Cir | C1 (Circulator) output (ON or OFF) | |
|
|
|
ZC | ZC (Zone Control) output (ON or OFF) | |
|
|
|
Zr | ZR (Zone Request) Call for HEAT (ON or OFF) | |
|
|
|
ELL | External Low Limit Enabled (L7248L only) | |
|
|
|
duu | ZR Configured as Domestic Hot Water | |
| Request (L7224, L7248L only) |
|
ASC | Anti | |
|
|
|
bSP | Boiler | |
dhc | DHW Module Connected 3 (YES or NO) | |
ot | Outdoor Temperature 2 | |
otL | Outdoor Temperature Low 2 | |
otH | Outdoor Temperature High 2 | |
btL | Boiler Temperature Low 2 | |
bP | Boost Period 2 | |
bS | Boost Step 2 | |
UUS | Warm Weather Shutdown Temperature 2 | |
1Display shows local setting; not the setting as modified by an external enviracom control.
2Settings are viewable only if the outdoor reset module and out- door temperature sensor are installed and functioning properly.
3Settings are viewable only if the domestic hot water module and sensor are installed and functioning properly.
Operation
The L7224 and L7248 models can be in any of four operational states: Normal, High Limit, Low Limit and Error. The controller moves back and forth from
High Limit to Normal to Low Limit state as part of normal operation. Only devices having High Limit settings are restricted to the High Limit and Normal states. However, the controller will enter the Error state when there is an abnormal condition. The operating states are:
1.Normal: Boiler temperature went below the High Limit setting (minus the Differential) and has not exceeded the High Limit setting; or, the boiler temperature went above the Low Limit setting and
has not gone below the Low Limit setting (minus the Differential); or, ZR input is not powered with 120 Vac (only L7248L with ELL set On).
2.High Limit: Boiler temperature went above the High Limit setting and has not dropped below the High Limit setting (minus the Differential).
3.Low Limit: Boiler temperature went below the Low Limit setting (minus the Low Limit Differential) and has not gone above the Low Limit setting; or, ZR input is powered with 120 Vac (only L7248L with ELL set On).
4.Error: The controller has detected an error condition (e.g., open sensor) and has shut down the burner output. The ZC output is energized. The controller continues to monitor the system and automatically restarts if the error condition clears. Refer toTable 4.
The operating sequence for the L7224/L7248 is shown in Table
High Limit Controller
The High Limit opens and turns off the burner when the water temperature reaches the setpoint. The High Limit automatically resets after the water temperature drops past the setpoint and through the Differential. The L7248 models have High Limit Differential presets of 15 °F
(8 °C). The L7224 models have High Limit Differential presets of 10 °F (6 °C).
Low Limit and Circulator
Controller
On a temperature rise, with the adjustable Differential at the default setting of 10 °F (6 °C), the burner circuit breaks and the circulator circuit makes (assuming no call for heat is present) at the Low Limit setpoint. On a temperature drop of 10 °F (6 °C) below the Low Limit setpoint, the burner circuit makes and the circulator circuit breaks. See Fig. 7.
SWITCH BREAKS ON
TEMPERATURE RISE.
BURNER TURNS OFF.
HIGH LIMITCIRCULATOR OPERATES
SETTING ON A CALL FOR HEAT.
L7224: 10°F (6°C) |
| |
DIFFERENCE | SWITCH MAKES ON | |
L7248: 15°F (8°C) | ||
DIFFERENCE | TEMPERATURE FALL. | |
| BURNER OPERATES ON A | |
| CALL FOR HEAT. | |
LOW LIMIT | WITH NO HEATING | |
SETTING | ||
10ºF (6ºC) | DEMAND, SWITCH BREAKS | |
ON TEMPERATURE RISE. 1 | ||
DIFFERENCE | ||
| SWITCH MAKES ON | |
| TEMPERATURE FALL, | |
| BURNER IS ON TO | |
| MAINTAIN MINIMUM | |
| WATER TEMPERATURE. | |
| CIRCULATOR IS OFF. |
1WHEN WATER REACHES LOW LIMIT SETTING, THE BURNER SHUTS OFF OR THE CIRCULATOR PUMP STARTS (WHEN CALLING FOR HEAT).
M23364
Fig. 7. Setpoints and differentials.
Anti Short-Cycle Feature
The Anti