Tracker controller specifications
Tracker controller specifications
Table 1 shows the specifications for the Tracker controller.
Table 1. Tracker Controller specifications
Specification |
|
|
| Description | |
|
| ||||
Power | 24 Vac nominal (19 Vac to 30 Vac), | ||||
| 50/60 Hz, 1 phase 40 VA minimum, | ||||
| UL Class 2 transformer required | ||||
|
| ||||
Operating environ- | From 32°F to 122°F (0°C to 50°C) | ||||
ment | 10% to 90% relative humidity, | ||||
|
| ||||
Storage environment | From | ||||
| 5% to 95% relative humidity, | ||||
|
| ||||
Cabinet | NEMA 1 resin | ||||
|
| ||||
Mounting | Flat wall surface with one of the following recessed | ||||
| conduit boxes: |
| |||
| 2 in. × 4 in. | (5.08 cm × 10.15 cm) | |||
| 4 in. × 4 in. | (10.15 cm × 10.15 cm) | |||
|
|
|
| ||
Dimensions | Height: | 8.75 in. | (22.38 cm) | ||
| Width: | 10.25 in. | (26.04 cm) | ||
| Depth: | 2.75 in. | (6.99 cm) | ||
|
|
|
| ||
Weight | 2.5 lb | (1.13 kg) |
| ||
|
|
| |||
Analog input | 10 kΩ at 77°F (25°C) |
| |||
• Thermistor | From | ||||
|
|
|
| ||
|
| ||||
Binary inputs | |||||
• Utility pulse meter | voltage of 12 Vdc nominal (10 Vdc to 14 Vdc) at | ||||
12 mA nominal (10 mA to 14 mA). | |||||
• Priority shutdown | |||||
|
|
|
| ||
|
| ||||
Binary output | |||||
• Alarm relay | contact rated at 24 Vac, 0.5 A maximum | ||||
|
|
|
| ||
|
| ||||
Memory backup | At power loss, the system backs up memory and | ||||
| stores all data for seven days. After seven days, | ||||
| trends and alarms are not retained. | ||||
|
| ||||
Approvals | See Appendix B, Declaration of Conformity. | ||||
|
|
|
|
|
| 9 |